1747-SDN DeviceNet Scanner Module User Manual: C - 1747-SDN Module Firmware History

Pages 129 to 132 of 160, from 1747-SDN DeviceNet Scanner Module User Manual

The original document is the PDF (3.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1747-SDN

Page 129

Appendix

C

1747-SDN Module Firmware History

Purpose

This section describes enhancements, corrected anomalies and other important information for this revision and previous revisions of the 1747-SDN module firmware.

Revision 8.002

The 1747-SDN series C module includes these firmware enhancements. • Embedded EDS file - The module contains its own electronic data sheet (EDS) file within its firmware. This allows RSNetWorx for DeviceNet software, 5.0 or later, to upload and register the EDS file directly from the scanner. In previous versions, you had to locate the EDS file on a website and manually install it. • AutoScan - This feature automatically sets up communication with the devices on your DeviceNet network. You no longer have to use RSNetWorx for DeviceNet software to map the devices into a scanlist. The 1747-SDN series C module includes all features provided in the series B module.

Revisions 7.005 and 7.006 Known Anomalies

Firmware revisions 7.005 and 7.006 contain the following known anomalies: • Inability to flash update the module if connections to all slave devices are not made. The module displays a 98 error. • Certain application programs (ladder programs) may cause the SLC controller to fault due to exceeded shared memory lock time. The SLC controller displays a 57 error. The module does not display an error. • Internal performance changes may cause timing dependant applications to fail. • Saving ADR data may cause the module to fault upon next power cycle. The module displays a E9 error. Upon next power cycle, the scanlist and configuration data defaults to out of box values.

129

Publication 1747-UM655B-EN-P - June 2007

Page 130

130

1747-SDN Module Firmware History

• If a slave in the scanlist does not match the identity of the slave at that address on the network, the module does not communicate with that slave again. After the mismatch is resolved, you have to cycle power to the module to reestablish communication. If you have not experienced any of these anomalies and want to flash upgrade this module to firmware revision 7.006, please contact Rockwell Automation Technical Support at 440-646-3223.

Revision 6.002

This section describes the enhancements and corrected anomalies for firmware revision 6.002.

Electronic Data Sheet Requirement The 6.002 firmware revision of the module requires the latest EDS file for RSNetWorx for DeviceNet software. If the software displays the device as an unknown device, then you must download the latest EDS file. You can get the latest EDS file online at: http://www.ab.com/networks/eds. Follow these steps once you are at this location. 1. Click DeviceNet. 2. Enter the catalog number: 1747-SDN. 3. Enter Major Revision: 6. 4. Enter the Minor Revision: 2. 5. Click Search.

Publication 1747-UM655B-EN-P - June 2007

Page 131

1747-SDN Module Firmware History

131

Enhancements This section describes the enhancements to the firmware.

Enhanced Explicit Message Pass-through Capability With the 6.002 firmware revision, the size of the M0/M1 file could be expanded to 395 words. This can accommodate a larger pass-through message than previous firmware revisions. For example, this enhanced capability now allows DeviceNet PanelView terminal downloads.

M1 File Includes Device Active Table Section With this revision, words 206…209 in the M1 file are now used for the Device Active Table. The scanner assigns one bit in consecutive order to consecutive device addresses starting at node 0 at M1.S.206/0. If a bit is set, it indicates that the node is in the scanner’s scanlist and has successfully communicated with the module. The bit is reset if the scanner tries to communicate to the node but the node has gone offline.

Immediate Input/Output With this revision, the scanner will act upon immediate input and output instructions (IIM, IOM) from the SLC 500 programmable controller.

Corrected Anomalies

Anomaly

Description

Reset I/O run bit in scanner copy of I/O during transition to processor Program mode.

This would prevent immediate change from Idle to Run mode before the I/O scan of the processor when the processor transitions to Run mode. This anomaly has been corrected.

Unwanted information from a previous connection remained when the former connection timed out while waiting for a fragment ack.

This prevented a new connection from being established since the connection state was incorrect. This anomaly has been corrected.

Check for error after setting EPR on slave connection.

If a device state conflict error is returned by a slave when the EPR bit is set, the scanner would not report the error. This anomaly has been corrected.

Publication 1747-UM655B-EN-P - June 2007

Page 132

132

1747-SDN Module Firmware History

Revision 5.001

This section describes the enhancements for firmware revision 5.001.

Enhancement The following enhancement was made to the firmware for this revision.

Scanlist Commit in Run/Idle Mode With the 5.001 firmware revision, with the module in Idle mode, the scanlist can be committed to the module’s memory while the programmable controller is in Run mode.

Revision 4.026

This section describes the enhancements for firmware revision 4.026.

Enhancement The following enhancement was made to the firmware for this revision.

Electronic Keying With the 4.026 firmware revision, electronic keying was enhanced to include major and minor revision checking.