Page 10
10 ControlLogix ControlNet Interface Module
Identify Module Features Refer to the figure Module Features to identify the hardware components of the 1756-CNB and 1756-CNBR modules.
Module Features Network Address Switches
Module Status Alphanumeric Display ControlNet Network Channel Status Indicators
Module Status Indicator
Network Access Port
Channel B
BNC Connector (1756-CNBR only)
Channel A BNC Connector
Front View
Publication 1756-IN604A-EN-P - February 2006
Side View
Backplane Connector
Page 11
ControlLogix ControlNet Interface Module 11
Set the Module’s Network Address Switches Use your fingers or a small screwdriver to set the module’s network address switches. For modules in a standalone chassis, you must specify a unique ControlNet network address; for modules in a redundant chassis, you must specify the same address for the secondary module that you specified for the corresponding primary module. Top of Module
Front of Module
Side of Module
This module’s network address is 23.
TIP
You can select an address of 01 to 99 for modules in a standalone chassis or 01 to 98 for modules in redundant chassis. 00 is an invalid ControlNet network address.
Publication 1756-IN604A-EN-P - February 2006
Page 12
12 ControlLogix ControlNet Interface Module
Prepare the Chassis for Module Installation Before you install the module, you must install and connect a ControlLogix chassis and power supply. A 4-slot chassis with a power supply is shown in the figure Chassis and Power Supply.
Chassis and Power Supply
Power Supply
Chassis
For information on installing these products, refer to the table Chassis Installation Publications. Chassis Installation Publications Chassis Type
Chassis Installation
Power Supply
Power Supply Installation
Series B 1756-A4 1756-A7 1756-A10 1756-A13
Publication 1756-IN080
1756-PA72/B
Publication 1756-5.67
1756-PB72/B 1756-PA75/A 1756-PB75/A
Publication 1756-IN604A-EN-P - February 2006
Publication 1756-5.78
Page 13
ControlLogix ControlNet Interface Module 13
Determine Module Slot Location The figure Chassis Slot Numbering shows chassis slot numbering in a 4-slot chassis. Slot 0 is the first slot and is always the leftmost slot in the rack (the first slot to the right of the power supply). You can use any size ControlLogix chassis and install the module in any slot. You can also install multiple 1756-CNB and 1756-CNBR modules in the same chassis. You can install as many modules as your power supply can accommodate (such as the number for which the power supply is rated). IMPORTANT
If you plan to install a redundant system, you must place the primary and redundant modules in the same corresponding slot in their respective chassis. For example, if you place a 1756-CNBR module in slot 3 (from the left) in the primary chassis, you must also place a 1756-CNBR module in slot 3 in the redundant chassis.
Chassis Slot Numbering Slot 2
Slot 0 Slot 1
Slot 3
Power Supply
Chassis
Publication 1756-IN604A-EN-P - February 2006
Page 14
14 ControlLogix ControlNet Interface Module
Install or Remove the Module Under Power You can install or remove the module while chassis power is applied if you observe the following precautions. WARNING
When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.
Publication 1756-IN604A-EN-P - February 2006
Page 15
ControlLogix ControlNet Interface Module 15
Install the Module Align the circuit board with top and bottom guides in the chassis.
Slide the module into the chassis. Make sure the module backplane connector properly connects to the chassis backplane
Circuit Board
The module is properly installed when it is flush with the power supply or other installed modules.
ATTENTION
Do not force the module into the backplane connector. If you cannot seat the module with firm pressure, check the alignment. Forcing the module into the chassis can damage the backplane connector or the module.
Publication 1756-IN604A-EN-P - February 2006
Page 16
16 ControlLogix ControlNet Interface Module
Remove the Module Upper Tab
Push on the upper and lower tabs to disengage them. Then slide the module out of the chassis.
If you are replacing an existing module with an identical one, and you want to resume identical system operation, you must install the new module with the same ControlNet address in the same slot.
Publication 1756-IN604A-EN-P - February 2006
Page 17
ControlLogix ControlNet Interface Module 17
Connect the Module to the Network You can connect the module to the ControlNet network using a tap (1786-TPR, 1786-TPS, 1786-TPYR, or 1786-TPYS) or a network access cable (1786-CP). WARNING
TIP
If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Use the 1786-CP cable for temporary connections, such as programming software. For permanent connections, use a tap.
The following figure shows an example ControlNet network using redundant media. 1756-CNBR Module (in a 1756-A4 chassis)
ControlNet Network Node
ControlNet Link Redundant Media (optional)
ControlNet Node
Publication 1756-IN604A-EN-P - February 2006
Page 18
18 ControlLogix ControlNet Interface Module When connecting the module to a ControlNet network, you should also refer to the following documentation: • ControlNet Coax Tap Installation Instructions, publication 1786-5.7 • ControlNet Cable System Planning and Installation Manual, publication CNET-IN002 TIP
For network connections we recommend taps with a straight connector (1786-TPS or 1786-TPYS) because of the location of the BNC connectors on the bottom of the module.
Publication 1756-IN604A-EN-P - February 2006