Page 19
1756 ControlLogix Communication Modules Specifications
Table 17 - Certifications - 1756-DNB/E DeviceNet Module Certification(1)
1756-DNB/E c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with the following: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with the following: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4X
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
ODVA
ODVA conformance tested to DeviceNet specifications
(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Accessories - DeviceNet Network Cat. No.
Description
KwikLink™ Lite flat media
KwikLink Lite flat media is a newer, ODVA-approved solution for wiring DeviceNet networks. Drop-lines for connecting nodes are added by using the KwikLink Lite two-piece connectors. This cable system supports the intermixing of DeviceNet cable types (thinround with flat). All of the KwikLink Lite connectors provide insulation displacement technology with reduced assembly time.
KwikLink flat media
The KwikLink flat media system provides a modular cabling method with its flat four-wire cable and Insulation Displacement Connectors (IDCs). The KwikLink system allows nodes to be added to the network without severing the trunkline. Cutting or stripping of the trunkline is eliminated, as is the need for predetermined cable lengths.
Round media
Round trunk cable is available in bulk spools or as pre-molded cordsets or patchcords in varying lengths. A wide variety of rugged, durable DeviceNet components is available for use in round trunk systems. Stainless steel versions of round cable system components are also available: • Thick-trunk round media systems use thick cable for maximum DeviceNet trunk line length. • Round media thin-trunk systems use thin cable to reduce maximum trunk line distances with a more compact and cost-effective installation for some applications. Thin-cable outer jacket material is TPE for additional chemical resistance.
For more information on selecting DeviceNet media, see the NetLinx™ Selection Guide, publication NETS-SG001.
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
19
Page 20
1756 ControlLogix Communication Modules Specifications
DH+ and Remote I/O Networks The Data Highway Plus network supports messaging between devices. The remote I/O link connects to remote I/O chassis and other intelligent devices. The 1756-DHRIO module supports messaging between devices on DH+™ networks. The remote I/O functionality enables the module to act as a scanner for transferring digital and block-transfer data to and from remote I/O devices. The 1756-RIO module can act as a scanner or adapter on a remote I/O network. In addition to digital and block-transfer data, the 1756-RIO module transfers analog and specialty data without message instructions.
Example Configuration - DH+ Network PLC-5® PanelView™ Plus
SLC™ 5/04
1784-U2DHP RSLogix 5000
ControlLogix 1756-DHRIO
Example Configuration - Remote I/O Network
1756-DHRIO as a Remote I/O Scanner
1791 I/O
1794 I/O
PLC-5
20
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
PanelView Plus
1756-RIO as a Remote I/O Adapter
Page 21
1756 ControlLogix Communication Modules Specifications
Table 18 - Technical Specifications - 1756 DH+ and Remote I/O Modules Attribute
1756-DHRIO
1756-RIO/B
Communication rate
57.6 Kbps, 115.2 Kbps, 230.4 Kbps
57.6 Kbps, 115.2 Kbps, 230.4 Kbps
Remote I/O communication
Remote I/O scanner only 32 logical rack connections per remote I/O channel 16 block-transfer connections per remote I/O channel
Remote I/O scanner or adapter 32 physical racks (0…76), any combination of rack size and block transfers
Connections supported, max
32
10 scheduled I/O
Current draw @ 5.1V DC
850 mA
450 mA
Current draw @ 24V DC
1.7 mA
5 mA
Power dissipation
4.5 W
2.5 W
Thermal dissipation
15.4 BTU/hr
8.5 BTU/hr
Isolation voltage
30V (continuous), basic insulation type, DHRIO A/B to backplane, and DHRIO A/programming port to DHRIO B No isolation between DHRIO A and Programming port Type tested at 877V DC for 60 s
50V (continuous), basic insulation type, RIO communication lines to backplane Type tested at 500V AC for 60 s
Slot width
1
Module location
Chassis-based, any slot
Chassis
1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17
Power supply, standard
1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant
1756-PA75R, 1756-PB75R, 1756-PSCA2
Ports
2, individually selectable for DH+ or remote I/O
1 for remote I/O
Screw terminal torque, 0.5…0.6 N•m (5…7 lb•in)
Wire size
0.519 mm2 (20 AWG) Belden 9463 copper twinaxial
Wire category(1)
1 - on DHRIO ports 3 - on local programming port
North American temperature code
T4A
IEC temperature code
T4
Enclosure type rating
None (open-style)
2 - on RIO ports, (1) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
21
Page 22
1756 ControlLogix Communication Modules Specifications
Table 19 - Environmental Specifications - 1756 DH+ and Remote I/O Modules Attribute
1756-DHRIO
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions CISPR 11
Group 1, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on DHRIO ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on DHRIO ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
22
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
1756-RIO/B
±2 kV at 5 kHz on RIO ports
Page 23
1756 ControlLogix Communication Modules Specifications
Table 20 - Certifications - 1756 DH+ and Remote I/O Modules Certification(1)
1756-DHRIO c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with the following: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with the following: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4X, TÜV
TÜV Certified for Functional Safety: Capable of SIL 2, 1756-RIO, (1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Table 21 - Technical Specifications - 1756 DH+ and Remote I/O XT Module Attribute
1756-DHRIOXT
Communication rate
57.6 Kbps, 115.2 Kbps, 230.4 Kbps
DH+ communication connections
32 DH+ messages per DH+ module
Remote I/O communication connections
Remote I/O scanner only 32 logical rack connections per remote I/O channel 16 block-transfer connections per remote I/O channel
Connections supported, max
32
Current draw @ 5.1V DC
850 mA
Current draw @ 24V DC
1.7 mA
Power dissipation
4.5 W
Thermal dissipation
15.4 BTU/hr
Isolation voltage
30V (continuous), basic insulation type, DHRIO A/B to backplane, and DHRIO A/programming port to DHRIO B No Isolation between DHRIO A and Programming port Type tested at 853V AC for 60 s
Slot width
1
Module location
Chassis-based, any slot
Chassis
1756-A4LXT, 1756-A5XT, 1756-A7LXT
Power supply, standard
1756-PBXT
Power supply, redundant
None
Ports
2, individually selectable for DH+ or remote I/O
Screw terminal torque
0.5…0.6 N•m (5…7 lb•in)
Wire size
0.519 mm2 (20 in.) Belden 9463 copper twinaxial
Wire category
1 - on DHRIO ports 3 - on local programming port(1)
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
23
Page 24
1756 ControlLogix Communication Modules Specifications
Table 21 - Technical Specifications - 1756 DH+ and Remote I/O XT Module (Continued) Attribute
1756-DHRIOXT
North American temperature code
T4A
IEC temperature code
T4
Enclosure type rating
None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Table 22 - Environmental Specifications - 1756 DH+ and Remote I/O XT Module Attribute
1756-DHRIOXT
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
-25…70 °C (-13…158 °F)
Temperature, surrounding air, max
70 °C (158 °F)
Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions CISPR 11
Group 1, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on DHRIO ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on DHRIO ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
24
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
Page 25
1756 ControlLogix Communication Modules Specifications
Table 23 - Certifications - 1756 DH+ and Remote I/O XT Module Certification(1)
1756-DHRIOXT c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2004/108/IEC EMC Directive, compliant with the following: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with the following: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4X
TÜV
TÜV Certified for Functional Safety: Capable of SIL 2
(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Accessories - DH+ and Remote I/O Networks Cat. No.
Description
Specifications
1770-CD
Cable to connect communication module to DH+ network
Belden 9463 twinaxial
9300-RADKIT
Remote access dial-in kit
56 Kbps modem connection to devices on a DH+ network, including the following: • Preconfigured modem • Communication module • DIN rail mounting hardware • Associated cables
FOUNDATION Fieldbus Network The FOUNDATION Fieldbus network is a communication network created by the Fieldbus Foundation. It is a protocol designed for robust, distributed control of process control applications. Devices connected by a FOUNDATION Fieldbus network can be used for sophisticated, highlydistributed process control.
If your application bridges from
Select
Description
EtherNet/IP network
1757-FFLD2 1757-FFLD4
The 1757-FFLDx linking device bridges from an Ethernet/IP network to either two or four H1 ports. Each H1 port can support the recommended maximum 8…10 devices. Each H1 network can support a maximum of 16 publisher and 16 subscriber VCR connections.
ControlNet network
1757-FFLDC2 1757-FFLDC4
The 1757-FFLDCx linking device bridges from a ControlNet network to either two or four H1 ports. Each H1 port can support the recommended maximum 8…10 devices. Each H1 network can support a maximum of 64 publisher and 64 subscriber VCR connections. The 1757-FFLDCx linking device is compatible with ControlLogix redundancy and supports redundant ControlNet media.
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
25
Page 26
1756 ControlLogix Communication Modules Specifications
Table 24 - Technical Specifications - 1757 FOUNDATION Fieldbus Modules Attribute
1757-FFLD2
Foundation Fieldbus communication rate
31.25 Kbps
EtherNet/IP communication rate
10/100 Mbps, - 5 Mbps
ControlNet communication rate (1)
Number of H1 networks per linking device, max
2
Number of Fieldbus devices per H1 network, max
16 (8…10 recommended)
Number of Fieldbus devices per linking device, max
32
(2) (3)
1757-FFLD4
1757-FFLDC2
1757-FFLDC4
4
2
4
64
32
64
Current draw @ 24V DC
300 mA
450 mA
Inrush current
1.5 A
Power dissipation, 9.6 W
Isolation voltage
50V (continuous), basic insulation type Fieldbus to system backplane and Ethernet network to system backplane Type tested @ 500V AC for 60 s
50V (continuous), basic insulation type tested at 500V AC for 60 s, Fieldbus to system backplane, ControlNet network to system backplane, and ControlNet Channel A to ControlNet Channel B Type tested @ 500V AC for 60 s
Module location
DIN rail or panel
Power supply
User-supplied 24V DC
Ports
2 H1 FOUNDATION Fieldbus 1 Ethernet RJ45
Wire category(3)
2 - on shielded Fieldbus port 3 - on power port 2 - on communication port
Wire size
DC power connection: 0.2…1.5 mm2 (26…16 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater, 1.2 mm (0.05 in.) insulation, max Fieldbus connections: 0.8 mm2 (18 AWG) solid or stranded shielded twisted pair copper wire rated at 75 °C (167 °F) or greater, 1.2 mm (0.05 in.) insulation, max Ethernet connections: RJ45 connector according to IEC 6003-7, 2 or 4 pair Category 5e min cable according to TIA 568-B.1, or Category 5 cable according to ISO/IEC 24702
Screw terminal torque
0.34 N•m (3 lb•in) on power and Fieldbus wire connections
Panel mount screw torque
1.1…1.8 N•m (10…16 lb•in)
North American temperature code
T4
IEC temperature code
T4
Enclosure type rating
None (open-style)
4 H1 FOUNDATION Fieldbus 1 Ethernet RJ45
2 H1 FOUNDATION Fieldbus 1 ControlNet BNC
DC power connection: 0.2…1.5 mm2 (26…16 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater 1.2 mm (3/64 in.) insulation max Fieldbus connections: 0.8 mm2 (18 AWG) solid or stranded shielded twisted-pair copper wire rated at 75 °C (167 °F) or greater 1.2 mm (3/64 in.) insulation max
(1) Each network defined as a Foundation Fieldbus 31.25 Kbps H1 network. (2) 24V DC (± 20%). (3) 24V DC (±10%).
26
4 H1 FOUNDATION Fieldbus 1 ControlNet BNC
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
Page 27
1756 ControlLogix Communication Modules Specifications
Table 25 - Environmental Specifications - 1757 FOUNDATION Fieldbus Modules Attribute
1757-FFLD2, 1756-FFLD4
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
5 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
15 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Emissions CISPR 11
Group 1, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 80…2700 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
EFT/B immunity IEC 61000-4-4
±2 kV at 5 kHz on power ports ±2 kV at 5 kHz on shielded Fieldbus ports ±2 kV at 5 kHz on Ethernet ports
±2 kV at 5 kHz on shielded Fieldbus ports ±2 kV at 5 kHz on ControlNet ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on shielded Fieldbus ports ±2 kV line-earth (CM) on shielded Ethernet ports
±2 kV line-earth (CM) on shielded Fieldbus ports ±2 kV line-earth (CM) on shielded ControlNet ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on power ports, shielded Fieldbus ports, and Ethernet ports
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on ControlNet and shielded Fieldbus ports
Magnetic field immunity IEC 61000-4-8
30 A/m long duration at 50 Hz
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
1757-FFLDC2, 1757-FFLDC4