For the Allen-Bradley 1756-CNB
Page 28
28 ControlLogix ControlNet Interface Module
ControlNet Network Channel Status Indicators The ControlNet network channel status indicators appear in one of the following states: • Steady - indicator is on continuously in the defined state. • Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together). The two indicators are always in opposite states, out of phase. • Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other). If both indicators are flashing, they must flash together, in phase. The ControlNet Network Channel Status Indicators table summarizes the meanings of these states. ControlNet Network Channel Status Indicators A and
Cause
Action
No power Faulted unit
None or power up. Cycle power or reset unit.
B
Off Steady red
Alternating Self-test red/green Alternating red/off Incorrect node configuration
Cause A
Off or
If fault persists, contact A-B representative or distributor. None Check network address and other ControlNet network configuration parameters. Action
B
Channel disabled
Steady green Normal operation Flashing green/off Temporary errors
Publication 1756-IN604A-EN-P - February 2006
Program network for redundant media, if required. None None; unit will self-correct.
Page 29
ControlLogix ControlNet Interface Module 29 ControlNet Network Channel Status Indicators A and
Cause
Action
Node is not configured to go on line
Make sure the configuration manager node is present and working and selected address is
B not greater than selected UMAX.(1) Flashing red/off
Media fault
No other nodes present on network Flashing red/green Incorrect network configuration
Check media. For example: broken cables, loose connectors, missing terminators. Add other nodes to the network. Cycle power or reset unit. If fault persists, contact A-B representative or distributor.
(1)
The configuration manager node is the node responsible for distributing ControlNet network configuration data to all nodes on the network.
Publication 1756-IN604A-EN-P - February 2006
Page 30
30 ControlLogix ControlNet Interface Module
Specifications ControlLogix ControlNet Interface Module 1756-CNB, 1756-CNBR, Series E Attribute
Value
Connectors 1756-CNB 1756-CNBR
1 BNC connector for nonredundant media operation 1 NAP (RJ-45 8-pin with shield) 2 BNC connectors for redundant media operation 1 NAP (RJ-45 8-pin with shield)
Cable
Quad shield RG-6 coaxial cable
Ground isolation
Transformer
ControlNet network communication rate
5M
Diagnostics
Yes
Weight 1756-CNB 1756-CNBR
0.260 kg (0.57 lb) 0.293 kg (0.64 lb)
Mounting type
Chassis
Mounting location
1756 ControlLogix Chassis
Number of nodes, max
99
Slot width
1
Connections supported, max
64
Communication interface type
Bridge
Device type
Communication interface
Power dissipation
5.14 W
Thermal dissipation
17.5 BTU/hr
Publication 1756-IN604A-EN-P - February 2006
Page 31
ControlLogix ControlNet Interface Module 31 ControlLogix ControlNet Interface Module 1756-CNB, 1756-CNBR, Series E Attribute
Value
Backplane current
970 mA @ 5.1 V 1.7 mA @ 24 V
Isolation voltage (continuous-voltage withstand rating)
50V Tested to 500V ac for 60 seconds
Wiring category(1)
2 - on communications ports
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications ControlLogix ControlNet Interface Module 1756-CNB, 1756-CNBR, Series E Attribute
Value
Operational temperature
IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0…60 °C (32…140 °F)
Storage temperature
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat): 5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating): 2 g @ 10…500 Hz
Operating shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g
Nonoperating shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50 g
Emissions
CISPR 11: Group 1, Class A
Publication 1756-IN604A-EN-P - February 2006
Page 32
32 ControlLogix ControlNet Interface Module Environmental Specifications ControlLogix ControlNet Interface Module 1756-CNB, 1756-CNBR, Series E Attribute
Value
ESD immunity
IEC 61000-4-2: 6 kV contact discharges 8 kV air discharges
Radiated RF immunity Series E
IEC 61000-4-3: 10 V/m with 1 kHz sine-wave 80%AM from 30…2000 MHz 10 V/m with 200 Hz 50% Pulse 100%AM at 900 MHz 10 V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz 1 V/m with 1 kHz sine-wave 80%AM from 2000 MHz…2700 MHz
EFT/B immunity
IEC 61000-4-4: ±2 kV at 5 kHz on communications ports
Surge transient immunity
IEC 61000-4-5: ±2 kV line-earth(CM) on communications ports
Conducted RF immunity
IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz
Enclosure type rating
None (open-style)
Publication 1756-IN604A-EN-P - February 2006
Page 33
ControlLogix ControlNet Interface Module 33 Certifications 1756-CNB Series E and 1756-CNBR, Series E Certification
Value
Certifications
UL
UL Listed Industrial Control Equipment
(when product is marked)(1) cULusUL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada CSA CSA Certified Process Control Equipment CSA CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
CE
European Union 89/336/EEC EMC Directive, compliant with: EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-TickAustralian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions EEx European Union 94/9/EC ATEX Directive, compliant with: EN 50021; Potentially Explosive Atmospheres, Protection “n” (Zone 2) CI (1)
ControlNet Int'l conformance tested to ControlNet network specifications
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Publication 1756-IN604A-EN-P - February 2006
Page 34
34 ControlLogix ControlNet Interface Module
Additional Resources Publication Title
Publication Number
Industrial Automation Wiring and Grounding Guidelines
1770-4.1
ControlNet Modules in Logix5000 Control Systems
CNET-UM001
ControlLogix Chassis Installation Instructions
1756-IN080
ControlLogix Power Supplies Installation Instructions
1756-IN078
ControlLogix Power Supplies Installation Instructions
1756-IN596
ControlNet Coax Tap Installation Instructions
1786-5.7
ControlNet Coax Media Planning and Installation Guide
CNET-IN002
ControlNet Fiber Media Planning and Installation Guide
CNET-IN001
ControlLogix is a trademark of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1756-IN604A-EN-P - February 2006
Page 35
ControlLogix ControlNet Interface Module 35
Notes:
Publication 1756-IN604A-EN-P - February 2006
Page 36
Rockwell Automation Support Rockwell Automation provides technical information on the web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.
Installation Assistance If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running: United States
1.440.646.3223 Monday – Friday, 8am – 5pm EST
Outside United States
Please contact your local Rockwell Automation representative for any technical support issues.
New Product Satisfaction Return Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned: United States
Contact your distributor. You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process.
Outside United States
Please contact your local Rockwell Automation representative for return procedure.
ö
Publication 1756-IN604A-EN-P - February 2006
PN 953002-64