The text of a manual · part 3 of 4
ControlLogix ControlNet Interface Module Installation Instructions, Catalog Numbers 1756-CNB, 1756-CNBR, Series E, pages 19 to 27
Pages 19 to 27 of 36
The original document is the PDF (685 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-CNB
Page 19
ControlLogix ControlNet Interface Module 19
Connect to the Network with a Tap Perform the following steps to connect the module to the network using a tap. 1. Remove and save the dust caps from the ControlNet network taps. ATTENTION
Do not allow any metal portions of the tap to contact any conductive material. If you disconnect the tap from the module, place the dust cap back on the straight or right-angle connector to prevent the connector from accidentally contacting a metallic grounded surface.
Segment 1
Segment 2 1756-CNB - Segment 1 1756-CNBR - Segments 1 and 2
Dust Cap
Dust Cap
2. Connect the tap’s straight or right-angle connector to the module’s BNC connector. If Your Node Supports
Connect The Tap’s Connector nonredundant media 1756-CNB to the channel A connector on the module redundant media
• from trunkline A to channel A on the 1756-CNBR
(channel B on the 1756-CNBR is not used)(1)
• from trunkline B to channel B on the 1756-CNBR (1)
While both channels are active, Rockwell recommends using channel A for nonredundant media.
Publication 1756-IN604A-EN-P - February 2006
Page 20
20 ControlLogix ControlNet Interface Module
IMPORTANT
To prevent inadvertent reversal of the tap connections (resulting in incorrect status displays requiring troubleshooting), check the tap drop cable for the label indicating the attached segment before making your connection. To work properly, when you use modules in a redundant control chassis pair, the primary and redundant partner modules must be connected to the same network segment. If you are using redundant media, connect the channel of each partner to the same network segment.
Segment 1 Segment 2 A
Tap
B
Tap
Publication 1756-IN604A-EN-P - February 2006
A
Tap
Page 21
ControlLogix ControlNet Interface Module 21 3. Apply power to the module and check module status. Use the following flowchart as a guide.
Turn the chassis power supply on.
Module status indicator red?
See the Troubleshoot section.
No
Yes Module performs a power-on self-test initialization.
Modules are in a redundant control chassis pair. WAIT SRM
OR
INIT
Module status indicator red?
No
Initialization is complete. The status indicator blinks green.
Yes INIT has failed, and the module displays an error message. Refer to Troubleshoot section.
Replace the module.
Channel A and B indicators display the network condition as listed on page 28.
Channel A and B indicators alternately flash.
Module status displays OK?
No
See the Troubleshoot section.
Yes Module is functional and operating. OK A#xx
Publication 1756-IN604A-EN-P - February 2006
Page 22
22 ControlLogix ControlNet Interface Module
Connect a Programming Terminal to the Network with a 1786-CP Cable To connect a programming terminal to the network using a 1786-CP cable, you have the following options: • Use a 1784-KTC, 1784-KTCx, or 1784-PCC communication card and a 1786-CP cable: 1756-CNBR
1784-KTC, KTCx, PCIC, or PCC Card
1786-CP Cable
ControlNet Link
IMPORTANT
To work properly, the primary and redundant partner module must be connected to the same network segment. If you are using redundant media, connect the channel of each partner to the same network segment.
• Use a 1770-KFC communication interface, a serial or parallel connection, and a 1786-CP cable: 1756-CNBR 1770-KFC 1786-CP Cable
Serial or Parallel Connections
ControlNet Link
Publication 1756-IN604A-EN-P - February 2006
Page 23
ControlLogix ControlNet Interface Module 23 The 1786-CP cable can be plugged into any ControlNet network product’s network access port (NAP) to provide programming capability on the ControlNet network. A programming terminal connected through this cable is counted as a node and must have a unique network address. ATTENTION
Use a 1786-CP cable when connecting a programming terminal to the network through network access port (NAP). Using a commercially available RJ-style cable could result in network failure.
Troubleshoot the Module The 1756-CNB and 1756-CNBR modules have the diagnostic indicators as shown: 1756-CNB
1756-CNBR Module Status Display - See Pages 24 to 27. Module Status Indicator See Pages 24 to 27.
ControlNet Channel Status Indicators - See Page 28.
Channel A BNC Connector Channel B BNC Connector
Publication 1756-IN604A-EN-P - February 2006
Page 24
24 ControlLogix ControlNet Interface Module
Interpret the Module Status Indicator and Display The Module Status Indicator LED and Module Status Display table provide diagnostic information. Module Status Indicator LED and Module Status Display LED
Display Cause
OK
Off
None
Red
Msg scrolls(1)
BPA# ERR
BPRX ERR
BPIC
ERR
The module is not communicating due to a power supply fault or internal fault.
Action
1. Check the power supply. 2. Check the cable connectors. 3. Make sure the module is firmly seated in the chassis. 4. If the indicator remains off, replace the module. The module’s network address is 1. (Optional, see page 12.) Turn chassis power supply off. set to 00, an invalid ControlNet 2. Remove the module from the network address, or 99, an chassis. invalid ControlNet network 3. Set the network address address if you are using switches to a unique address redundant control. See footnote (01-99, or 01-98 if redundant control) at end of table. 4. Install the module in the chassis. 5. If off, turn chassis power supply on. The module detected a different Replace the chassis or module. slot address from that latched in at power-up. Excessive noise on the backplane causes this error. There are too many CRC errors Replace the module. being generated by the multicast backplane receiver, so the backplane multicast receivers have been shut off. There is a hardware fault Replace the module. within the module.
CNIC
ERR
Publication 1756-IN604A-EN-P - February 2006
Page 25
ControlLogix ControlNet Interface Module 25 Module Status Indicator LED and Module Status Display LED
Display Cause
OK
Red
DUPL NODE
RACK ERR STOP
WAIT SRM(2) Flashing BOOT Red ROM UPDT SNGL KPR!
Action
For a redundant system this may 1. (For redundant systems only.) Wait 10 seconds; if the be a temporary condition during condition persists, perform the chassis switchover. Otherwise, following steps: the module’s network address is 2. (Optional, see page 12.) the same as another module’s on Turn chassis power supply off. the link. 3. Remove the module from the chassis. 4. Set the network address switches to a unique address (01-99). 5. Install the module in the chassis. 6. If off, turn chassis power supply on. Cannot read backplane EEPROM, Replace the chassis. or rack/slot address incorrect The module commanded to stop Remove nonredundancy compliant functioning by the redundancy module from redundant secondary module. This occurs when a chassis and replace with nonredundancy compliant redundancy compliant module. module is placed into a redundant secondary chassis. The module waiting for the None required. redundancy module to complete power-up. The module has invalid Update module firmware with firmware. ControlFlash Update Utility. Flash update is in progress. None required.
The module detected that it has been connected to a ControlNet 1.5 (single-keeper) network.
Update the module’s firmware at MAC ID 01 and reschedule the network.
Publication 1756-IN604A-EN-P - February 2006
Page 26
26 ControlLogix ControlNet Interface Module Module Status Indicator LED and Module Status Display LED
Display
OK
Green
OK INIT BW >MAX
CMPT(2) DSNP(2)
PwDS(2) PwQg(2) PwQS(2) PwNS(2)
Qfng(2) QS(2) SW ERR
Cause
Action
Normal operation The module is initializing. The module is receiving too much network traffic and connections are timing out. The network bandwidth has been exceeded. The secondary module is compatible with its partner. The secondary module is disqualified with no partner.
None required
The module is primary with a disqualified secondary partner. The module is primary with a qualifying secondary partner. The module is primary with a qualified secondary partner. The module is primary with no secondary partner. The secondary module is qualifying. The secondary module is qualified. The node address switch changed after power-up.
Publication 1756-IN604A-EN-P - February 2006
None (temporary condition). If this happens frequently, add another 1756-CNB or 1756-CNBR and split the traffic between them. None required. Check corresponding slot of primary chassis for type and revision of module. Check the type and revision of the 1756-CNB module. Redundant system status. No action required.
Check corresponding slot of secondary chassis for correct module. Redundant system status. No action required.
None required, but we recommend that you either return switches to their original settings or replace the module, since this could indicate a latent hardware problem.
Page 27
ControlLogix ControlNet Interface Module 27 Module Status Indicator LED and Module Status Display LED
Display
OK
Flashing CNFG Green ERR NET
ERR Green or SO_1(2) Off SO_2(2) SO_3(2) SN_1(2) SN_2(2) SN_3(2) ?Cpt(2) !Cpt(2) (1)
Cause
Action
ControlNet network configuration error. Network cabling error or no other active nodes on network.
Recheck configuration. Re-check your network cabling and make sure another node on the network is active (online). If the display shows any message for more than three seconds, then the module failed during transition from one redundancy phase to another. Replace one or both redundancy modules.
Old primary switchover phase 1 in progress. Old primary switchover phase 2 in progress. Old primary switchover phase 3 in progress. New primary switchover phase 1 in progress. New primary switchover phase 2 in progress. New primary switchover phase 3 in progress. the module has not determined if it is compatible. the module has determined that Replace the module with correct it is not compatible. type and revision.
If switches are set to 00 the display scrolls: “FAULT: ADDRESS SWITCHES = 00, ILLEGAL” If switches are set to 99 in a redundant chassis, the display scrolls: “FAULT: ADDRESS SWITCHES = 99, ILLEGAL IN REDUNDANT SYSTEM”
(2)
Messages are for redundant control. These messages will be available in Series E firmware version 11.xx.
Publication 1756-IN604A-EN-P - February 2006