The text of a manual · part 14 of 18
ControlLogix Ethernet Communication Interface Module 1756-ENET/B User Manual, pages 97 to 104
Pages 97 to 104 of 122: A - LED Status Indicators; B - 1756-ENET/B Module Web Pages
The original document is the PDF (1.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-ENET
Page 97
Appendix
A
LED Status Indicators
Interpreting the Status Indicators
The faceplate of the 1756-ENET/B module is provided with LED indicators that display the module status and transmit/receive status. The following table describes module health indicator displays, module status, and recommended action:
TXD Indicator
If the OK indicator is:
then module status is:
take this action:
Off
Not operating.
Apply chassis power. Verify module is completely inserted into chassis and backplane.
Red, then flashing red or flashing green
Performing powerup diagnostics.
None, normal operation.
Green
Operating.
None.
Red flashing
Not configured.
Configure the module.
Red
Unrecoverable fault.
Repair or replace module.
ETHERNET
RXD Indicator
OK Indicator
RXD TXD OK
AUI
The following table describes the displays of the transmit (TX) and receive (RX) indicators:
10 BASET
1756-ENET
If this indicator: is:
the module is:
TXD
Green
Transmitting data
Off
Not active
Green
Receiving data
Off
Not active
31153-M
Front View
RXD
Detailed network diagnostics are provided by the module’s Web pages, which can be accessed through Netscape or Microsoft Internet Explorer. See Appendix B.
1
Publication 1756-UM051B-EN-P - November 2000
Page 98
A-2
LED Status Indicators
Publication 1756-UM051B-EN-P - November 2000
Page 99
Appendix
B
1756-ENET/B Module Web Pages
Web Page Diagnostics
The Ethernet module’s Web pages offer extensive internal and network diagnostics. To view the Web pages, enter the module’s IP address into Netscape or Microsoft Internet Explorer. You will see the following Web page:
The module’s Web pages provide the following information: • Module Information • TCP/IP Configuration • Diagnostic Information • Chassis Who These pages are shown in the following figures.
1
Publication 1756-UM051B-EN-P - November 2000
Page 100
B-2
1756-ENET/B Module Web Pages
Module Information
The Module Information page provides specific information about your ENET/B module, such as its serial number and firmware version.
TCP/IP Configuration
The TCP/IP Configuration page provides the Ethernet configuration of your module, including IP Address, Gateway Address, Subnet Mask, etc. Publication 1756-UM051B-EN-P - November 2000
Page 101
1756-ENET/B Module Web Pages
B-3
Diagnostic Information
The 1756-ENET/B module provides advanced diagnostic information via this page. This information may be useful to systems administrators and other experienced information technology personnel. As an example, selecting ENET/IP Statistics under the Miscellaneous heading opens the following window.
ENET/IP Statistics
Publication 1756-UM051B-EN-P - November 2000
Page 102
B-4
1756-ENET/B Module Web Pages
This page provides access to detailed ENET/IP diagnostics. For example, selecting CIP (ENET/IP) Statistics opens the following window.
ENET/IP (CIP) STATISTICS
The CIP (ENET/IP) Statistics page provides the connection and traffic information shown above.
Publication 1756-UM051B-EN-P - November 2000
Page 103
1756-ENET/B Module Web Pages
B-5
Chassis Who
The Chassis Who window shows the current configuration of the chassis in which the 1756-ENET/B module resides. It identifies all of the modules in the chassis and their slot locations.
Publication 1756-UM051B-EN-P - November 2000
Page 104
B-6
1756-ENET/B Module Web Pages
Publication 1756-UM051B-EN-P - November 2000