ControlLogix Ethernet Communication Interface Module 1756-ENET/B User Manual: 1 - About the 1756-ENET/B Module
Pages 19 to 24 of 122, from ControlLogix Ethernet Communication Interface Module 1756-ENET/B User Manual
The original document is the PDF (1.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-ENET
Page 19
Chapter
1
About the 1756-ENET/B Module
What This Chapter Contains This chapter provides an overview of the ControlLogix 1756-ENET/B module, its primary features, what it does, and how to use it. You will need to understand the concepts discussed in this chapter in order to configure your Ethernet module and use it in a control system. The following table lists where to find specific information in this chapter. .
For information about
Module Features
See page
Module Features
1-1
What the Module Does
1-2
Hardware/Software Compatibility
1-2
Support of Rack Optimized and Direct Connections
1-2
Mixing Rack Optimized and Direct Connections
1-3
Use of the Control and Information Protocol (CIP)
1-4
Understanding the Producer/Consumer Model
1-4
Specifying the Requested Packet Interval (RPI)
1-5
The 1756-ENET/B module’s features include: • use Ethernet/IP messages encapsulated within standard TCP/UDP/IP protocol • common application layer with ControlNet and DeviceNet • interfacing via AUI and 10 Base-T media • removal or insertion under power • number of modules per chassis limited only by chassis size • communication to and from other ControlLogix modules in the same chassis • communication supported by RSLinx software • configurable via RSLinx or standard BootP tools • no network scheduling required • no routing tables required
1
Publication 1756-UM051B-EN-P - November 2000
Page 20
1-2
About the 1756-ENET/B Module
Hardware/Software Compatibility
What the Module Does
The 1756-ENET/B module is compatible with the following firmware versions and software releases. Contact Rockwell Automation if you need software or firmware upgrades to use this equipment.: Product
Firmware Version/ Software Release
1756-ENET/B module
2.01 or higher
Logix 5550 Controller
6.10 or higher
RSLogix 5000 software
7.0 or higher
RSLinx software
2.2 or higher
The 1756-ENET/B module performs two primary tasks: 1. Control of real time I/O data (also known as “implicit messaging”) in conjunction with a Logix 5550 controller. The Ethernet module may serve as an adaptor, interfacing the I/O modules to the network, or as a scanner, sending and receiving data between the controller and the network. Scanner L 5 5 5 0
E N E T
EtherNet Network
I/O
E N E T
I/O
Adaptor
I/O
E N E T
I/O
Adaptor
I/O
E N E T
I/O
Adaptor
2. Support of messaging data for configuration and programming information, operator interfaces, etc. (also known as “explicit messaging.”).
Support of Rack Optimized and Direct Connections
Publication 1756-UM051B-EN-P - November 2000
The 1756-ENET/B module supports both Rack Optimized and Direct Connections. A direct connection is a real-time data transfer link between the controller and the device that occupies the slot that the configuration data references. A rack optimized connection is a grouping of data from more than one I/O module into a single block of data sent over a single connection.
Page 21
About the 1756-ENET/B Module
1-3
Rack optimized connections reduce the total number of connections needed to transfer data when using many I/O modules in a system. The following example illustrates the benefit of rack optimized connections. Assume you have set up a system that contains 10 discrete I/O modules in a remote ControlLogix chassis. If you use direct connections to transfer data to each of the these I/O modules, you need 10 connections to transfer all of the data, one to each of the ten I/O modules. If you use a rack-optimized connection to transfer the data, you only need a single connection – the connection to the Ethernet module.
IMPORTANT
Although rack optimized connections offer an efficient way to use resources, there are a few limitations on their use: • You can only use rack optimized connections to send data to and from discrete digital I/O modules. Analog I/O requires direct connections. • Rack optimized connections can contain I/O data and status information only. Additional module information, such as diagnostics, is not available through a rack-optimized connection. • All data is sent at the same time at the RPI rate of the Ethernet module, regardless of a COS on a particular module.
See the Ethernet Performance and Application Guide, publication number ENET-AP001A-EN-P, for more information on connections.
Mixing Rack Optimized and Direct Connections You can mix communication formats for different I/O modules in the same chassis. I/O modules set up to use Rack Optimization will communicate at the rate of the RPI (requested packet interval) configured for the 1756-ENET/B module. I/O modules configured for direct communication will communicate at their set RPI and ignore the Ethernet module’s RPI.
Publication 1756-UM051B-EN-P - November 2000
Page 22
1-4
About the 1756-ENET/B Module
Use of the Control and Information Protocol (CIP)
The Ethernet module uses the Control and Information Protocol (CIP). CIP is the application layer protocol specified for Ethernet/IP, the Ethernet Industrial Protocol, as well as for ControlNet and DeviceNet. It is a message-based protocol that implements a relative path to send a message from the “producing” device in a system to the “consuming” devices. The producing device contains the path information that steers the message along the proper route to reach its consumers. Since the producing device holds this information, other devices along the path simply pass this information; they do not need to store it. This has two significant benefits: • You do not need to configure routing tables in the bridging module, which greatly simplifies maintenance and module replacement. • You maintain full control over the route taken by each message, which enables you to select alternative paths for the same end device.
Understanding the Producer/Consumer Model
CIP uses the “producer/consumer” networking model, replacing the old source/destination (master/slave) model. The producer/consumer model reduces network traffic and increases speed of transmission. In traditional I/O systems, controllers poll input modules to obtain their input status. In the CIP system digital input modules are not polled by a controller. Instead, they produce (“multicast”) their data either upon a change of state (COS) or periodically. The frequency of update depends upon the options chosen during configuration and where on the network the input module resides. The input module, therefore, is a producer of input data and the controller is a consumer of the data. The controller can also produce data for other controllers to consume. The produced and consumed data is accessible by multiple controllers over the ControlLogix backplane and over the Ethernet network. This data exchange conforms to the producer/consumer model. You configure the producer and consumer by creating controller scoped tags using RSLogix 5000 software (see chapter 7).
Tag Type Produced(1) Consumed(1)
(1)
Description Specify Using RSLogix5000 Software Tags that the controller produced for other Enabled for producing nodes to consume. Number of consumers allowed Tags whose values are produced by another Name of controller that owns the tag the local controller wants controller. to consume Tag name or instance that the local controller wants to consume Data type of the tag to consume Update interval of how often the local controller consumes the tag data
Produced and consumed tags must be controller-scoped tags of DINT or REAL data type, or in an array or structure.
Publication 1756-UM051B-EN-P - November 2000
Page 23
About the 1756-ENET/B Module
Specifying the Requested Packet Interval (RPI)
1-5
The RPI is the update rate specified for a particular piece of data on the network. The RPI can be specified for an entire rack (using a rack optimized connection) or for a particular module (using direct connection). When you add a module to the I/O configuration of a controller, you must enter the RPI as a parameter. ‘This value specifies how often to produce the data for that module. For example, if you specify an RPI of 50ms, it means that every 50ms the I/O module should send its data to the controller or that the controller should send its data to the I/O module. RPIs are only used for modules that produce data. For example a local 1756-ENET/B module (i.e., an ENET/B module in the same chassis as the controller) does not require an RPI because it is not a data-producing member of the system; it is used only as a bridge to remote racks.
What’s Next?
The following chapter describes how to install the Ethernet module and connect it to the network.
Publication 1756-UM051B-EN-P - November 2000
Page 24
1-6
About the 1756-ENET/B Module
Publication 1756-UM051B-EN-P - November 2000