Page 97

Appendix

A

LED Status Indicators

Interpreting the Status Indicators

The faceplate of the 1756-ENET/B module is provided with LED indicators that display the module status and transmit/receive status. The following table describes module health indicator displays, module status, and recommended action:

TXD Indicator

If the OK indicator is:

then module status is:

take this action:

Off

Not operating.

Apply chassis power. Verify module is completely inserted into chassis and backplane.

Red, then flashing red or flashing green

Performing powerup diagnostics.

None, normal operation.

Green

Operating.

None.

Red flashing

Not configured.

Configure the module.

Red

Unrecoverable fault.

Repair or replace module.

ETHERNET

RXD Indicator

OK Indicator

RXD TXD OK

AUI

The following table describes the displays of the transmit (TX) and receive (RX) indicators:

10 BASET

1756-ENET

If this indicator: is:

the module is:

TXD

Green

Transmitting data

Off

Not active

Green

Receiving data

Off

Not active

31153-M

Front View

RXD

Detailed network diagnostics are provided by the module’s Web pages, which can be accessed through Netscape or Microsoft Internet Explorer. See Appendix B.

1

Publication 1756-UM051B-EN-P - November 2000

Page 98

A-2

LED Status Indicators

Publication 1756-UM051B-EN-P - November 2000

Page 99

Appendix

B

1756-ENET/B Module Web Pages

Web Page Diagnostics

The Ethernet module’s Web pages offer extensive internal and network diagnostics. To view the Web pages, enter the module’s IP address into Netscape or Microsoft Internet Explorer. You will see the following Web page:

The module’s Web pages provide the following information: • Module Information • TCP/IP Configuration • Diagnostic Information • Chassis Who These pages are shown in the following figures.

1

Publication 1756-UM051B-EN-P - November 2000

Page 100

B-2

1756-ENET/B Module Web Pages

Module Information

The Module Information page provides specific information about your ENET/B module, such as its serial number and firmware version.

TCP/IP Configuration

The TCP/IP Configuration page provides the Ethernet configuration of your module, including IP Address, Gateway Address, Subnet Mask, etc. Publication 1756-UM051B-EN-P - November 2000

Page 101

1756-ENET/B Module Web Pages

B-3

Diagnostic Information

The 1756-ENET/B module provides advanced diagnostic information via this page. This information may be useful to systems administrators and other experienced information technology personnel. As an example, selecting ENET/IP Statistics under the Miscellaneous heading opens the following window.

ENET/IP Statistics

Publication 1756-UM051B-EN-P - November 2000

Page 102

B-4

1756-ENET/B Module Web Pages

This page provides access to detailed ENET/IP diagnostics. For example, selecting CIP (ENET/IP) Statistics opens the following window.

ENET/IP (CIP) STATISTICS

The CIP (ENET/IP) Statistics page provides the connection and traffic information shown above.

Publication 1756-UM051B-EN-P - November 2000

Page 103

1756-ENET/B Module Web Pages

B-5

Chassis Who

The Chassis Who window shows the current configuration of the chassis in which the 1756-ENET/B module resides. It identifies all of the modules in the chassis and their slot locations.

Publication 1756-UM051B-EN-P - November 2000

Page 104

B-6

1756-ENET/B Module Web Pages

Publication 1756-UM051B-EN-P - November 2000