Page 87

Produced and Consumed Tags

7-11

Add the Remote ENET/B Module to the I/O Configuration Next, you must add the remote 1756-ENET/B as a “child” of the local 1756-ENET/B.

1. In the Project window, right click on the local 1756-ENET/B module under the I/O Configuration folder and select New Module from the pop-up window. The Select Module Type window will open

2. Select the 1756-ENET/B module and click on OK.

Publication 1756-UM051B-EN-P - November 2000

Page 88

7-12

Produced and Consumed Tags

The Module Properties window will open.

3. Enter the following parameters: Name

Remote_ENET

IP Address

130.130.130.2

Chassis Size

4

Slot

1

Comm Format

Rack Optimization

Electronic Keying(1)

Compatible Module

(1)

See Appendix F for important information about Electronic Keying.

4. Click on Finish to accept the configuration. The remote 1756-ENET/B module will appear indented under the local 1756-ENET/B in the I/O Configuration folder.

Publication 1756-UM051B-EN-P - November 2000

Page 89

Produced and Consumed Tags

7-13

Add the Remote (Producer) Controller to the I/O Configuration You must now add the remote Controller (the Producer) to the I/O Configuration under the remote 1756-ENET/B module.

1. Right click on the remote 1756-ENET/B module under the I/O Configuration folder and select New Module. The Select Module Type window will open.

2. Select the 1756-L1 ControlLogix5550 processor and click on OK.

Publication 1756-UM051B-EN-P - November 2000

Page 90

7-14

Produced and Consumed Tags

The Module Properties window will open.

3. Enter the following parameters: Name

Producer

Slot

0

4. Click on the Finish button to accept the configuration. The I/O Configuration tree should look similar to the one shown below.

Publication 1756-UM051B-EN-P - November 2000

Page 91

Produced and Consumed Tags

7-15

Create the Consumer Tags The consumer tags are created via the Project window.

1. Double-click on the Controller Tags icon in the project window. The Controller Tags window will open.

Enter the new tag here

Publication 1756-UM051B-EN-P - November 2000

Page 92

7-16

Produced and Consumed Tags

2. Select the Edit Tags tab and create the following tag: Tag Name

Type

Style consumed_data

DINT

Decimal

3. Right-click on the new tag. The following pop-up menu will open:

4. Select Edit Tag Properties.

Publication 1756-UM051B-EN-P - November 2000

Page 93

Produced and Consumed Tags

7-17

The Tag Properties window will open.

5. Enter or select the following parameters: Name consumed_data

Tag Type

Consumed

Controller

Producer

Remote Tag produced_data(1)

Data Type

DINT(1)

Style

Decimal(1)

RPI

10ms(1)

(1)

These parameters must match those in the Producer.

6. Click on OK to save the tag properties.

Publication 1756-UM051B-EN-P - November 2000

Page 94

7-18

Produced and Consumed Tags

Download the Configuration to the Consumer You must now load the configuration parameters to the Consumer controller. Note that no ladder logic is required for routing in the Consumer. The logic can consist of a single “End” rung.

1. Click on the Communications menu and select Who Active. The Who Active window will open (Your window will display the drivers and devices you have installed).

2. Select your Ethernet driver (e.g., AB_ETH-1) and expand the tree through the backplane of the local ControlLogix chassis. 3. Highlight the Logix 5550 controller and click on the Download button. You will see a message similar to the following:

4. Click on the Download button.

Publication 1756-UM051B-EN-P - November 2000

Page 95

Produced and Consumed Tags

Test the Messaging

7-19

1. Open the session of RSLogix 5000 for the Producer and verify that the timer is running. 2. In the RSLogix 5000 session for the Consumer controller: a. Double-click on the Controller Tags folder and select the Monitor Tags tab.

You should see this value changing.

b. Examine the consumed_data field. You should see the value changing in step with the accumulated value of the timer in the Producer. This completes the example of Logix5550 controller to Logix5550 messaging using produced/consumed tags.

What’s Next?

This concludes the example applications. The appendices that follow provide information to help you troubleshoot the module, describe how to configure the Ethernet driver in RSLinx, and show the use of the Ethernet module in a ControlLogix Gateway system and in larger control systems.

Publication 1756-UM051B-EN-P - November 2000

Page 96

7-20

Produced and Consumed Tags

Publication 1756-UM051B-EN-P - November 2000