For the Allen-Bradley 1756-CNB

Page 28

28 ControlLogix ControlNet Interface Module

ControlNet Network Channel Status Indicators The ControlNet network channel status indicators appear in one of the following states: • Steady - indicator is on continuously in the defined state. • Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together). The two indicators are always in opposite states, out of phase. • Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other). If both indicators are flashing, they must flash together, in phase. The ControlNet Network Channel Status Indicators table summarizes the meanings of these states. ControlNet Network Channel Status Indicators A and

Cause

Action

No power Faulted unit

None or power up. Cycle power or reset unit.

B

Off Steady red

Alternating Self-test red/green Alternating red/off Incorrect node configuration

Cause A

Off or

If fault persists, contact A-B representative or distributor. None Check network address and other ControlNet network configuration parameters. Action

B

Channel disabled

Steady green Normal operation Flashing green/off Temporary errors

Publication 1756-IN604A-EN-P - February 2006

Program network for redundant media, if required. None None; unit will self-correct.

Page 29

ControlLogix ControlNet Interface Module 29 ControlNet Network Channel Status Indicators A and

Cause

Action

Node is not configured to go on line

Make sure the configuration manager node is present and working and selected address is

B not greater than selected UMAX.(1) Flashing red/off

Media fault

No other nodes present on network Flashing red/green Incorrect network configuration

Check media. For example: broken cables, loose connectors, missing terminators. Add other nodes to the network. Cycle power or reset unit. If fault persists, contact A-B representative or distributor.

(1)

The configuration manager node is the node responsible for distributing ControlNet network configuration data to all nodes on the network.

Publication 1756-IN604A-EN-P - February 2006

Page 30

30 ControlLogix ControlNet Interface Module

Specifications ControlLogix ControlNet Interface Module 1756-CNB, 1756-CNBR, Series E Attribute

Value

Connectors 1756-CNB 1756-CNBR

1 BNC connector for nonredundant media operation 1 NAP (RJ-45 8-pin with shield) 2 BNC connectors for redundant media operation 1 NAP (RJ-45 8-pin with shield)

Cable

Quad shield RG-6 coaxial cable

Ground isolation

Transformer

ControlNet network communication rate

5M

Diagnostics

Yes

Weight 1756-CNB 1756-CNBR

0.260 kg (0.57 lb) 0.293 kg (0.64 lb)

Mounting type

Chassis

Mounting location

1756 ControlLogix Chassis

Number of nodes, max

99

Slot width

1

Connections supported, max

64

Communication interface type

Bridge

Device type

Communication interface

Power dissipation

5.14 W

Thermal dissipation

17.5 BTU/hr

Publication 1756-IN604A-EN-P - February 2006

Page 31

ControlLogix ControlNet Interface Module 31 ControlLogix ControlNet Interface Module 1756-CNB, 1756-CNBR, Series E Attribute

Value

Backplane current

970 mA @ 5.1 V 1.7 mA @ 24 V

Isolation voltage (continuous-voltage withstand rating)

50V Tested to 500V ac for 60 seconds

Wiring category(1)

2 - on communications ports

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications ControlLogix ControlNet Interface Module 1756-CNB, 1756-CNBR, Series E Attribute

Value

Operational temperature

IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0…60 °C (32…140 °F)

Storage temperature

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat): 5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating): 2 g @ 10…500 Hz

Operating shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g

Nonoperating shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50 g

Emissions

CISPR 11: Group 1, Class A

Publication 1756-IN604A-EN-P - February 2006

Page 32

32 ControlLogix ControlNet Interface Module Environmental Specifications ControlLogix ControlNet Interface Module 1756-CNB, 1756-CNBR, Series E Attribute

Value

ESD immunity

IEC 61000-4-2: 6 kV contact discharges 8 kV air discharges

Radiated RF immunity Series E

IEC 61000-4-3: 10 V/m with 1 kHz sine-wave 80%AM from 30…2000 MHz 10 V/m with 200 Hz 50% Pulse 100%AM at 900 MHz 10 V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz 1 V/m with 1 kHz sine-wave 80%AM from 2000 MHz…2700 MHz

EFT/B immunity

IEC 61000-4-4: ±2 kV at 5 kHz on communications ports

Surge transient immunity

IEC 61000-4-5: ±2 kV line-earth(CM) on communications ports

Conducted RF immunity

IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz

Enclosure type rating

None (open-style)

Publication 1756-IN604A-EN-P - February 2006

Page 33

ControlLogix ControlNet Interface Module 33 Certifications 1756-CNB Series E and 1756-CNBR, Series E Certification

Value

Certifications

UL

UL Listed Industrial Control Equipment

(when product is marked)(1) cULusUL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada CSA CSA Certified Process Control Equipment CSA CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

CE

European Union 89/336/EEC EMC Directive, compliant with: EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-TickAustralian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions EEx European Union 94/9/EC ATEX Directive, compliant with: EN 50021; Potentially Explosive Atmospheres, Protection “n” (Zone 2) CI (1)

ControlNet Int'l conformance tested to ControlNet network specifications

See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-IN604A-EN-P - February 2006

Page 34

34 ControlLogix ControlNet Interface Module

Additional Resources Publication Title

Publication Number

Industrial Automation Wiring and Grounding Guidelines

1770-4.1

ControlNet Modules in Logix5000 Control Systems

CNET-UM001

ControlLogix Chassis Installation Instructions

1756-IN080

ControlLogix Power Supplies Installation Instructions

1756-IN078

ControlLogix Power Supplies Installation Instructions

1756-IN596

ControlNet Coax Tap Installation Instructions

1786-5.7

ControlNet Coax Media Planning and Installation Guide

CNET-IN002

ControlNet Fiber Media Planning and Installation Guide

CNET-IN001

ControlLogix is a trademark of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.

Publication 1756-IN604A-EN-P - February 2006

Page 35

ControlLogix ControlNet Interface Module 35

Notes:

Publication 1756-IN604A-EN-P - February 2006

Page 36

Rockwell Automation Support Rockwell Automation provides technical information on the web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.

Installation Assistance If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running: United States

1.440.646.3223 Monday – Friday, 8am – 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues.

New Product Satisfaction Return Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned: United States

Contact your distributor. You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process.

Outside United States

Please contact your local Rockwell Automation representative for return procedure.