For the Allen-Bradley 1756-DNB

Page 1

Technical Data

1756 ControlLogix Communication Modules Specifications Standard ControlLogix Catalog Numbers 1756-EN2F, 1756-EN2T, 1756-EN2TR, 1756-EN3TR, 1756-ENBT, 1756-EWEB, 1756-CN2, 1756-CN2R, 1756-CNB, 1756-CNBR, 1756-DNB, 1756-DHRIO, 1756-RIO, 1756-DH485, 1756-SYNCH, 1756-EN2TXT, 1756-CN2RXT, 1756-DHRIOXT, 1757-FFLD2, 1757-FFLD4, 1757-FFLDC2, 1757-FFLDC4 ControlLogix-XT Catalog Numbers 1756-EN2TXT, 1756-CN2RXT, 1756-DHRIOXT Linking Device Catalog Numbers 1757-FFLD2, 1757-FFLD4, 1757-FFLDC2, 1757-FFLDC4 Topic

Page

Additional Resources

2

Available Communication Modules

2

EtherNet/IP Network

3

Stratix Switches

9

ControlNet Network

10

DeviceNet Network

17

DH+ and Remote I/O Networks

20

FOUNDATION Fieldbus Network

25

DH-485 Network

28

SynchLink Communication

31

Separate communication-interface modules are available for different networks. Install multiple communication-interface modules into the ControlLogix® backplane to configure a gateway to bridge or route control and information data between different networks. You do not need a ControlLogix controller in the chassis.

Page 2

1756 ControlLogix Communication Modules Specifications

Additional Resources These documents contain additional information concerning related products from Rockwell Automation®. Resource

Description

Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Provides general guidelines for installing a Rockwell Automation industrial system.

Product Certifications website, http://www.ab.com

Provides declarations of conformity, certificates, and other certification details.

You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley® distributor or Rockwell Automation sales representative.

Available Communication Modules Network

Cat. No.

Description

Page

EtherNet/IP

1756-EN2F

EtherNet/IP bridge, fiber, 256 Logix connections

4

1756-EN2T

EtherNet/IP bridge, copper, 256 Logix connections

4

1756-EN2TR

EtherNet/IP bridge, embedded switch, copper Supports as many as 8 axis of motion

4

1756-EN3TR

EtherNet/IP bridge, embedded switch, copper Supports as many as 128 axis of motion

4

1756-ENBT

EtherNet/IP bridge, copper, 128 Logix connections

4

1756-EWEB

Ethernet web server, 128 Logix connections, Class 3 messaging only

4

1756-EN2TXT

ControlLogix-XT™, EtherNet/IP bridge, copper, 256 Logix connections

6

1756-CN2/B, 1756-CN2R/B

ControlNet bridge, 128 Logix connections(1)

11

1756-CNB, 1756-CNBR

ControlNet bridge, 64 connections; recommend using only 40…48 Logix connections for I/O

11

1756-CN2RXT

ControlLogix-XT, ControlNet bridge, 128 Logix connections(1)

11

DeviceNet

1756-DNB/E

DeviceNet bridge

17

Data Highway Plus™

1756-DHRIO

Data Highway Plus/Remote I/O module

21

1756-DHRIOXT

ControlLogix-XT, Data Highway Plus/Remote I/O module

23

1756-DHRIO

Data Highway Plus/Remote I/O module

21

1756-RIO/B

Remote I/O module

21

1756-DHRIOXT

ControlLogix-XT, Data Highway Plus/Remote I/O module

23

1757FFLD2, 1757-FFLD4

Foundation Fieldbus linking device bridges from an Ethernet network to either two or four H1 ports

25

1757-FFLDC2, 1757-FFLDC4

Foundation Fieldbus linking device bridges from a ControlNet network to either two or four H1 ports

25

Serial

1756-DH485

Compatible with RS-232 serial communication, supports the DF1 protocol, send and receive messages, does not support remote programming and monitoring

28

SynchLink™

1756-SYNCH

SynchLink fiber-optic communication link

31

ControlNet

Remote I/O

Foundation Fieldbus

(1) 128 connections are available for standard use. An additional three connections are reserved for redundant control.

2

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

Page 3

1756 ControlLogix Communication Modules Specifications

Communication Connections A ControlLogix system uses connections to establish communication links between devices. The types of connections include the following: • Controller-to-local I/O modules or local communication modules • Controller-to-remote I/O or remote communication modules • Controller-to-remote I/O (rack-optimized) modules • Produced and consumed tags • Messages • Controller access by RSLogix™ 5000 software • Controller access by RSLinx® software for HMI or other applications You indirectly determine the number of connections the controller uses by configuring the controller to communicate with other devices in the system. The limit of connections may ultimately reside in the communication module you use for the connection. If a message path routes through a communication module, the connection related to the message also counts towards the connection limit of that communication module.

EtherNet/IP Network The Ethernet Industrial (EtherNet/IP) network protocol is an open industrial-networking standard that supports both real-time I/O messaging and message exchange. The EtherNet/IP network uses off-the-shelf Ethernet communication chips and physical media.

If you need to

Select this interface

• Control I/O modules and drives

1756-EN2F bridge 1756-EN2T bridge 1756-ENBT bridge

• Act as an adapter for I/O on remote EtherNet/IP links • Communicate with other EtherNet/IP devices (messages and HMI) • Bridge EtherNet/IP links to route messages to devices on other networks Support device level ring (DLR) and linear topologies

1756-EN2TR bridge 1756-EN3TR bridge

Provide control in environments where temperatures range from -25…70 ° C (-13…158 ° F)

1756-EN2TXT bridge

• Use an Internet browser to remotely access tags in a ControlLogix controller

1756-EWEB web server

• Communicate with other EtherNet/IP or generic Ethernet devices (messaging only; no I/O control) • Bridge EtherNet/IP links to route messages to devices on other networks

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

3

Page 4

1756 ControlLogix Communication Modules Specifications

Table 1 - Technical Specifications - 1756 EtherNet/IP Modules Attribute

1756-EN2F

1756-EN2T

1756-EN2TR, 1756-EN3TR

1756-ENBT

1756-EWEB

EtherNet/IP communication rate

100 Mbps

10/100 Mbps

10/100 Mbps

10/100 Mbps

10/100 Mbps

Logix communication connections

256

128

TCP/IP communication connections

128

64

Current draw @ 5.1V DC

1.2 A

1A

1A

700 mA

Current draw @ 24V DC

3 mA

3 mA

3 mA

3 mA

Power dissipation

6.2 W

5.1 W

5.1 W

3.65 W

Isolation voltage

No isolation between USB and system

30V (continuous), basic insulation type, Ethernet network to backplane No isolation between USB and backplane Type tested @ 510V AC for 60 s

30V (continuous), basic insulation type, Ethernet network to backplane No isolation between USB and backplane Type tested @ 853V AC for 60 s

30V (continuous), basic insulation type, Ethernet network to backplane Type tested @ 707V DC for 60 s

Slot width

1

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

756-PA75R, 1756-PB75R, 1756-PSCA2

Ethernet port

1 Ethernet fiber

1 Ethernet RJ45 Category 5

Ethernet cable

Multimode fiber, LC connector

802.3 compliant shielded or unshielded twisted pair

USB port(1)

USB 1.1, full speed (12 Mbps)

Wire category(2)

3 - on USB ports

North American temperature code

T4A

IEC temperature code

T4

Enclosure type rating

None (open-style)

Transmitter launch power at Beginning of Life (BOL), min Allow -1 dB at End of Life (EOL)

-19 dBm into 62.5/125 μm fiber, N/A = 0.275 -22.5 dBm into 50/125 μm fiber, N/A = 0.20

1 Ethernet RJ45 Category 5, 2 - on Ethernet ports 3 - on USB ports

2 - on Ethernet ports, (1) The USB port is intended for temporary local programming purposes only and not intended for permanent connection. Do not use the USB port in hazardous locations. (2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

4

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

Page 5

1756 ControlLogix Communication Modules Specifications

Table 2 - Environmental Specifications - 1756 EtherNet/IP Modules Attribute

1756-EN2F

1756-EN2T

1756-EN2TR, 1756-EN3TR

1756-ENBT, 1756-EWEB

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged damp heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emission CISPR 11

Group 1, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4, ±2 kV at 5 kHz on Ethernet ports

Surge transient immunity IEC 61000-4-5, ±2 kV line-earth (CM) on Ethernet ports

Conducted RF immunity IEC 61000-4-6, 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

±3 kV at 5 kHz on Ethernet ports ±2 kV at 5 kHz on Ethernet ports

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

5

Page 6

1756 ControlLogix Communication Modules Specifications

Table 3 - Certifications - 1756 EtherNet/IP Modules Certification(1)

1756-EN2F, 1756-EN2T c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

1756-EN2TR, 1756-EN3TR, 1756-ENBT

1756-EWEB

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

C-Tick

Australian Radiocommunications Act, compliant with AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with the following: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4X

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

TÜV, EtherNet/IP

ODVA conformance tested to EtherNet/IP specifications

TÜV Certified for Functional Safety: Capable of SIL 2, (1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Table 4 - Technical Specifications - 1756 EtherNet/IP-XT Module

6

Attribute

1756-EN2TXT

EtherNet/IP communication rate

10/100 Mbps

Logix communication connections

256

TCP/IP communication connections

128

Current draw @ 5.1V DC

1A

Current draw @ 24V DC

3 mA

Power dissipation

5.2 W

Power consumption

17.7 BTU/hr

Isolation voltage

30V (continuous), basic insulation type, Ethernet network to backplane No isolation between USB and backplane Type tested @ 853V AC for 60 s

Slot width

1

Module location

Chassis-based, any slot

Chassis

1756-A4LXT, 1756-A5XT, 1756-A7LXT

Power supply, standard

1756-PAXT, 1756-PBXT

Power supply, redundant

None

Ethernet port

1 Ethernet RJ45 Category 5

Ethernet cable

802.3 compliant shielded or unshielded twisted pair

USB port(1)

USB 1.1, full speed (12 Mbps)

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

Page 7

1756 ControlLogix Communication Modules Specifications

Table 4 - Technical Specifications - 1756 EtherNet/IP-XT Module (Continued) Attribute Wire category

1756-EN2TXT (2)

2 - on Ethernet ports 3 - on USB ports

North American temperature code

T4A

IEC temperature code

T4

Enclosure type rating

None (open-style)

(1) The USB port is intended for temporary local programming purposes only and not intended for permanent connection. Do not use the USB port in hazardous locations. (2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 5 - Environmental Specifications - 1756 EtherNet/IP-XT Module Attribute

1756-EN2TXT

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

-25…70 °C (-13…158 °F)

Temperature, surrounding air, max

70 °C (158 °F)

Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged damp heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions CISPR 11

Group 1, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8k V air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±2 kV at 5 kHz on Ethernet ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on Ethernet ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

7

Page 8

1756 ControlLogix Communication Modules Specifications

Table 6 - Certifications - 1756 EtherNet/IP-XT Module Certification(1)

1756-EN2TXT c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/IEC EMC Directive, compliant with the following: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with the following: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4X

TÜV

TÜV Certified for Functional Safety: Capable of SIL 2

EtherNet/IP

ODVA conformance tested to EtherNet/IP specifications

(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Accessories - Ethernet Network

8

Cat. No.

Description

Specifications

1585J-M8PBJM-x

Ethernet RJ45 patchcord x = 2 (2 m), 5 (5 m), or 10 (10 m)

8-conductor, Teal Riser PVC Cable (flex Rated cable also available)

1585J-M8CC-H

RJ45 insulation displacement connector (IDC)

0.128…0.325 mm2 (26…22 AWG), Cat. 6, IDC, no tool required

1585J-M8CC-C

RJ45 crimp connector with boot, qty = 50 pieces

0.128…0.205 mm2 (26…24 AWG), Cat. 5e, requires crimp tool for assembly

1585A-JCRIMP

Crimp tool, 9300-RADES

Remote access dial-in kit

56 Kbps modem connection to devices on an Ethernet network

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

Page 9

1756 ControlLogix Communication Modules Specifications

Stratix Switches To effectively manage real-time control and information flow throughout the manufacturing and IT enterprise, Rockwell Automation offers a full portfolio of industrial Ethernet switches and media, including a line of Stratix switches integrated with Cisco technology. The Stratix line of switches includes modular managed, fixed managed, and unmanaged switches. If your application

Select

• • • • •

Requires Layer 3 routing Integrates enterprise and manufacturing environments Manages multicast traffic Requires diagnostics data Requires security options

Stratix 8300™ modular, managed switch

• • • •

Integrates enterprise and manufacturing environments Manages multicast traffic Requires diagnostics data Requires security options

Stratix 8000™ modular, managed switch

• • • •

Integrates plant floor devices Manages multicast traffic Requires diagnostics data Requires security options

Stratix 6000™ fixed, managed switch

• Requires easy setup and direct replacement of switches • Is a small, isolated network

Stratix 2000™ unmanaged switch

Table 7 - Stratix Managed Switch Specifications Stratix 8000 and Stratix 8300

Stratix 6000

Base

Base

Base

Base

Expansion

Expansion

Feature

1783-MS06T

1783-RMS06T

1783-MS10T

1783-RMS10T

1783-MX08T

1783-MX08F

Ports per module

6

Layer 3 routing

No

Total ports, max

Up to 26(1)

Fiber ports

0…10(1)

10/100 copper ports

4…24(1)

100 base LC fiber ports

0…8(1)

SFP slots

1783-EMS04T

1783-EMS08T

4

9

No

No, - - 1

4

8, - 2(2), 1

10/100/1000 copper ports

2(2), - 100 Mbps fiber support

Yes, Yes

No

No

1 G fiber support

Yes, - No

Yes

CompactFlash memory

Yes

No

No

Power requirements

24/48V DC (18…60V DC)

24V DC (12…48V DC)

10 Yes

No

8 Yes

No

No

(1) Maximum port counts require expansion ports. (2) Two ports each can be used for SFP or 10/100/1000 copper.

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

9