The text of a spec sheet · part 2 of 4
1756 ControlLogix Communication Modules Specifications, pages 10 to 18
Pages 10 to 18 of 34
The original document is the PDF (943 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-DNB
Page 10
1756 ControlLogix Communication Modules Specifications
Table 8 - Stratix Unmanaged Switch Specifications Stratix 2000 Feature
1783-US03T01F
1783-US05T
1783-US06T01F
1783-US08T
Ports per module
4
5
7
8
Fiber ports
1, 1, 10/100 copper ports
3
5
6
8
100 base LC fiber ports
1, 1, 100 Mbps fiber support
Yes, Yes, CompactFlash memory
No
No
No
No
Power requirements
20V AC (10…24V AC) 24V DC (10…35V DC)
ControlNet Network The ControlNet network is an open, control network for real-time, high-throughput applications. The ControlNet network uses the Common Industrial Protocol (CIP) to combine the functionality of an I/O network and a peer-to-peer network providing high-speed performance for both functions. The ControlNet network gives you deterministic, repeatable transfers of all mission-critical control data in addition to supporting transfers of non-time-critical data. I/O updates and controller-to-controller interlocking always take precedence over program uploads and downloads, and messaging.
If your application requires
Select this interface
128 ControlNet connections per communication module
1756-CN2/B 1756-CN2R/B 1756-CN2RXT/B
Control in environments where temperatures range from -25…70 ° C (-13…158 ° F)
1756-CN2RXT
40…48 ControlNet connections per communication module
1756-CNB 1756-CNBR
Connect to Other Devices via a ControlNet Network The RSLogix 5000 Enterprise Series software supports a generic ControlNet module that allows connections to ControlNet nodes for which there is no specific support currently available in the programming software. A module configured as a generic ControlNet module communicates with the controller in the form of input, output, status, and configuration tags. For example, use the generic module configuration to set up communication between a ControlLogix controller and a 1203-CN1 ControlNet communication module. Then use the CIP generic MSG instruction type to send and receive messages from the 1203-CN1 module.
10
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
Page 11
1756 ControlLogix Communication Modules Specifications
Table 9 - Technical Specifications - 1756 ControlNet Modules Attribute
1756-CN2/B
1756-CN2R/B
1756-CNB/E
1756-CNBR/E
Configuration
Standard
Redundant
Standard
Redundant
ControlNet communication rate
5 Mbps
Logix communication connections
128
40…48
Connections supported, max
131(3)
64
Number of nodes, max
99
Current draw @ 5.1V DC
1100 mA
Current draw @ 24V DC
3 mA
Power dissipation
5.7 W
6.7 W
5.14 W
Thermal dissipation
19.5 BTU/hr
22.9 BTU/hr
17.5 BTU/hr
Isolation voltage
Standard: 30V (continuous), basic insulation type, ControlNet network to backplane Redundant: 30V (continuous), basic insulation type, ControlNet A/B to backplane, and ControlNet A to ControlNet B No isolation between NAP or USB and backplane Type tested at 500V AC for 60 s
Weight, approx.
0.26 kg (0.57 lb)
Slot width
1
Module location
Chassis-based, any slot
Chassis
1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17
Power supply, standard
1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant
1756-PA75R, 1756-PB75R, 1756-PSCA2
ControlNet port
1 ControlNet BNC
ControlNet cable
1786-RG6 quad shield RG6 coaxial cable
USB port(1)
USB 1.1, full speed (12 Mbps)
NAP port, - NAP cable, - Wire category(2)
1 - on ControlNet ports 3 - on USB ports
North American temperature code
T4A
IEC temperature code
T4
Enclosure type rating
None (open-style)
1300 mA
970 mA 1.7 mA
0.293 kg (0.64 lb)
2 ControlNet BNC
0.26 kg (0.57 lb)
0.293 kg (0.64 lb)
1 ControlNet BNC
2 ControlNet BNC, - 1 NAP RJ45
1 NAP RJ45
1786-CP 1 - on ControlNet ports 3 - on NAP ports
(1) The USB port is intended for temporary local programming purposes only and not intended for permanent connection. Do not use the USB port in hazardous locations. (2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. (3) 128 connections are available for standard use. An additional three connections are reserved for redundant control.
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
11
Page 12
1756 ControlLogix Communication Modules Specifications
Table 10 - Environmental Specifications - 1756 ControlNet Modules Attribute
1756-CN2/B, 1756-CN2R/B
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions CISPR 11
Group 1, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±3 kV at 5 kHz on ControlNet ports
±2 kV at 5 kHz on ControlNet ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on ControlNet ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
12
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
1756-CNB/E, 1756-CNBR/E
Page 13
1756 ControlLogix Communication Modules Specifications
Table 11 - Certifications - 1756 ControlNet Modules Certification(1)
1756-CN2/B, 1756-CN2R/B, 1756-CNB/E, 1756-CNBR/E c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with the following: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with the following: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4X
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
TÜV
TÜV Certified for Functional Safety: Capable of SIL 2
CI
ControlNet International conformance tested to ControlNet specifications
(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
13
Page 14
1756 ControlLogix Communication Modules Specifications
Table 12 - Technical Specifications - 1756 ControlNet-XT Module Attribute
1756-CN2RXT/B
Configuration
Redundant
ControlNet communication rate
5 Mbps
Logix communication connections
128
Connections supported, max
131(3)
Number of nodes, max
99
Current draw @ 5.1V DC
1300 mA
Current draw @ 24V DC
3 mA
Power dissipation
6.7 W
Thermal dissipation
22.9 BTU/hr
Isolation voltage
30V (continuous), basic insulation type, ControlNet A/B to backplane, and ControlNet A to ControlNet B No isolation between USB and backplane Type tested at 500V AC for 60 s
Weight, approx.
0.293 kg (0.64 lb)
Slot width
1
Module location
Chassis-based, any slot
Chassis
1756-A4LXT, 1756-A5XT, 1756-A7LXT
Power supply, standard
1756-PAXT, 1756-PBXT
Power supply, redundant
None
ControlNet port
2 ControlNet BNC
ControlNet cable
1786-RG6 quad shield RG6 coaxial cable
USB port(1)
USB 1.1, full speed (12 Mbps)
Wire category(2)
2 - on ControlNet ports 3 - on USB port
North American temperature code
T4A
IEC temperature code
T4
Enclosure type rating
None (open-style)
(1) The USB port is intended for temporary local programming purposes only and not intended for permanent connection. Do not use the USB port in hazardous locations. (2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. (3) 128 connections are available for standard use. An additional three connections are reserved for redundant control.
14
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
Page 15
1756 ControlLogix Communication Modules Specifications
Table 13 - Environmental Specifications - 1756 ControlNet-XT Module Attribute
1756-CN2RXT/B
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
-25…70 °C (-13…158 °F)
Temperature, surrounding air, max
70 °C (158 °F)
Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions CISPR 11
Group 1, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±2 kV at 5 kHz on ControlNet ports
Surge transient immunity IEC 61000-4-5
±1 kV line-earth (CM) on ControlNet port
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
15
Page 16
1756 ControlLogix Communication Modules Specifications
Table 14 - Certifications - 1756 ControlNet-XT Module Certification(1)
1756-CN2RXT/B c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2004/108/IEC EMC Directive, compliant with the following: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with the following: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4X
TÜV
TÜV Certified for Functional Safety: Capable of SIL 2
CI
ControlNet International conformance tested to ControlNet specifications
(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Accessories - ControlNet Network Cat. No.
Description
Taps 1786-TCT2BD1
T-tap straight IP67 rated
1786-TPR
T-tap right angle
1786-TPS
T-tap straight
1786-TPYR
Y-tap right angle
1786-TPYS
Y-tap straight
Cables 1786-CP
Programming cable to ControlNet RJ45 port
1786-RG6
ControlNet network, shield high-flex cable
1756-RG6F
ControlNet network, quad-shield high-flex coax cable
Other 1786-TNCLXT4
ControlNet IP67 termination resistor
1786-XT
ControlNet termination resistor
Repeaters 1786-RPA
ControlNet modular repeater adapter
1786-RPCD
ControlNet coaxial hub repeater
1786-RPFRL
ControlNet fiber ring repeater, long distance
1786-RPFRXL
ControlNet fiber ring repeater, extra long distance
1786-RPFS
ControlNet fiber repeater, short distance
1786-RPFM
ControlNet fiber repeater, medium distance
For more information, see ControlNet Media System Components List, publication AG-PA002.
16
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
Page 17
1756 ControlLogix Communication Modules Specifications
DeviceNet Network The DeviceNet network is an open, low-level network that provides connections between simple industrial devices, such as sensors and actuators, and higher-level devices, such as controllers and computers. The DeviceNet network uses the proven Common Industrial Protocol (CIP) to provide the control, configure, and data collection capabilities for industrial devices. ATTENTION: If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. Table 15 - Technical Specifications - 1756-DNB/E DeviceNet Module Attribute
1756-DNB/E
DeviceNet communication rate
125 Kbps (500 m max) 250 Kbps (250 m max) 500 Kbps (100 m max)
Number of nodes, max
64
Current draw @ 5.1V DC
400 mA
Current draw @ 24V DC
0 mA
DeviceNet current draw @ 24V DC
60 mA
DeviceNet voltage range
11...25V DC CL 2/SELV
Power dissipation
3.5 W
Thermal dissipation
11.9 BTU/hr
Isolation voltage
50V (continuous), basic insulation type, DeviceNet network to backplane Type tested at 853V AC for 60 s No isolation between USB and backplane
Slot width
1
Module location
Chassis-based, any slot
Chassis
1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17
Power supply, standard
1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant
1756-PA75R, 1756-PB75R, 1756-PSCA2
DeviceNet power
To comply with the CE low voltage directive (LVD), the DeviceNet network must be powered from a source compliant with the safety extra low voltage (SELV) or protected extra low voltage (PELV). To comply with UL restrictions, the DeviceNet network must be powered from a source compliant with Class 2 or limited voltage/current.
DeviceNet port
1 DeviceNet open-style 5-or 10-pin linear plug
DeviceNet connector torque
0.56…0.79 N•m (5…7 lb•in)
USB port(1)
USB 2.0, full speed (12 Mbps)
Wire category(2)
1 - On DeviceNet ports 3 - On USB ports
North American temperature code
T4A
IEC temperature code
T4
Enclosure type rating
None (open-style)
(1) The USB port is intended for temporary local programming purposes only and not intended for permanent connection. Do not use the USB port in hazardous locations. (2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. Refer to the DeviceNet Media Design and Planning Guide, publication DNET-UM072, for information specific to your DeviceNet network.
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012
17
Page 18
1756 ControlLogix Communication Modules Specifications
Table 16 - Environmental Specifications - 1756-DNB/E DeviceNet Module Attribute
1756-DNB/E
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions CISPR 11
Group 1, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±3 kV at 5 kHz on DeviceNet ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on DeviceNet ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
18
Rockwell Automation Publication 1756-TD003D-EN-E - January 2012