The text of a manual · part 6 of 18
ControlLogix Ethernet Communication Interface Module 1756-ENET/B User Manual: 2 - Installing the Ethernet Module
Pages 25 to 32 of 122, from ControlLogix Ethernet Communication Interface Module 1756-ENET/B User Manual
The original document is the PDF (1.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-ENET
Page 25
Chapter
2
Installing the Ethernet Module
What This Chapter Contains This chapter describes how to install the module in the ControlLogix chassis and connect it to the network. The following table describes what this chapter contains and where to find specific information. For information about
Identifying Module Features
See page
Insertion and Removal Under Power
2-2
Installing the Ethernet Module
2-2
Preparing the Chassis for Module Installation
2-2
Determining Module Slot Location
2-3
Inserting the Module in the Chassis
2-4
Removing or Replacing the Module (when applicable)
2-5
Wiring the Ethernet Connector
2-6
Connecting the Module to the Ethernet Network
2-6
Applying Chassis Power
2-7
Checking Power Supply and Module Status
2-8
Use the following illustration to identify the external features of the 1756-ENET/B module. Backplane Connector
Product Label <www> ETHERNET
Front Panel RXD
TXD
OK
AUI Ethernet Connector
MAC ID Label AUI
10 BASET
10BT Ethernet Connector 1756-ENET
Side View
1
Front View
Publication 1756-UM051B-EN-P - November 2000
Page 26
2-2
Installing the Ethernet Module
Insertion and Removal Under Power
The Ethernet module is designed to be installed or removed while chassis power is applied. However, please observe the following precautions.
WARNING
! Installing the Ethernet Module
When you insert or remove the module while backplane power is on, or you connect or disconnect the communications connectors, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Use the following procedure to install the Ethernet module.
Preparing the Chassis for Module Installation Before you install the Ethernet module, you must install and connect a ControlLogix chassis and power supply.
1756-A4 Chassis
Power Supply
20805-M
For information on installing these products, refer to the publications listed in the following table. Chassis Type
Publication 1756-UM051B-EN-P - November 2000
Chassis Installation
Series A: 1756-A4, -A7, -A10, -A13
1756-5.69
Series B: 1756-A4, -A7, -A10, -A13
1756-5.80
(1)
Compatible with Series A chassis
(2)
Compatible with Series B chassis
Power Supply 1756-PA72/B(1) 1756-PB72/B(1) 1756-PA75/A(2) 1756-PB75/A(2)
Power Supply Installation 1756-5.67
1756-5.78
Page 27
Installing the Ethernet Module
2-3
Determining Module Slot Location You can install the module in any slot in the ControlLogix chassis. You can also install multiple ENET/B modules in the same chassis. The figure below shows chassis slot numbering in a 4-slot chassis. In a ControlLogix chassis slot 0 is the first slot and is always the leftmost slot in the rack (the first slot to the right of the power supply). Slot 0
Slot 2 Slot 1
Slot 3
Power Supply
Chassis
Publication 1756-UM051B-EN-P - November 2000
Page 28
2-4
Installing the Ethernet Module
Inserting the Module in the Chassis 1 Align the circuit board with top and bottom guides in the chassis.
Circuit Board
2 Slide the module into the chassis. Make sure the module backplane connector properly connects to the chassis backplane.
3 The module is properly installed when it is flush with the power supply or other installed modules.
Publication 1756-UM051B-EN-P - November 2000
Page 29
Installing the Ethernet Module
2-5
Removing or Replacing the Module (when applicable) 1 Push on upper and lower module tabs to disengage them.
2 Slide module out of chassis.
IMPORTANT If you are replacing an existing module with an identical one, and you want to resume identical system operation, you must install the new module in the same slot.
Publication 1756-UM051B-EN-P - November 2000
Page 30
2-6
Installing the Ethernet Module
Wiring the Ethernet Connector Note: If your application requires the module door to be closed, use one of the custom AUI connector cables, available in two lengths: • 2 meters (cat. no. 1756- TC02) • 15 meters (cat. no. 1756- TC15)
Use either an AUI or an RJ45 connector to connect to the Ethernet network. Wire the appropriate connector as shown below: Protective Ground 1-Ctrl IN Ckt Shield 2-Ctrl IN Ckt A 3-Data OUT Ckt A 4-Data IN Ckt Shield 5-Data In Ckt A 6-Voltage Comm 7-Ctrl OUT Ckt A 8-Ctrl OUT Ckt Shield
9-Ctrl IN Ckt B 10-Data OUT Ckt B 11-Data OUT Ckt B 12-Data OUT Ckt B 13-Voltage Plus 14-Voltage Shield 15-Ctrl OUT Ckt B
1 ------ TD+ 2 ------ TD3 ------ RD+ 4 ------ NC 5 ------ NC 6 ------ RD7 ------ NC 8 ------ NC 8 1
AUI
RJ 45
Connecting the Module to the Ethernet Network
ATTENTION
!
Publication 1756-UM051B-EN-P - November 2000
If you connect or disconnect the Ethernet cable with power applied to the module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceding.
Page 31
Installing the Ethernet Module
2-7
Attach either the AUI or RJ45 connector to the matching Ethernet port.
POWER
OR
IMPORTANT
POWER
Connecting the module to the network via an Ethernet switch instead of a hub reduces the number of collisions and lost packets and increases the bandwidth. See the Ethernet/IP Performance and Application Guide, publication ENET-AP001A-EN-P, for more information.
Applying Chassis Power
ON ON POWER OFF
POWER OFF
20921-M
Publication 1756-UM051B-EN-P - November 2000
Page 32
2-8
Installing the Ethernet Module
Checking Power Supply and Module Status Check the LED indicators to determine if the power supply and the Ethernet module are operating properly.
<www> ETHERNET
POWER
RXD
RXD Power Supply indicator is GREEN.
TXD
TXD
OK
OK indicator is RED, then FLASHING RED (or is GREEN if module is configured).
If the Power Supply and module OK indicators are not in the states described above refer to Appendix A for help in troubleshooting your module.
What’s Next?
Publication 1756-UM051B-EN-P - November 2000
The following chapter describes some Ethernet basics you should know before configuring your module.