Page 19

1756 ControlLogix Communication Modules Specifications

Table 17 - Certifications - 1756-DNB/E DeviceNet Module Certification(1)

1756-DNB/E c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with the following: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with the following: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4X

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

ODVA

ODVA conformance tested to DeviceNet specifications

(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Accessories - DeviceNet Network Cat. No.

Description

KwikLink™ Lite flat media

KwikLink Lite flat media is a newer, ODVA-approved solution for wiring DeviceNet networks. Drop-lines for connecting nodes are added by using the KwikLink Lite two-piece connectors. This cable system supports the intermixing of DeviceNet cable types (thinround with flat). All of the KwikLink Lite connectors provide insulation displacement technology with reduced assembly time.

KwikLink flat media

The KwikLink flat media system provides a modular cabling method with its flat four-wire cable and Insulation Displacement Connectors (IDCs). The KwikLink system allows nodes to be added to the network without severing the trunkline. Cutting or stripping of the trunkline is eliminated, as is the need for predetermined cable lengths.

Round media

Round trunk cable is available in bulk spools or as pre-molded cordsets or patchcords in varying lengths. A wide variety of rugged, durable DeviceNet components is available for use in round trunk systems. Stainless steel versions of round cable system components are also available: • Thick-trunk round media systems use thick cable for maximum DeviceNet trunk line length. • Round media thin-trunk systems use thin cable to reduce maximum trunk line distances with a more compact and cost-effective installation for some applications. Thin-cable outer jacket material is TPE for additional chemical resistance.

For more information on selecting DeviceNet media, see the NetLinx™ Selection Guide, publication NETS-SG001.

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

19

Page 20

1756 ControlLogix Communication Modules Specifications

DH+ and Remote I/O Networks The Data Highway Plus network supports messaging between devices. The remote I/O link connects to remote I/O chassis and other intelligent devices. The 1756-DHRIO module supports messaging between devices on DH+™ networks. The remote I/O functionality enables the module to act as a scanner for transferring digital and block-transfer data to and from remote I/O devices. The 1756-RIO module can act as a scanner or adapter on a remote I/O network. In addition to digital and block-transfer data, the 1756-RIO module transfers analog and specialty data without message instructions.

Example Configuration - DH+ Network PLC-5® PanelView™ Plus

SLC™ 5/04

1784-U2DHP RSLogix 5000

ControlLogix 1756-DHRIO

Example Configuration - Remote I/O Network

1756-DHRIO as a Remote I/O Scanner

1791 I/O

1794 I/O

PLC-5

20

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

PanelView Plus

1756-RIO as a Remote I/O Adapter

Page 21

1756 ControlLogix Communication Modules Specifications

Table 18 - Technical Specifications - 1756 DH+ and Remote I/O Modules Attribute

1756-DHRIO

1756-RIO/B

Communication rate

57.6 Kbps, 115.2 Kbps, 230.4 Kbps

57.6 Kbps, 115.2 Kbps, 230.4 Kbps

Remote I/O communication

Remote I/O scanner only 32 logical rack connections per remote I/O channel 16 block-transfer connections per remote I/O channel

Remote I/O scanner or adapter 32 physical racks (0…76), any combination of rack size and block transfers

Connections supported, max

32

10 scheduled I/O

Current draw @ 5.1V DC

850 mA

450 mA

Current draw @ 24V DC

1.7 mA

5 mA

Power dissipation

4.5 W

2.5 W

Thermal dissipation

15.4 BTU/hr

8.5 BTU/hr

Isolation voltage

30V (continuous), basic insulation type, DHRIO A/B to backplane, and DHRIO A/programming port to DHRIO B No isolation between DHRIO A and Programming port Type tested at 877V DC for 60 s

50V (continuous), basic insulation type, RIO communication lines to backplane Type tested at 500V AC for 60 s

Slot width

1

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Ports

2, individually selectable for DH+ or remote I/O

1 for remote I/O

Screw terminal torque, 0.5…0.6 N•m (5…7 lb•in)

Wire size

0.519 mm2 (20 AWG) Belden 9463 copper twinaxial

Wire category(1)

1 - on DHRIO ports 3 - on local programming port

North American temperature code

T4A

IEC temperature code

T4

Enclosure type rating

None (open-style)

2 - on RIO ports, (1) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

21

Page 22

1756 ControlLogix Communication Modules Specifications

Table 19 - Environmental Specifications - 1756 DH+ and Remote I/O Modules Attribute

1756-DHRIO

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions CISPR 11

Group 1, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on DHRIO ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on DHRIO ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

22

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

1756-RIO/B

±2 kV at 5 kHz on RIO ports

Page 23

1756 ControlLogix Communication Modules Specifications

Table 20 - Certifications - 1756 DH+ and Remote I/O Modules Certification(1)

1756-DHRIO c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with the following: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with the following: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4X, TÜV

TÜV Certified for Functional Safety: Capable of SIL 2, 1756-RIO, (1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Table 21 - Technical Specifications - 1756 DH+ and Remote I/O XT Module Attribute

1756-DHRIOXT

Communication rate

57.6 Kbps, 115.2 Kbps, 230.4 Kbps

DH+ communication connections

32 DH+ messages per DH+ module

Remote I/O communication connections

Remote I/O scanner only 32 logical rack connections per remote I/O channel 16 block-transfer connections per remote I/O channel

Connections supported, max

32

Current draw @ 5.1V DC

850 mA

Current draw @ 24V DC

1.7 mA

Power dissipation

4.5 W

Thermal dissipation

15.4 BTU/hr

Isolation voltage

30V (continuous), basic insulation type, DHRIO A/B to backplane, and DHRIO A/programming port to DHRIO B No Isolation between DHRIO A and Programming port Type tested at 853V AC for 60 s

Slot width

1

Module location

Chassis-based, any slot

Chassis

1756-A4LXT, 1756-A5XT, 1756-A7LXT

Power supply, standard

1756-PBXT

Power supply, redundant

None

Ports

2, individually selectable for DH+ or remote I/O

Screw terminal torque

0.5…0.6 N•m (5…7 lb•in)

Wire size

0.519 mm2 (20 in.) Belden 9463 copper twinaxial

Wire category

1 - on DHRIO ports 3 - on local programming port(1)

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

23

Page 24

1756 ControlLogix Communication Modules Specifications

Table 21 - Technical Specifications - 1756 DH+ and Remote I/O XT Module (Continued) Attribute

1756-DHRIOXT

North American temperature code

T4A

IEC temperature code

T4

Enclosure type rating

None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 22 - Environmental Specifications - 1756 DH+ and Remote I/O XT Module Attribute

1756-DHRIOXT

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

-25…70 °C (-13…158 °F)

Temperature, surrounding air, max

70 °C (158 °F)

Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions CISPR 11

Group 1, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on DHRIO ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on DHRIO ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

24

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

Page 25

1756 ControlLogix Communication Modules Specifications

Table 23 - Certifications - 1756 DH+ and Remote I/O XT Module Certification(1)

1756-DHRIOXT c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/IEC EMC Directive, compliant with the following: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with the following: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4X

TÜV

TÜV Certified for Functional Safety: Capable of SIL 2

(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Accessories - DH+ and Remote I/O Networks Cat. No.

Description

Specifications

1770-CD

Cable to connect communication module to DH+ network

Belden 9463 twinaxial

9300-RADKIT

Remote access dial-in kit

56 Kbps modem connection to devices on a DH+ network, including the following: • Preconfigured modem • Communication module • DIN rail mounting hardware • Associated cables

FOUNDATION Fieldbus Network The FOUNDATION Fieldbus network is a communication network created by the Fieldbus Foundation. It is a protocol designed for robust, distributed control of process control applications. Devices connected by a FOUNDATION Fieldbus network can be used for sophisticated, highlydistributed process control.

If your application bridges from

Select

Description

EtherNet/IP network

1757-FFLD2 1757-FFLD4

The 1757-FFLDx linking device bridges from an Ethernet/IP network to either two or four H1 ports. Each H1 port can support the recommended maximum 8…10 devices. Each H1 network can support a maximum of 16 publisher and 16 subscriber VCR connections.

ControlNet network

1757-FFLDC2 1757-FFLDC4

The 1757-FFLDCx linking device bridges from a ControlNet network to either two or four H1 ports. Each H1 port can support the recommended maximum 8…10 devices. Each H1 network can support a maximum of 64 publisher and 64 subscriber VCR connections. The 1757-FFLDCx linking device is compatible with ControlLogix redundancy and supports redundant ControlNet media.

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

25

Page 26

1756 ControlLogix Communication Modules Specifications

Table 24 - Technical Specifications - 1757 FOUNDATION Fieldbus Modules Attribute

1757-FFLD2

Foundation Fieldbus communication rate

31.25 Kbps

EtherNet/IP communication rate

10/100 Mbps, - 5 Mbps

ControlNet communication rate (1)

Number of H1 networks per linking device, max

2

Number of Fieldbus devices per H1 network, max

16 (8…10 recommended)

Number of Fieldbus devices per linking device, max

32

(2) (3)

1757-FFLD4

1757-FFLDC2

1757-FFLDC4

4

2

4

64

32

64

Current draw @ 24V DC

300 mA

450 mA

Inrush current

1.5 A

Power dissipation, 9.6 W

Isolation voltage

50V (continuous), basic insulation type Fieldbus to system backplane and Ethernet network to system backplane Type tested @ 500V AC for 60 s

50V (continuous), basic insulation type tested at 500V AC for 60 s, Fieldbus to system backplane, ControlNet network to system backplane, and ControlNet Channel A to ControlNet Channel B Type tested @ 500V AC for 60 s

Module location

DIN rail or panel

Power supply

User-supplied 24V DC

Ports

2 H1 FOUNDATION Fieldbus 1 Ethernet RJ45

Wire category(3)

2 - on shielded Fieldbus port 3 - on power port 2 - on communication port

Wire size

DC power connection: 0.2…1.5 mm2 (26…16 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater, 1.2 mm (0.05 in.) insulation, max Fieldbus connections: 0.8 mm2 (18 AWG) solid or stranded shielded twisted pair copper wire rated at 75 °C (167 °F) or greater, 1.2 mm (0.05 in.) insulation, max Ethernet connections: RJ45 connector according to IEC 6003-7, 2 or 4 pair Category 5e min cable according to TIA 568-B.1, or Category 5 cable according to ISO/IEC 24702

Screw terminal torque

0.34 N•m (3 lb•in) on power and Fieldbus wire connections

Panel mount screw torque

1.1…1.8 N•m (10…16 lb•in)

North American temperature code

T4

IEC temperature code

T4

Enclosure type rating

None (open-style)

4 H1 FOUNDATION Fieldbus 1 Ethernet RJ45

2 H1 FOUNDATION Fieldbus 1 ControlNet BNC

DC power connection: 0.2…1.5 mm2 (26…16 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater 1.2 mm (3/64 in.) insulation max Fieldbus connections: 0.8 mm2 (18 AWG) solid or stranded shielded twisted-pair copper wire rated at 75 °C (167 °F) or greater 1.2 mm (3/64 in.) insulation max

(1) Each network defined as a Foundation Fieldbus 31.25 Kbps H1 network. (2) 24V DC (± 20%). (3) 24V DC (±10%).

26

4 H1 FOUNDATION Fieldbus 1 ControlNet BNC

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

Page 27

1756 ControlLogix Communication Modules Specifications

Table 25 - Environmental Specifications - 1757 FOUNDATION Fieldbus Modules Attribute

1757-FFLD2, 1756-FFLD4

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

5 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

15 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Emissions CISPR 11

Group 1, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz

10V/m with 1 kHz sine-wave 80% AM from 80…2700 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz

EFT/B immunity IEC 61000-4-4

±2 kV at 5 kHz on power ports ±2 kV at 5 kHz on shielded Fieldbus ports ±2 kV at 5 kHz on Ethernet ports

±2 kV at 5 kHz on shielded Fieldbus ports ±2 kV at 5 kHz on ControlNet ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on shielded Fieldbus ports ±2 kV line-earth (CM) on shielded Ethernet ports

±2 kV line-earth (CM) on shielded Fieldbus ports ±2 kV line-earth (CM) on shielded ControlNet ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on power ports, shielded Fieldbus ports, and Ethernet ports

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on ControlNet and shielded Fieldbus ports

Magnetic field immunity IEC 61000-4-8

30 A/m long duration at 50 Hz

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

1757-FFLDC2, 1757-FFLDC4

27