For the Allen-Bradley 1756-DNB

Page 28

1756 ControlLogix Communication Modules Specifications

Table 26 - Certifications - 1757 Foundation Fieldbus Modules Certification(1)

1757-FFLD2, 1757-FFLD4 c-UL-us

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/IEC EMC Directive, compliant with the following: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with the following: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA nL IIC

FF

Foundation Fieldbus H1 CTK Registered

ODVA - EtherNet/IP

ODVA conformance tested to EtherNet/IP specifications, CI, ControlNet International conformance tested to ControlNet specifications

1757-FFLDC2, 1757-FFLDC4

(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Accessories - Foundation Fieldbus Network Cat. No.

Description

DIN rail

35 x 7.5 or 35 x 15 DIN (EN 50 022), zinc-plated yellow chromate steel

DH-485 Network On the DH-485 network, the controller can send and receive messages to and from other controllers on the network. The DH-485 connection does support remote programming and monitoring via RSLogix 5000 software. Excessive traffic over a DH-485 connection can adversely affect overall performance and can lead to timeouts and loss in RSLogix 5000 configuration performance. IMPORTANT

Use Logix5000™ controllers on DH-485 networks only when you want to add controllers to an existing DH-485 network. For new applications with Logix5000 controllers, we recommend open architecture networks.

You need a 1761-NET-AIC converter for each controller on the DH-485 network. You can have two controllers per one 1761-NET-AIC converter, but you need a different cable for each controller. Connect one controller to port 1 (9-pin connector) and one controller to port 2 (mini-DIN connector). To connect to this port

Use this cable

Port 1 DB-9 RS-232, DTE connection

1747-CP3, 1761-CBL-AC00

Port 2 mini-DIN 8 RS-232 connection

1761-CBL-AP00, 1761-CBL-PM02

28

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

Page 29

1756 ControlLogix Communication Modules Specifications

Table 27 - Technical Specifications - 1756-DH485 Module Attribute

1756-DH485

Communication rate

19.2 Kbps 9600 Kbps

Current draw @ 5.1V DC

850 mA

Current draw @ 24V DC

1.7 mA

Power dissipation

4.5 W

Thermal dissipation

15.4 BTU/hr

Isolation voltage

50V (continuous), basic insulation type, DH485 A/B to backplane, and DH485 A to DH485 B Type tested at 750V DC for 60 s

Slot width

1

Module location

Chassis

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Ports

2 DH-485 9-pin, D-shell

Wire category(1)

2 - on DH485 ports

Wire type

Belden 9463 twinaxial

North American temperature code

T5

Enclosure type rating

None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

29

Page 30

1756 ControlLogix Communication Modules Specifications

Table 28 - Environmental Specifications - 1756-DH485 Module Attribute

1756-DH485

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions CISPR 11

Group 1, Class A

ESD immunity IEC 61000-4-2

4 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±2 kV at 5 kHz on communication ports

Surge transient immunity IEC 61000-4-5

±1 kV line-earth (CM) on communication ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Magnetic field immunity IEC 61000-4-8

30 A/m @ 50 Hz

Table 29 - Certifications - 1756-DH485 Module Certification(1)

1756-DH485 c-UL-us

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CSA

CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with the following: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with AS/NZS CISPR 11; Industrial Emissions

(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

30

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

Page 31

1756 ControlLogix Communication Modules Specifications

Accessories - DH-485 Network Cat. No.

Description

Specifications

1747-CP3

9-pin D-shell, straight; 9-pin D-shell, right angle

3 m (9.8 ft)

1761-CBL-AC00

9-pin D-shell, right angle; 9-pin D-shell, right angle

45 cm (17.7 in.)

1761-CBL-AP00

9-pin D-shell, right angle; 8-pin mini-DIN

45 cm (17.7 in.)

1761-CBL-PM02

9-pin D-shell, straight; 8-pin mini-DIN

2 m (6.5 ft)

1761-NET-AIC

Advanced Interface Converter (AIC+) connects each channel on the 1756-DH485 module to the DH-485 network

20.4…28.8V DC power source required Typical 120 mA 24V DC current draw

9300-RADKIT

Remote access dial-in kit

56 Kbps modem connection to devices on a DH+ network, including the following: • Preconfigured modem • Communication module • DIN rail mounting hardware • Associated cables

SynchLink Communication The SynchLink module provides time synchronization and data broadcasting capabilities for distributed motion and coordinated drive control. The 1756-SYNCH SynchLink module connects a ControlLogix chassis to a SynchLink fiber-optic communication link. The module does the following: • Coordinates Coordinated System Time across multiple ControlLogix chassis • Moves a limited amount of data from one chassis to another at a high speed • Lets one controller consume motion axes data from a controller in another chassis

Table 30 - Technical Specifications - 1756-SYNCH Module Attribute

1756-SYNCH

SynchLink data rate

5 Mbps

Operating wavelength

650 nm (red)

Type of communication

Synchronous

Frame period

50 μs

Frame parameters

3 Flags - 3 bytes Control field - 1 byte Data field - 24 bytes CRC field - 2 bytes

Current draw @ 5.1V DC

1200 mA

Current draw @ 24V DC

3 mA

Power dissipation

6.19 W

Thermal dissipation

21.1 BTU/hr

Slot width

1

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

31

Page 32

1756 ControlLogix Communication Modules Specifications

Table 30 - Technical Specifications - 1756-SYNCH Module (Continued) Attribute

1756-SYNCH

Power supply, redundant

1756-PA1756-PA75R, 1756-PB75R, 1756-PSCA2

Ports

2 fiber optic

Cable fiber type

200/230 micron HCS (Hard Clad Silica)

Cable fiber termination type

Versalink V-System

Cable length

1…300 m (3.28…984.2 ft)

Enclosure type rating

None (open-style)

Table 31 - Environmental Specifications - 1756-SYNCH Module Attribute

1756-SYNCH

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions CISPR 11

Group 1, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz

32

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

Page 33

1756 ControlLogix Communication Modules Specifications

Table 32 - Certifications - 1756-SYNCH Module Certification(1)

1756-SYNCH

UL

UL Listed Industrial Control Equipment. See UL file E65584

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA file LR69960C

CE

European Union 2004/108/EC EMC Directive, compliant with the following: • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions

C-Tick

Australian Radiocommunications Act, compliant with AS/NZS CISPR 11; Industrial Emissions

TÜV

TÜV Certified for Functional Safety Capable of SIL 2

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Accessories - SynchLink Network Cat. No.

Description

1403-CFxxx

Fiber-optic cable assembly (Rockwell Automation)

HCP-M0200T V01RK

Lucent Technologies 200 μm simplex cable

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

33

Page 34

Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this publication are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

Rockwell Automation, Rockwell Software, Allen-Bradley, ControlLogix, ControlLogix-XT, Data Highway Plus, DH+, KwikLink, Logix5000, PLC-5, PanelView, SLC, Stratix 8300, Stratix 8000, Stratix 6000, Stratix 2000, RSLogix, RSLinx, NetLinx, and SynchLink are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.

Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 www.rockwel lautomation.com Power, Control and Information Solutions Headquarters Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444 Europe/Middle East/Africa: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640 Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846

Publication 1756-TD003D-EN-E - January 2012 Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.