Page 19

ControlLogix ControlNet Interface Module 19

Connect to the Network with a Tap Perform the following steps to connect the module to the network using a tap. 1. Remove and save the dust caps from the ControlNet network taps. ATTENTION

Do not allow any metal portions of the tap to contact any conductive material. If you disconnect the tap from the module, place the dust cap back on the straight or right-angle connector to prevent the connector from accidentally contacting a metallic grounded surface.

Segment 1

Segment 2 1756-CNB - Segment 1 1756-CNBR - Segments 1 and 2

Dust Cap

Dust Cap

2. Connect the tap’s straight or right-angle connector to the module’s BNC connector. If Your Node Supports

Connect The Tap’s Connector nonredundant media 1756-CNB to the channel A connector on the module redundant media

• from trunkline A to channel A on the 1756-CNBR

(channel B on the 1756-CNBR is not used)(1)

• from trunkline B to channel B on the 1756-CNBR (1)

While both channels are active, Rockwell recommends using channel A for nonredundant media.

Publication 1756-IN604A-EN-P - February 2006

Page 20

20 ControlLogix ControlNet Interface Module

IMPORTANT

To prevent inadvertent reversal of the tap connections (resulting in incorrect status displays requiring troubleshooting), check the tap drop cable for the label indicating the attached segment before making your connection. To work properly, when you use modules in a redundant control chassis pair, the primary and redundant partner modules must be connected to the same network segment. If you are using redundant media, connect the channel of each partner to the same network segment.

Segment 1 Segment 2 A

Tap

B

Tap

Publication 1756-IN604A-EN-P - February 2006

A

Tap

Page 21

ControlLogix ControlNet Interface Module 21 3. Apply power to the module and check module status. Use the following flowchart as a guide.

Turn the chassis power supply on.

Module status indicator red?

See the Troubleshoot section.

No

Yes Module performs a power-on self-test initialization.

Modules are in a redundant control chassis pair. WAIT SRM

OR

INIT

Module status indicator red?

No

Initialization is complete. The status indicator blinks green.

Yes INIT has failed, and the module displays an error message. Refer to Troubleshoot section.

Replace the module.

Channel A and B indicators display the network condition as listed on page 28.

Channel A and B indicators alternately flash.

Module status displays OK?

No

See the Troubleshoot section.

Yes Module is functional and operating. OK A#xx

Publication 1756-IN604A-EN-P - February 2006

Page 22

22 ControlLogix ControlNet Interface Module

Connect a Programming Terminal to the Network with a 1786-CP Cable To connect a programming terminal to the network using a 1786-CP cable, you have the following options: • Use a 1784-KTC, 1784-KTCx, or 1784-PCC communication card and a 1786-CP cable: 1756-CNBR

1784-KTC, KTCx, PCIC, or PCC Card

1786-CP Cable

ControlNet Link

IMPORTANT

To work properly, the primary and redundant partner module must be connected to the same network segment. If you are using redundant media, connect the channel of each partner to the same network segment.

• Use a 1770-KFC communication interface, a serial or parallel connection, and a 1786-CP cable: 1756-CNBR 1770-KFC 1786-CP Cable

Serial or Parallel Connections

ControlNet Link

Publication 1756-IN604A-EN-P - February 2006

Page 23

ControlLogix ControlNet Interface Module 23 The 1786-CP cable can be plugged into any ControlNet network product’s network access port (NAP) to provide programming capability on the ControlNet network. A programming terminal connected through this cable is counted as a node and must have a unique network address. ATTENTION

Use a 1786-CP cable when connecting a programming terminal to the network through network access port (NAP). Using a commercially available RJ-style cable could result in network failure.

Troubleshoot the Module The 1756-CNB and 1756-CNBR modules have the diagnostic indicators as shown: 1756-CNB

1756-CNBR Module Status Display - See Pages 24 to 27. Module Status Indicator See Pages 24 to 27.

ControlNet Channel Status Indicators - See Page 28.

Channel A BNC Connector Channel B BNC Connector

Publication 1756-IN604A-EN-P - February 2006

Page 24

24 ControlLogix ControlNet Interface Module

Interpret the Module Status Indicator and Display The Module Status Indicator LED and Module Status Display table provide diagnostic information. Module Status Indicator LED and Module Status Display LED

Display Cause

OK

Off

None

Red

Msg scrolls(1)

BPA# ERR

BPRX ERR

BPIC

ERR

The module is not communicating due to a power supply fault or internal fault.

Action

1. Check the power supply. 2. Check the cable connectors. 3. Make sure the module is firmly seated in the chassis. 4. If the indicator remains off, replace the module. The module’s network address is 1. (Optional, see page 12.) Turn chassis power supply off. set to 00, an invalid ControlNet 2. Remove the module from the network address, or 99, an chassis. invalid ControlNet network 3. Set the network address address if you are using switches to a unique address redundant control. See footnote (01-99, or 01-98 if redundant control) at end of table. 4. Install the module in the chassis. 5. If off, turn chassis power supply on. The module detected a different Replace the chassis or module. slot address from that latched in at power-up. Excessive noise on the backplane causes this error. There are too many CRC errors Replace the module. being generated by the multicast backplane receiver, so the backplane multicast receivers have been shut off. There is a hardware fault Replace the module. within the module.

CNIC

ERR

Publication 1756-IN604A-EN-P - February 2006

Page 25

ControlLogix ControlNet Interface Module 25 Module Status Indicator LED and Module Status Display LED

Display Cause

OK

Red

DUPL NODE

RACK ERR STOP

WAIT SRM(2) Flashing BOOT Red ROM UPDT SNGL KPR!

Action

For a redundant system this may 1. (For redundant systems only.) Wait 10 seconds; if the be a temporary condition during condition persists, perform the chassis switchover. Otherwise, following steps: the module’s network address is 2. (Optional, see page 12.) the same as another module’s on Turn chassis power supply off. the link. 3. Remove the module from the chassis. 4. Set the network address switches to a unique address (01-99). 5. Install the module in the chassis. 6. If off, turn chassis power supply on. Cannot read backplane EEPROM, Replace the chassis. or rack/slot address incorrect The module commanded to stop Remove nonredundancy compliant functioning by the redundancy module from redundant secondary module. This occurs when a chassis and replace with nonredundancy compliant redundancy compliant module. module is placed into a redundant secondary chassis. The module waiting for the None required. redundancy module to complete power-up. The module has invalid Update module firmware with firmware. ControlFlash Update Utility. Flash update is in progress. None required.

The module detected that it has been connected to a ControlNet 1.5 (single-keeper) network.

Update the module’s firmware at MAC ID 01 and reschedule the network.

Publication 1756-IN604A-EN-P - February 2006

Page 26

26 ControlLogix ControlNet Interface Module Module Status Indicator LED and Module Status Display LED

Display

OK

Green

OK INIT BW >MAX

CMPT(2) DSNP(2)

PwDS(2) PwQg(2) PwQS(2) PwNS(2)

Qfng(2) QS(2) SW ERR

Cause

Action

Normal operation The module is initializing. The module is receiving too much network traffic and connections are timing out. The network bandwidth has been exceeded. The secondary module is compatible with its partner. The secondary module is disqualified with no partner.

None required

The module is primary with a disqualified secondary partner. The module is primary with a qualifying secondary partner. The module is primary with a qualified secondary partner. The module is primary with no secondary partner. The secondary module is qualifying. The secondary module is qualified. The node address switch changed after power-up.

Publication 1756-IN604A-EN-P - February 2006

None (temporary condition). If this happens frequently, add another 1756-CNB or 1756-CNBR and split the traffic between them. None required. Check corresponding slot of primary chassis for type and revision of module. Check the type and revision of the 1756-CNB module. Redundant system status. No action required.

Check corresponding slot of secondary chassis for correct module. Redundant system status. No action required.

None required, but we recommend that you either return switches to their original settings or replace the module, since this could indicate a latent hardware problem.

Page 27

ControlLogix ControlNet Interface Module 27 Module Status Indicator LED and Module Status Display LED

Display

OK

Flashing CNFG Green ERR NET

ERR Green or SO_1(2) Off SO_2(2) SO_3(2) SN_1(2) SN_2(2) SN_3(2) ?Cpt(2) !Cpt(2) (1)

Cause

Action

ControlNet network configuration error. Network cabling error or no other active nodes on network.

Recheck configuration. Re-check your network cabling and make sure another node on the network is active (online). If the display shows any message for more than three seconds, then the module failed during transition from one redundancy phase to another. Replace one or both redundancy modules.

Old primary switchover phase 1 in progress. Old primary switchover phase 2 in progress. Old primary switchover phase 3 in progress. New primary switchover phase 1 in progress. New primary switchover phase 2 in progress. New primary switchover phase 3 in progress. the module has not determined if it is compatible. the module has determined that Replace the module with correct it is not compatible. type and revision.

If switches are set to 00 the display scrolls: “FAULT: ADDRESS SWITCHES = 00, ILLEGAL” If switches are set to 99 in a redundant chassis, the display scrolls: “FAULT: ADDRESS SWITCHES = 99, ILLEGAL IN REDUNDANT SYSTEM”

(2)

Messages are for redundant control. These messages will be available in Series E firmware version 11.xx.

Publication 1756-IN604A-EN-P - February 2006