For the Allen-Bradley 1756-DNB

Page 10

1756 ControlLogix Communication Modules Specifications

Table 8 - Stratix Unmanaged Switch Specifications Stratix 2000 Feature

1783-US03T01F

1783-US05T

1783-US06T01F

1783-US08T

Ports per module

4

5

7

8

Fiber ports

1, 1, 10/100 copper ports

3

5

6

8

100 base LC fiber ports

1, 1, 100 Mbps fiber support

Yes, Yes, CompactFlash memory

No

No

No

No

Power requirements

20V AC (10…24V AC) 24V DC (10…35V DC)

ControlNet Network The ControlNet network is an open, control network for real-time, high-throughput applications. The ControlNet network uses the Common Industrial Protocol (CIP) to combine the functionality of an I/O network and a peer-to-peer network providing high-speed performance for both functions. The ControlNet network gives you deterministic, repeatable transfers of all mission-critical control data in addition to supporting transfers of non-time-critical data. I/O updates and controller-to-controller interlocking always take precedence over program uploads and downloads, and messaging.

If your application requires

Select this interface

128 ControlNet connections per communication module

1756-CN2/B 1756-CN2R/B 1756-CN2RXT/B

Control in environments where temperatures range from -25…70 ° C (-13…158 ° F)

1756-CN2RXT

40…48 ControlNet connections per communication module

1756-CNB 1756-CNBR

Connect to Other Devices via a ControlNet Network The RSLogix 5000 Enterprise Series software supports a generic ControlNet module that allows connections to ControlNet nodes for which there is no specific support currently available in the programming software. A module configured as a generic ControlNet module communicates with the controller in the form of input, output, status, and configuration tags. For example, use the generic module configuration to set up communication between a ControlLogix controller and a 1203-CN1 ControlNet communication module. Then use the CIP generic MSG instruction type to send and receive messages from the 1203-CN1 module.

10

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

Page 11

1756 ControlLogix Communication Modules Specifications

Table 9 - Technical Specifications - 1756 ControlNet Modules Attribute

1756-CN2/B

1756-CN2R/B

1756-CNB/E

1756-CNBR/E

Configuration

Standard

Redundant

Standard

Redundant

ControlNet communication rate

5 Mbps

Logix communication connections

128

40…48

Connections supported, max

131(3)

64

Number of nodes, max

99

Current draw @ 5.1V DC

1100 mA

Current draw @ 24V DC

3 mA

Power dissipation

5.7 W

6.7 W

5.14 W

Thermal dissipation

19.5 BTU/hr

22.9 BTU/hr

17.5 BTU/hr

Isolation voltage

Standard: 30V (continuous), basic insulation type, ControlNet network to backplane Redundant: 30V (continuous), basic insulation type, ControlNet A/B to backplane, and ControlNet A to ControlNet B No isolation between NAP or USB and backplane Type tested at 500V AC for 60 s

Weight, approx.

0.26 kg (0.57 lb)

Slot width

1

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

ControlNet port

1 ControlNet BNC

ControlNet cable

1786-RG6 quad shield RG6 coaxial cable

USB port(1)

USB 1.1, full speed (12 Mbps)

NAP port, - NAP cable, - Wire category(2)

1 - on ControlNet ports 3 - on USB ports

North American temperature code

T4A

IEC temperature code

T4

Enclosure type rating

None (open-style)

1300 mA

970 mA 1.7 mA

0.293 kg (0.64 lb)

2 ControlNet BNC

0.26 kg (0.57 lb)

0.293 kg (0.64 lb)

1 ControlNet BNC

2 ControlNet BNC, - 1 NAP RJ45

1 NAP RJ45

1786-CP 1 - on ControlNet ports 3 - on NAP ports

(1) The USB port is intended for temporary local programming purposes only and not intended for permanent connection. Do not use the USB port in hazardous locations. (2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. (3) 128 connections are available for standard use. An additional three connections are reserved for redundant control.

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

11

Page 12

1756 ControlLogix Communication Modules Specifications

Table 10 - Environmental Specifications - 1756 ControlNet Modules Attribute

1756-CN2/B, 1756-CN2R/B

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions CISPR 11

Group 1, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±3 kV at 5 kHz on ControlNet ports

±2 kV at 5 kHz on ControlNet ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on ControlNet ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

12

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

1756-CNB/E, 1756-CNBR/E

Page 13

1756 ControlLogix Communication Modules Specifications

Table 11 - Certifications - 1756 ControlNet Modules Certification(1)

1756-CN2/B, 1756-CN2R/B, 1756-CNB/E, 1756-CNBR/E c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with the following: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with the following: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4X

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

TÜV

TÜV Certified for Functional Safety: Capable of SIL 2

CI

ControlNet International conformance tested to ControlNet specifications

(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

13

Page 14

1756 ControlLogix Communication Modules Specifications

Table 12 - Technical Specifications - 1756 ControlNet-XT Module Attribute

1756-CN2RXT/B

Configuration

Redundant

ControlNet communication rate

5 Mbps

Logix communication connections

128

Connections supported, max

131(3)

Number of nodes, max

99

Current draw @ 5.1V DC

1300 mA

Current draw @ 24V DC

3 mA

Power dissipation

6.7 W

Thermal dissipation

22.9 BTU/hr

Isolation voltage

30V (continuous), basic insulation type, ControlNet A/B to backplane, and ControlNet A to ControlNet B No isolation between USB and backplane Type tested at 500V AC for 60 s

Weight, approx.

0.293 kg (0.64 lb)

Slot width

1

Module location

Chassis-based, any slot

Chassis

1756-A4LXT, 1756-A5XT, 1756-A7LXT

Power supply, standard

1756-PAXT, 1756-PBXT

Power supply, redundant

None

ControlNet port

2 ControlNet BNC

ControlNet cable

1786-RG6 quad shield RG6 coaxial cable

USB port(1)

USB 1.1, full speed (12 Mbps)

Wire category(2)

2 - on ControlNet ports 3 - on USB port

North American temperature code

T4A

IEC temperature code

T4

Enclosure type rating

None (open-style)

(1) The USB port is intended for temporary local programming purposes only and not intended for permanent connection. Do not use the USB port in hazardous locations. (2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. (3) 128 connections are available for standard use. An additional three connections are reserved for redundant control.

14

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

Page 15

1756 ControlLogix Communication Modules Specifications

Table 13 - Environmental Specifications - 1756 ControlNet-XT Module Attribute

1756-CN2RXT/B

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

-25…70 °C (-13…158 °F)

Temperature, surrounding air, max

70 °C (158 °F)

Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions CISPR 11

Group 1, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±2 kV at 5 kHz on ControlNet ports

Surge transient immunity IEC 61000-4-5

±1 kV line-earth (CM) on ControlNet port

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

15

Page 16

1756 ControlLogix Communication Modules Specifications

Table 14 - Certifications - 1756 ControlNet-XT Module Certification(1)

1756-CN2RXT/B c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/IEC EMC Directive, compliant with the following: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with the following: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4X

TÜV

TÜV Certified for Functional Safety: Capable of SIL 2

CI

ControlNet International conformance tested to ControlNet specifications

(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Accessories - ControlNet Network Cat. No.

Description

Taps 1786-TCT2BD1

T-tap straight IP67 rated

1786-TPR

T-tap right angle

1786-TPS

T-tap straight

1786-TPYR

Y-tap right angle

1786-TPYS

Y-tap straight

Cables 1786-CP

Programming cable to ControlNet RJ45 port

1786-RG6

ControlNet network, shield high-flex cable

1756-RG6F

ControlNet network, quad-shield high-flex coax cable

Other 1786-TNCLXT4

ControlNet IP67 termination resistor

1786-XT

ControlNet termination resistor

Repeaters 1786-RPA

ControlNet modular repeater adapter

1786-RPCD

ControlNet coaxial hub repeater

1786-RPFRL

ControlNet fiber ring repeater, long distance

1786-RPFRXL

ControlNet fiber ring repeater, extra long distance

1786-RPFS

ControlNet fiber repeater, short distance

1786-RPFM

ControlNet fiber repeater, medium distance

For more information, see ControlNet Media System Components List, publication AG-PA002.

16

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

Page 17

1756 ControlLogix Communication Modules Specifications

DeviceNet Network The DeviceNet network is an open, low-level network that provides connections between simple industrial devices, such as sensors and actuators, and higher-level devices, such as controllers and computers. The DeviceNet network uses the proven Common Industrial Protocol (CIP) to provide the control, configure, and data collection capabilities for industrial devices. ATTENTION: If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. Table 15 - Technical Specifications - 1756-DNB/E DeviceNet Module Attribute

1756-DNB/E

DeviceNet communication rate

125 Kbps (500 m max) 250 Kbps (250 m max) 500 Kbps (100 m max)

Number of nodes, max

64

Current draw @ 5.1V DC

400 mA

Current draw @ 24V DC

0 mA

DeviceNet current draw @ 24V DC

60 mA

DeviceNet voltage range

11...25V DC CL 2/SELV

Power dissipation

3.5 W

Thermal dissipation

11.9 BTU/hr

Isolation voltage

50V (continuous), basic insulation type, DeviceNet network to backplane Type tested at 853V AC for 60 s No isolation between USB and backplane

Slot width

1

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

DeviceNet power

To comply with the CE low voltage directive (LVD), the DeviceNet network must be powered from a source compliant with the safety extra low voltage (SELV) or protected extra low voltage (PELV). To comply with UL restrictions, the DeviceNet network must be powered from a source compliant with Class 2 or limited voltage/current.

DeviceNet port

1 DeviceNet open-style 5-or 10-pin linear plug

DeviceNet connector torque

0.56…0.79 N•m (5…7 lb•in)

USB port(1)

USB 2.0, full speed (12 Mbps)

Wire category(2)

1 - On DeviceNet ports 3 - On USB ports

North American temperature code

T4A

IEC temperature code

T4

Enclosure type rating

None (open-style)

(1) The USB port is intended for temporary local programming purposes only and not intended for permanent connection. Do not use the USB port in hazardous locations. (2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. Refer to the DeviceNet Media Design and Planning Guide, publication DNET-UM072, for information specific to your DeviceNet network.

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012

17

Page 18

1756 ControlLogix Communication Modules Specifications

Table 16 - Environmental Specifications - 1756-DNB/E DeviceNet Module Attribute

1756-DNB/E

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions CISPR 11

Group 1, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±3 kV at 5 kHz on DeviceNet ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on DeviceNet ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

18

Rockwell Automation Publication 1756-TD003D-EN-E - January 2012