The text of a spec sheet · part 1 of 4
1756 ControlLogix Communication Modules Specifications, pages 1 to 9
Pages 1 to 9 of 34: 1756 ControlLogix Communication Modules Specifications Technical Data; Back Cover
The original document is the PDF (943 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-DNB
Page 1
Technical Data
1756 ControlLogix Communication Modules Specifications Standard ControlLogix Catalog Numbers 1756-EN2F, 1756-EN2T, 1756-EN2TR, 1756-EN3TR, 1756-ENBT, 1756-EWEB, 1756-CN2, 1756-CN2R, 1756-CNB, 1756-CNBR, 1756-DNB, 1756-DHRIO, 1756-RIO, 1756-DH485, 1756-SYNCH, 1756-EN2TXT, 1756-CN2RXT, 1756-DHRIOXT, 1757-FFLD2, 1757-FFLD4, 1757-FFLDC2, 1757-FFLDC4 ControlLogix-XT Catalog Numbers 1756-EN2TXT, 1756-CN2RXT, 1756-DHRIOXT Linking Device Catalog Numbers 1757-FFLD2, 1757-FFLD4, 1757-FFLDC2, 1757-FFLDC4 Topic
Page
Additional Resources
2
Available Communication Modules
2
EtherNet/IP Network
3
Stratix Switches
9
ControlNet Network
10
DeviceNet Network
17
DH+ and Remote I/O Networks
20
FOUNDATION Fieldbus Network
25
DH-485 Network
28
SynchLink Communication
31
Separate communication-interface modules are available for different networks. Install multiple communication-interface modules into the ControlLogix® backplane to configure a gateway to bridge or route control and information data between different networks. You do not need a ControlLogix controller in the chassis.
Page 2
1756 ControlLogix Communication Modules Specifications
Additional Resources These documents contain additional information concerning related products from Rockwell Automation®. Resource
Description
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, http://www.ab.com
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley® distributor or Rockwell Automation sales representative.
Available Communication Modules Network
Cat. No.
Description
Page
EtherNet/IP
1756-EN2F
EtherNet/IP bridge, fiber, 256 Logix connections
4
1756-EN2T
EtherNet/IP bridge, copper, 256 Logix connections
4
1756-EN2TR
EtherNet/IP bridge, embedded switch, copper Supports as many as 8 axis of motion
4
1756-EN3TR
EtherNet/IP bridge, embedded switch, copper Supports as many as 128 axis of motion
4
1756-ENBT
EtherNet/IP bridge, copper, 128 Logix connections
4
1756-EWEB
Ethernet web server, 128 Logix connections, Class 3 messaging only
4
1756-EN2TXT
ControlLogix-XT™, EtherNet/IP bridge, copper, 256 Logix connections
6
1756-CN2/B, 1756-CN2R/B
ControlNet bridge, 128 Logix connections(1)
11
1756-CNB, 1756-CNBR
ControlNet bridge, 64 connections; recommend using only 40…48 Logix connections for I/O
11
1756-CN2RXT
ControlLogix-XT, ControlNet bridge, 128 Logix connections(1)
11
DeviceNet
1756-DNB/E
DeviceNet bridge
17
Data Highway Plus™
1756-DHRIO
Data Highway Plus/Remote I/O module
21
1756-DHRIOXT
ControlLogix-XT, Data Highway Plus/Remote I/O module
23
1756-DHRIO
Data Highway Plus/Remote I/O module
21
1756-RIO/B
Remote I/O module
21
1756-DHRIOXT
ControlLogix-XT, Data Highway Plus/Remote I/O module
23
1757FFLD2, 1757-FFLD4
Foundation Fieldbus linking device bridges from an Ethernet network to either two or four H1 ports
25
1757-FFLDC2, 1757-FFLDC4
Foundation Fieldbus linking device bridges from a ControlNet network to either two or four H1 ports
25
Serial
1756-DH485
Compatible with RS-232 serial communication, supports the DF1 protocol, send and receive messages, does not support remote programming and monitoring
28
SynchLink™
1756-SYNCH
SynchLink fiber-optic communication link
31
ControlNet
Remote I/O
Foundation Fieldbus
(1) 128 connections are available for standard use. An additional three connections are reserved for redundant control.
2
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
Page 3
1756 ControlLogix Communication Modules Specifications
Communication Connections A ControlLogix system uses connections to establish communication links between devices. The types of connections include the following: • Controller-to-local I/O modules or local communication modules • Controller-to-remote I/O or remote communication modules • Controller-to-remote I/O (rack-optimized) modules • Produced and consumed tags • Messages • Controller access by RSLogix™ 5000 software • Controller access by RSLinx® software for HMI or other applications You indirectly determine the number of connections the controller uses by configuring the controller to communicate with other devices in the system. The limit of connections may ultimately reside in the communication module you use for the connection. If a message path routes through a communication module, the connection related to the message also counts towards the connection limit of that communication module.
EtherNet/IP Network The Ethernet Industrial (EtherNet/IP) network protocol is an open industrial-networking standard that supports both real-time I/O messaging and message exchange. The EtherNet/IP network uses off-the-shelf Ethernet communication chips and physical media.
If you need to
Select this interface
• Control I/O modules and drives
1756-EN2F bridge 1756-EN2T bridge 1756-ENBT bridge
• Act as an adapter for I/O on remote EtherNet/IP links • Communicate with other EtherNet/IP devices (messages and HMI) • Bridge EtherNet/IP links to route messages to devices on other networks Support device level ring (DLR) and linear topologies
1756-EN2TR bridge 1756-EN3TR bridge
Provide control in environments where temperatures range from -25…70 ° C (-13…158 ° F)
1756-EN2TXT bridge
• Use an Internet browser to remotely access tags in a ControlLogix controller
1756-EWEB web server
• Communicate with other EtherNet/IP or generic Ethernet devices (messaging only; no I/O control) • Bridge EtherNet/IP links to route messages to devices on other networks
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
3
Page 4
1756 ControlLogix Communication Modules Specifications
Table 1 - Technical Specifications - 1756 EtherNet/IP Modules Attribute
1756-EN2F
1756-EN2T
1756-EN2TR, 1756-EN3TR
1756-ENBT
1756-EWEB
EtherNet/IP communication rate
100 Mbps
10/100 Mbps
10/100 Mbps
10/100 Mbps
10/100 Mbps
Logix communication connections
256
128
TCP/IP communication connections
128
64
Current draw @ 5.1V DC
1.2 A
1A
1A
700 mA
Current draw @ 24V DC
3 mA
3 mA
3 mA
3 mA
Power dissipation
6.2 W
5.1 W
5.1 W
3.65 W
Isolation voltage
No isolation between USB and system
30V (continuous), basic insulation type, Ethernet network to backplane No isolation between USB and backplane Type tested @ 510V AC for 60 s
30V (continuous), basic insulation type, Ethernet network to backplane No isolation between USB and backplane Type tested @ 853V AC for 60 s
30V (continuous), basic insulation type, Ethernet network to backplane Type tested @ 707V DC for 60 s
Slot width
1
Module location
Chassis-based, any slot
Chassis
1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17
Power supply, standard
1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant
756-PA75R, 1756-PB75R, 1756-PSCA2
Ethernet port
1 Ethernet fiber
1 Ethernet RJ45 Category 5
Ethernet cable
Multimode fiber, LC connector
802.3 compliant shielded or unshielded twisted pair
USB port(1)
USB 1.1, full speed (12 Mbps)
Wire category(2)
3 - on USB ports
North American temperature code
T4A
IEC temperature code
T4
Enclosure type rating
None (open-style)
Transmitter launch power at Beginning of Life (BOL), min Allow -1 dB at End of Life (EOL)
-19 dBm into 62.5/125 μm fiber, N/A = 0.275 -22.5 dBm into 50/125 μm fiber, N/A = 0.20
1 Ethernet RJ45 Category 5, 2 - on Ethernet ports 3 - on USB ports
2 - on Ethernet ports, (1) The USB port is intended for temporary local programming purposes only and not intended for permanent connection. Do not use the USB port in hazardous locations. (2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
4
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
Page 5
1756 ControlLogix Communication Modules Specifications
Table 2 - Environmental Specifications - 1756 EtherNet/IP Modules Attribute
1756-EN2F
1756-EN2T
1756-EN2TR, 1756-EN3TR
1756-ENBT, 1756-EWEB
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged damp heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emission CISPR 11
Group 1, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4, ±2 kV at 5 kHz on Ethernet ports
Surge transient immunity IEC 61000-4-5, ±2 kV line-earth (CM) on Ethernet ports
Conducted RF immunity IEC 61000-4-6, 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
±3 kV at 5 kHz on Ethernet ports ±2 kV at 5 kHz on Ethernet ports
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
5
Page 6
1756 ControlLogix Communication Modules Specifications
Table 3 - Certifications - 1756 EtherNet/IP Modules Certification(1)
1756-EN2F, 1756-EN2T c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
1756-EN2TR, 1756-EN3TR, 1756-ENBT
1756-EWEB
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
C-Tick
Australian Radiocommunications Act, compliant with AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with the following: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4X
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
TÜV, EtherNet/IP
ODVA conformance tested to EtherNet/IP specifications
TÜV Certified for Functional Safety: Capable of SIL 2, (1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Table 4 - Technical Specifications - 1756 EtherNet/IP-XT Module
6
Attribute
1756-EN2TXT
EtherNet/IP communication rate
10/100 Mbps
Logix communication connections
256
TCP/IP communication connections
128
Current draw @ 5.1V DC
1A
Current draw @ 24V DC
3 mA
Power dissipation
5.2 W
Power consumption
17.7 BTU/hr
Isolation voltage
30V (continuous), basic insulation type, Ethernet network to backplane No isolation between USB and backplane Type tested @ 853V AC for 60 s
Slot width
1
Module location
Chassis-based, any slot
Chassis
1756-A4LXT, 1756-A5XT, 1756-A7LXT
Power supply, standard
1756-PAXT, 1756-PBXT
Power supply, redundant
None
Ethernet port
1 Ethernet RJ45 Category 5
Ethernet cable
802.3 compliant shielded or unshielded twisted pair
USB port(1)
USB 1.1, full speed (12 Mbps)
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
Page 7
1756 ControlLogix Communication Modules Specifications
Table 4 - Technical Specifications - 1756 EtherNet/IP-XT Module (Continued) Attribute Wire category
1756-EN2TXT (2)
2 - on Ethernet ports 3 - on USB ports
North American temperature code
T4A
IEC temperature code
T4
Enclosure type rating
None (open-style)
(1) The USB port is intended for temporary local programming purposes only and not intended for permanent connection. Do not use the USB port in hazardous locations. (2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Table 5 - Environmental Specifications - 1756 EtherNet/IP-XT Module Attribute
1756-EN2TXT
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
-25…70 °C (-13…158 °F)
Temperature, surrounding air, max
70 °C (158 °F)
Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged damp heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions CISPR 11
Group 1, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8k V air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±2 kV at 5 kHz on Ethernet ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on Ethernet ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
7
Page 8
1756 ControlLogix Communication Modules Specifications
Table 6 - Certifications - 1756 EtherNet/IP-XT Module Certification(1)
1756-EN2TXT c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2004/108/IEC EMC Directive, compliant with the following: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with the following: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4X
TÜV
TÜV Certified for Functional Safety: Capable of SIL 2
EtherNet/IP
ODVA conformance tested to EtherNet/IP specifications
(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Accessories - Ethernet Network
8
Cat. No.
Description
Specifications
1585J-M8PBJM-x
Ethernet RJ45 patchcord x = 2 (2 m), 5 (5 m), or 10 (10 m)
8-conductor, Teal Riser PVC Cable (flex Rated cable also available)
1585J-M8CC-H
RJ45 insulation displacement connector (IDC)
0.128…0.325 mm2 (26…22 AWG), Cat. 6, IDC, no tool required
1585J-M8CC-C
RJ45 crimp connector with boot, qty = 50 pieces
0.128…0.205 mm2 (26…24 AWG), Cat. 5e, requires crimp tool for assembly
1585A-JCRIMP
Crimp tool, 9300-RADES
Remote access dial-in kit
56 Kbps modem connection to devices on an Ethernet network
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
Page 9
1756 ControlLogix Communication Modules Specifications
Stratix Switches To effectively manage real-time control and information flow throughout the manufacturing and IT enterprise, Rockwell Automation offers a full portfolio of industrial Ethernet switches and media, including a line of Stratix switches integrated with Cisco technology. The Stratix line of switches includes modular managed, fixed managed, and unmanaged switches. If your application
Select
• • • • •
Requires Layer 3 routing Integrates enterprise and manufacturing environments Manages multicast traffic Requires diagnostics data Requires security options
Stratix 8300™ modular, managed switch
• • • •
Integrates enterprise and manufacturing environments Manages multicast traffic Requires diagnostics data Requires security options
Stratix 8000™ modular, managed switch
• • • •
Integrates plant floor devices Manages multicast traffic Requires diagnostics data Requires security options
Stratix 6000™ fixed, managed switch
• Requires easy setup and direct replacement of switches • Is a small, isolated network
Stratix 2000™ unmanaged switch
Table 7 - Stratix Managed Switch Specifications Stratix 8000 and Stratix 8300
Stratix 6000
Base
Base
Base
Base
Expansion
Expansion
Feature
1783-MS06T
1783-RMS06T
1783-MS10T
1783-RMS10T
1783-MX08T
1783-MX08F
Ports per module
6
Layer 3 routing
No
Total ports, max
Up to 26(1)
Fiber ports
0…10(1)
10/100 copper ports
4…24(1)
100 base LC fiber ports
0…8(1)
SFP slots
1783-EMS04T
1783-EMS08T
4
9
No
No, - - 1
4
8, - 2(2), 1
10/100/1000 copper ports
2(2), - 100 Mbps fiber support
Yes, Yes
No
No
1 G fiber support
Yes, - No
Yes
CompactFlash memory
Yes
No
No
Power requirements
24/48V DC (18…60V DC)
24V DC (12…48V DC)
10 Yes
No
8 Yes
No
No
(1) Maximum port counts require expansion ports. (2) Two ports each can be used for SFP or 10/100/1000 copper.
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012