For the Allen-Bradley 1756-DNB
Page 5
Preface
About This User Manual
Introduction
This user manual is designed to provide you enough information to get a small example application up and running. Use this manual if you are knowledgeable about DeviceNet and ControlLogix products, but may not have used the products in conjunction. The information provided is a base; modify or expand the examples to suit your particular needs. The manual contains instructions on configuring a DeviceNet network using RSLinx and RSNetWorx for DeviceNet software over various networks: • directly over the DeviceNet network • from a ControlNet network • from an Ethernet network • from a Data Highway Plus network The example application demonstrates how to perform control on a DeviceNet network using a Logix5550 controller and the 1756-DNB module. You use RSLogix 5000 programming software to create a ladder logic program to control a photoeye and a RediSTATION.
IMPORTANT
1
This User Manual should be used in conjunction with the 1756-DNB DeviceNet Scanner Module Installation Instructions, publication 1756-5.66. The Installation Instructions contain important information on configuring your scanner.
Publication 1756-6.5.19 - May 2000
Page 6
P-2
About This User Manual
Contents
This user manual contains the following chapters:
1
4
Before You Begin go to Chapter 1
2
Planning Your Configuration go to Chapter 2
3
5
Configuring DeviceNet From Another Network go to Chapter 5
Setting Up the Hardware go to Chapter 3
6 7
Audience
Configuring the DeviceNet Network go to Chapter 4
Creating and Running the Application Program go to Chapter 6
Troubleshooting go to Chapter 7
This manual is intended for control engineers and technicians who are installing, programming, and maintaining a control system that includes a Logix5550 controller communicating on a DeviceNet network through a 1756-DNB module. We assume that you: • are developing a DeviceNet network using a ControlLogix chassis in conjunction with a 1756–DNB interface module • know each of your device’s I/O parameters and requirements • are experienced with the Microsoft® Windows environment • are familiar with RSNetWorx for DeviceNet software
Publication 1756-6.5.19 - May 2000
Page 7
About This User Manual
The Example Application
P-3
This manual describes how to set up an example application. The manual provides examples of each step of the setup, with references to other manuals for more details.
System Components We used the following devices and software for the example application. For your own application, substitute your own devices to fit your needs. The recommended configurations in this user manual will help you set up the test system and get it working. Your eventual configuration will depend on your application. Note: If you use different software or fimware versions of these products some of your screens may appear slightly different from those shown in the example. Product Name
Catalog Number
Series
Revision
1756-A4, -A7, -A10
-
-
Qty Hardware 1
ControlLogix chassis
1
Logix5550 controller
1756-L1
A
5.12
1
ControlLogix DeviceNet Interface module
1756-DNB
A
3.003
1
DeviceNet Quad-Tap
1492-DN3TW
-
-
1
RediSTATION operator interface module
2705-T3DN1A42A
-
-
1
Series 9000 Photoeye
42GNP-9000 or equivalent
-
-
1
DeviceNet PC serial communication module
1770-KFD
A
1.04
1
RS-232 cable
1787-RSCABL/A (PC to 1770-KFD)
-
-
1
24V Power Supply
Regulated 24VDC, 8A
-
-
1
PC
IBM-compatible Windows NT 4.0
-
-
DeviceNet dropline or trunkline cables, as needed
1787-PCABL, -TCABL, -MCABL
-
-
1(1) ControlLogix ControlNet Interface module
1756-CNB
B
2.24
1(2) ControlLogix Data Highway Plus Interface module
1756-DHRIO
B
2.17
1(3) ControlLogix Ethernet Interface module
1756-ENET
A
1.18
Software RSLogix 5000
9324-RL5300END
-
2.51
RSNetWorx for DeviceNet
9357-DNETL3,
-
2.11
RSLinx
9355-WAB
-
2.10
(1)
Required if interfacing the DeviceNet network and a ControlNet network. See chapters 5 and 6.
(2)
Required if interfacing the DeviceNet network and a Data Highway Plus network. See chapters 5 and 6.
(3)
Required if interfacing the DeviceNet network and an Ethernet network. See chapters 5 and 6.
Publication 1756-6.5.19 - May 2000
Page 8
P-4
About This User Manual
Common Techniques Used in This Manual
The following conventions are used throughout this manual: • Bulleted lists provide information, not procedural steps. • Numbered lists provide sequential steps. • Information in bold contained within text identifies menu windows, or screen options, screen names and areas of the screen, such as dialog boxes, status bars, radio buttons and parameters. This symbol identifies helpful tips.
TIP
This is a definition box. When a word is bold within the text of a paragraph, a definition box will appear in the left margin to further define the text.
A definition box defines terms that may be unfamiliar to you.
Screen captures are pictures of the software’s actual screens. The names of screen buttons and fields are often in bold in the text of a procedure. Pictures of keys represent the actual keys you press.
More
Publication 1756-6.5.19 - May 2000
The “MORE” icon is placed beside any paragraph that references sources of additional information outside of this document.
Page 9
About This User Manual
Where to Find More Information
More
For information about
P-5
Refer to the following publications as needed for additional help when setting up and using your DeviceNet network: See this publication
Publication Number the ControlLogix DeviceNet interface module ControlLogix DeviceNet Scanner Module Installation Instructions
1756-5.66 the ControlLogix Chassis
ControlLogix Chassis Installation Instructions
1756-5.2
ControlLogix power supplies
ControlLogix Power Supplies Installation Instructions
1756-5.1 connecting the DeviceNet network
DeviceNet Cable Planning and Installation Manual
DN-6.7.2 the 1770-KFD communication module
DeviceNet RS-232 Interface Module Installation Instructions
1770-5.6 the Logix5550 controller
Logix5550 Controller User Manual
1756-6.5.12 the RediSTATION
RediSTATION Operator Interface User Manual
2705-804 the ControlLogix ControlNet Interface module ControlLogix ControlNet Bridge Installation Instructions
1756-5.32 the ControlLogix DH+ Interface module
ControlLogix DHRIO Module Installation Instructions
1756-5.4 the ControlLogix Ethernet Interface module
ControlLogix Ethernet Module Installation Instructions
1756-5.3
RSLogix 5000 software
Getting Results with RSLogix 5000
9399-RLD300GR
RSLinx software
RSLinx Lite User Guide
9399-WAB32LUG
RSNetWorx for DeviceNet software
See the software’s online Help
N/A terms and definitions
Allen-Bradley Industrial Automation Glossary
AG-7.1
TIP
Many of the above publications are available online from the Automation Bookstore: http://www.theautomationbookstore.com.
TIP
For more information about Rockwell Software products, visit the Rockwell Software internet site: http://www.software.rockwell.com.
Publication 1756-6.5.19 - May 2000
Page 10
P-6
About This User Manual
Terminology
Publication 1756-6.5.19 - May 2000
This term Means Bridge The interface module’s support of explicit message transfer. Change of State A type of I/O data communication. The interface module can send and receive data with slave devices that have the change of state feature. Data is sent whenever a data change occurs. Data is updated at the rate of the heartbeat. Communication The 1756-DNB interface module or the 1770-KFD module. Module Cyclic A type of I/O data communication. The interface module can send and receive data with slave devices that have the cyclic feature. Data is only sent at a user-configurable rate. EDS Electronic Data Sheet. A vendor-supplied template that specifies how information is displayed as well as what is an appropriate entry (value). Explicit A type of messaging used for lower priority tasks, such as configuration Messaging and data monitoring. Heartbeat Rate Devices that are configured for change of state data can also send a “heartbeat” signal to indicate proper operation. Host Platform The computer that hosts the 1756-DNB interface module. I/O An abbreviation for “input and output”. Implicit The type of messaging used for high priority I/O control data; e.g., change Messaging of state, cyclic, polled, or strobed. Input Data Data produced by a DeviceNet device and collected by the interface module for a host platform to read. MAC ID The network address of a DeviceNet node. Network The DeviceNet network or the RSNetWorx for DeviceNet software representation of the network. Node Hardware that is assigned a single address on the network (also referred to as device). Offline When the PC communication interface is not communicating on the network. Online When the PC communication interface is configured and enabled to communicate on the network. Output Data Data produced by a host platform that is written to the interface module’s memory. This data is sent by the interface module to DeviceNet devices. PC Abbreviation for an IBM® compatible personal-computer. Polled A type of input/output-data communication. A polled message solicits a response from a single, specified device on the network (a point-to-point transfer of data). Record The node address and channel-specific memory assigned in the interface module’s non-volatile storage for a node in the scanlist. Rx An abbreviation for “receive”. Scanlist The list of devices (nodes) with which the scanner is configured to exchange I/O data. Scanner The function of the 1756-DNB interface module to support the exchange of I/O with slave modules. Slave Mode The interface module is in slave mode when it is placed in another interface module’s scanlist as a slave device. Strobed A type of I/O data communication. A strobed message solicits a response from each strobed device (a multicast transfer). It is a 64-bit message that contains one bit for each device on the network. Tx An abbreviation for “transmit”.
Page 11
About This User Manual
Rockwell Automation Support
P-7
Rockwell Automation offers support services worldwide, with over 75 sales/support offices, 512 authorized distributors, and 260 authorized systems integrators located throughout the United States alone, plus Rockwell Automation representatives in every major country in the world.
Local Product Support Contact your local Rockwell Automation representative for: • sales and order support • product technical training • warranty support • support service agreements
Technical Product Assistance If you need to contact Rockwell Automation for technical assistance, call your local Rockwell Automation representative, or call Rockwell directly at: 1 440 646-6800. For presales support, call 1 440 646-3NET. You can obtain technical assistance online from the following Rockwell Automation WEB sites: • www.ab.com/mem/technotes/kbhome.html (knowledge base) • www.ab.com/networks/eds (electronic data sheets)
Your Questions or Comments about This Manual If you find a problem with this manual, please notify us of it on the enclosed Publication Problem Report (at the back of this manual). If you have any suggestions about how we can make this manual more useful to you, please contact us at the following address: Rockwell Automation, Allen-Bradley Company, Inc. Control and Information Group Technical Communication 1 Allen-Bradley Drive Mayfield Heights, OH 44124-6118 Publication 1756-6.5.19 - May 2000
Page 12
P-8
About This User Manual
Publication 1756-6.5.19 - May 2000