Spec sheet · Allen-Bradley
1756 ControlLogix Communication Modules Specifications
Spec sheet34 pagesPDF 943 KB
Technical data for Allen-Bradley 1756 ControlLogix communication modules, including the 1756-DNB DeviceNet bridge module.
Covers · 1 model
The models it covers
Summary
What is in it
Rockwell Automation technical data covering every 1756 ControlLogix communication module: EtherNet/IP bridges and web server, Stratix switches, ControlNet bridges, the 1756-DNB DeviceNet bridge, DH+ and Remote I/O modules, FOUNDATION Fieldbus linking devices, DH-485 and SynchLink. For each network it gives technical, environmental and certification specifications plus accessories. The DeviceNet section lists data rates, node count, current draw and connector details for the 1756-DNB/E.
Its parts
- Additional Resources
- Available Communication Modules
- EtherNet/IP Network
- Stratix Switches
- ControlNet Network
- DeviceNet Network
- DH+ and Remote I/O Networks
- FOUNDATION Fieldbus Network
- DH-485 Network
- SynchLink Communication
From the sheet
Key facts from this sheet
Each line names its page in the PDF.
Allen-Bradley technical data (publication 1756-TD003D-EN-E) for the 1756 ControlLogix communication modules: EtherNet/IP, ControlNet, DeviceNet, DH+ and Remote I/O, Foundation Fieldbus, DH-485 and SynchLink. For the 1756-DNB it gives the specifications of the series E module (1756-DNB/E), a DeviceNet bridge: data rates, node count, power draw, ports, chassis and power supplies, environment and certifications. It also describes the DeviceNet cable media.
- Module type
- 1756-DNB/E: DeviceNet bridge module for the ControlLogix chassis p. 2, 17
- Data rates
- 1756-DNB/E: 125 Kbps (500 m max), 250 Kbps (250 m max), 500 Kbps (100 m max) p. 17
- Nodes
- 1756-DNB/E: 64 max p. 17
- Power draw
- 1756-DNB/E: 400 mA at 5.1V DC and 0 mA at 24V DC from the backplane; 60 mA at 24V DC from DeviceNet; DeviceNet voltage 11...25V DC p. 17
- Ports
- 1756-DNB/E: one DeviceNet open-style 5- or 10-pin linear plug; USB 2.0 full speed (12 Mbps) p. 17
- Chassis
- 1756-DNB/E: one slot, any slot of a 1756-A4, 1756-A7, 1756-A10, 1756-A13 or 1756-A17 chassis p. 17
- Power supplies
- Standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B; redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2 p. 17
- Operating temperature
- 0…60 °C (32…140 °F); storage -40…85 °C (-40…185 °F) p. 18
- Isolation
- 50V continuous, DeviceNet network to backplane, type tested at 853V AC for 60 s; no isolation between USB and backplane p. 17
- Power dissipation
- 3.5 W (11.9 BTU/hr) p. 17
- Humidity, vibration, shock
- 5…95% noncondensing; 2 g at 10…500 Hz; 30 g operating, 50 g nonoperating shock p. 18
- Connector torque
- DeviceNet connector 0.56…0.79 N•m (5…7 lb•in) p. 17
- Certifications
- The spec sheet states UL and CSA listings, CE, C-Tick, FM approval and ODVA conformance, when the product is marked p. 19
- Document
- Rockwell Automation publication 1756-TD003D-EN-E, January 2012 p. 17
What this sheet walks you through
- Checking the electrical and environmental specifications of the 1756-DNB/E p. 17, 18
- Powering the DeviceNet network to meet CE low voltage and UL rules p. 17
- Choosing DeviceNet cable: KwikLink Lite, KwikLink flat and round thick or thin trunk p. 19
- Building a gateway between networks with several communication modules in one chassis p. 1
- Comparing the ControlLogix communication modules by network p. 2
Good to know
- The spec sheet states the USB port is for temporary local programming only, not a permanent connection, and must not be used in hazardous locations. p. 17
- For CE compliance the DeviceNet network must be powered from an SELV or PELV source. p. 17
- The module is open-style, with no enclosure type rating. p. 17
Questions this sheet answers
How many DeviceNet nodes does the 1756-DNB support?
The 1756-DNB/E supports up to 64 nodes. p. 17
What speeds and cable lengths does the 1756-DNB support?
125 Kbps up to 500 m, 250 Kbps up to 250 m and 500 Kbps up to 100 m (1756-DNB/E). p. 17
How much backplane current does the 1756-DNB draw?
The 1756-DNB/E draws 400 mA at 5.1V DC and 0 mA at 24V DC from the backplane. p. 17
Which chassis does the 1756-DNB fit?
The 1756-A4, 1756-A7, 1756-A10, 1756-A13 and 1756-A17 ControlLogix chassis, in any slot. p. 17
Does the 1756-DNB have a USB port?
The 1756-DNB/E has a USB 2.0 full speed port, meant only for temporary local programming. p. 17
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 4 parts
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file