Manual · Allen-Bradley
ControlLogix ControlNet Interface Module Installation Instructions, Catalog Numbers 1756-CNB, 1756-CNBR, Series E
Manual36 pagesPDF 685 KB
Installation instructions for the Allen-Bradley 1756-CNB and 1756-CNBR Series E ControlLogix ControlNet interface modules.
Covers · 1 model
The models it covers
Summary
What is in it
Rockwell Automation installation instructions for the ControlLogix ControlNet interface modules 1756-CNB and 1756-CNBR, Series E. They cover hazardous location and enclosure requirements, standalone and redundant control, keeper types, the module's features, setting the network address switches, preparing the chassis, installing and removing the module (including under power), connecting it to the ControlNet network with a tap or a programming terminal with a 1786-CP cable, reading the status indicators and display, and specifications.
Its parts
- About the 1756-CNB and 1756-CNBR Series E Modules
- Understand Standalone and Redundant Control
- Before You Begin
- Install or Remove the Module Under Power
- Install the Module
- Connect the Module to the Network
- Connect to the Network with a Tap
- Connect a Programming Terminal to the Network with a 1786-CP Cable
- Troubleshoot the Module
- Interpret the Module Status Indicator and Display
- ControlNet Network Channel Status Indicators
- Specifications
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
These are the Allen-Bradley installation instructions for the ControlLogix ControlNet interface modules 1756-CNB and 1756-CNBR, Series E. They cover setting the network address, installing the module in a chassis, connecting it to a ControlNet network by tap or 1786-CP cable, and reading the status display and indicators. Specifications are listed at the end.
- Type
- ControlNet bridge module for a 1756 ControlLogix chassis, Series E; one slot wide p. 30
- Connectors
- 1756-CNB: 1 BNC connector plus 1 NAP (RJ-45 8-pin with shield); 1756-CNBR: 2 BNC connectors for redundant media p. 10, 30
- Network
- ControlNet at 5M; up to 99 nodes; up to 64 connections p. 30
- Backplane current
- 970 mA @ 5.1 V and 1.7 mA @ 24 V; 5.14 W dissipation p. 30, 31
- Cable
- Quad shield RG-6 coaxial cable p. 30
- Temperature
- Operating 0…60 °C (32…140 °F); storage -40…85 °C (-40…185 °F) p. 31
- Network address
- 01 to 99 in a standalone chassis, 01 to 98 in a redundant chassis; 00 is invalid p. 11
- Taps
- 1786-TPR, 1786-TPS, 1786-TPYR or 1786-TPYS; straight 1786-TPS or 1786-TPYS recommended p. 17, 18
- Programming connection
- 1786-CP cable to the network access port, with a 1784-KTC, KTCx or PCC card or a 1770-KFC interface p. 22, 23
- Chassis and power
- 1756-A4, 1756-A7, 1756-A10, 1756-A13 or 1756-A17 chassis; 1756-PA72/75 or 1756-PB72/75 power supply p. 8
- Keeper type
- Series E, firmware 10.xx and 11.xx: multi-keeper p. 9
- Redundancy
- Series E supported in ControlLogix Redundancy release 15 or later after a firmware upgrade to 11.xx p. 6
- Isolation
- Transformer ground isolation; 50V continuous, tested to 500V ac for 60 seconds p. 30, 31
What this manual walks you through
- Choosing standalone or redundant control p. 7
- Matching the module's keeper type to the network p. 9
- Setting the network address switches p. 11
- Choosing a chassis slot p. 13
- Installing and removing the module p. 15, 16
- Connecting the module to the network with a tap p. 19, 20
- Checking module status at power-up p. 21
- Connecting a programming terminal with a 1786-CP cable p. 22, 23
- Reading the module status indicator and display codes p. 24, 25, 26, 27
- Reading the network channel status indicators p. 28, 29
Good to know
- A Series D module cannot be upgraded to Series E. p. 6
- Use only a 1786-CP cable on the network access port; an ordinary RJ-style cable could cause network failure. p. 23
- Partner modules in redundant control need the same network address and the same slot. p. 7
- Keep metal parts of a tap away from conductive material. p. 19
- Repeated insertion or removal under power wears the contacts. p. 14
Questions this manual answers
What does BW >MAX mean on a 1756-CNB display?
The module gets too much network traffic and connections time out; if it happens often, add another 1756-CNB or 1756-CNBR and split the traffic. p. 26
What network addresses can a 1756-CNB use?
01 to 99 in a standalone chassis or 01 to 98 in a redundant chassis; 00 is invalid. p. 11
How much backplane current does the 1756-CNB draw?
970 mA at 5.1 V and 1.7 mA at 24 V. p. 31
Which cable connects a programming terminal to a 1756-CNB?
A 1786-CP cable into the network access port; the terminal counts as a node and needs a unique address. p. 23
Contents
Chapters and sections
Each line opens the PDF at its page.
- 1756-IN604A-EN-P1
- About This Publication1
- Important User Information2
- European Hazardous Location Approval3
- North American Hazardous Location Approval4
- Environment and Enclosure5
- Prevent Electrostatic Discharge6
- About the 1756-CNB and 1756-CNBR Series E Modules6
- Understand Standalone and Redundant Control7
- Before You Begin8
- Install or Remove the Module Under Power14
- Install the Module15
- Connect the Module to the Network17
- Connect to the Network with a Tap19
- Connect a Programming Terminal to the Network with a 1786-CP Cable22
- Troubleshoot the Module23
- Interpret the Module Status Indicator and Display24
- ControlNet Network Channel Status Indicators28
- Specifications30
- Additional Resources34
- Rockwell Automation Support36
- Installation Assistance36
- Backcover36
The whole text · 4 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file