Page 1
Technical Data
1756 ControlLogix I/O Specifications Topic
Page
Summary of Changes
2
Available 1756 I/O Modules
3
ControlLogix I/O Accessories
239
Additional Resources
241
The ControlLogix® architecture provides a wide range of input and output modules to span many applications, from high-speed digital to process control. The ControlLogix architecture uses Producer/Consumer technology, which allows input information and output status to be shared among multiple ControlLogix controllers. Each ControlLogix I/O module mounts in a ControlLogix chassis and requires either a removable terminal block (RTB) or a 1492 interface module (IFM) to connect all field-side wiring. RTBs and IFMs are not included with the I/O modules. They must be ordered separately.
Page 2
1756 ControlLogix I/O Specifications
Summary of Changes This publication contains new and updated information as indicated in the following table.
2
Topic
Page
Updated 1756-IF4FXOF2F specifications
37
Updated 1756-IF8 specifications
49
Updated 1756-IF8H specifications
54
Updated 1756-IF8IH specifications
61
Updated 1756-IF16 specifications
65
Updated 1756-IF16H specifications
70
Updated 1756-IF16IH specifications
73
Updated 1756-OF4 specifications
175
Updated 1756-OF8 specifications
185
Updated 1756-OF8H specifications
189
Updated 1756-OF8IH specifications
197
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 3
1756 ControlLogix I/O Specifications
Available 1756 I/O Modules You can select these types of digital I/O modules. Digital I/O Type
Description
Diagnostic
These modules provide diagnostic features to the point level. These modules have a D at the end of the catalog number.
Electronic fusing
These modules have internal electronic fusing to help prevent too much current from flowing through the module. These modules have an E at the end of the catalog number.
Individually isolated
These modules have individually isolated inputs or outputs. These modules have an I at the end of the catalog number.
I/O Type
Cat. No.
Page
Cat. No.
Page
AC digital
1756-IA8D 1756-IA16 1756-IA16I 1756-IA32 1756-IM16I 1756-IN16
4 7 10 13 86 89
1756-LSC8XIB8I 1756-OA8D 1756-OA8E 1756-OA16 1756-OA16I 1756-ON8
230 128 131 134 138 206
DC digital
1756-IB16 1756-IB16D 1756-IB16I 1756-IB16IF 1756-IB16ISOE 1756-IB32 1756-IC16 1756-IG16 1756-IH16I 1756-IH16ISOE 1756-IV16 1756-IV32 1756-OB8 1756-OB8EI
16 19 22 25 28 31 34 77 80 83 119 122 141 144
1756-OB8I 1756-OB16D 1756-OB16E 1756-OB16I 1756-OB16IEF 1756-OB16IEFS 1756-OB16IS 1756-OB32 1756-OC8 1756-OG16 1756-OH8I 1756-OV16E 1756-OV32E
147 150 153 157 160 163 166 169 172 200 203 209 212
1756-OW16I 1756-OX8I
215 218
Contact Analog
1756-IF6CIS 1756-IF6I 1756-IF8 1756-IF8I 1756-IF16 1756-IF4FXOF2F 1756-IR6I 1756-IRT8I 1756-IR12 1756-IT6I 1756-IT6I2 1756-IT16
41 45 49 57 65 37 92 97 103 107 111 115
1756-OF4 1756-OF6CI 1756-OF6VI 1756-OF8 1756-OF8I
175 179 182 185 193
HART interface
1756-IF8H 1756-IF8IH 1756-IF16H 1756-IF16IH
54 61 70 73
1756-OF8H 1756-OF8IH
189 197
Specialty
1756-CFM 1756-HSC
221 226
1756-LSC8XIB8I 1756-PLS
230 234
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
3
Page 4
1756 ControlLogix I/O Specifications
1756-IA8D ControlLogix 120V AC diagnostic input module Simplified Schematic
1756-IA8D +5V
2
1
4
3
6
5
8
7
10
9
12
11
14
13
16
15
18
17
20
19
Not Used Input Display
Daisy Chain to Other RTBs
GND
L2-0
IN-0
L2-0
+5V
ControlLogix Backplane Interface
Group 0
Open Wire
IN-1
L2-0
IN-2
L2-0
Display GND
L1-0 Loss of Field Power
IN-3
L2-1
ControlLogix Backplane Interface
IN-5
L2-1
IN-6
L2-1
AC INPUT L2-1 ST 0 1 2 3 4 5 6 7 O FLT 0 1 2 3 4 5 6 7 K
L2 L1
Diagnostic Specifications - 1756-IA8D Attribute
1756-IA8D
Open wire
Off-state leakage current 1.5 mA min
Loss of power
Transition range 46…85V AC
Time stamp of diagnostics
±1 ms
Technical Specifications - 1756-IA8D Attribute
1756-IA8D
Inputs
Eight diagnostic (4 points/group)
Voltage category
120V AC 50/60 Hz
Operating voltage range(1)
79…132V AC, 47…63 Hz
Input voltage, nom
120V AC 50/60 Hz
Input delay time (screw to backplane) Off to On On to Off
4
Hardware delay: 10 ms max + filter time User-selectable filter time: 1 ms or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 ms or 18 ms
Current draw @ 5.1V
100 mA
Current draw @ 24V
3 mA
Total backplane power
0.58 W
Power dissipation, max
4.5 W @ 60 °C (140 °F)
Thermal dissipation
15.35 BTU/hr
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
47 kΩ, 1/2 W, 5% Resistor
IN-4
L2-1
Group 1
Group 0
Group 1
47 kΩ, 1/2 W, 5% Resistor
IN-7 L1-1 Loss of Field Power
Page 5
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-IA8D (continued) Attribute
1756-IA8D
Off-state voltage, max
20V
Off-state current, max
2.5 mA
On-state current, min
5 mA @ 74V AC
On-state current, max
16 mA @ 132V AC
Inrush current, max
250 mA
Input impedance, max
8.25 k @ 132V AC, 60 Hz
Cyclic update time
200 s…750 ms
Change of state
Software configurable
Time stamp of inputs
±200 μs
Isolation voltage
125V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1200V AC for 2 s
Module keying
Electronic, software configurable
Removable terminal block housing
1756-TBNH 1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(2)
North American temperature code
T4A
Enclosure type
None (open-style)
(1) UL certification for 120V 50/60 Hz nominal. Rockwell Automation specified to 74…132V, 47…63 Hz. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-IA8D Attribute
1756-IA8D
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
5
Page 6
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-IA8D (continued) Attribute
1756-IA8D
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 Hz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-IA8D Certification(1)
1756-IA8D
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
6
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 7
1756 ControlLogix I/O Specifications
1756-IA16 ControlLogix 120V AC input module 1756-IA16 Simplified Schematic
1
4
3
6
5
8
7
10
9
12
11
14
13
16
15
18
17
20
19
IN-1
IN-0
Group 0
+5V
IN-O
2
Daisy Chain to Other RTBs
L2-0 GND
IN-3
IN-2
IN-5
IN-4
IN-7
IN-6
L2-0
ControlLogix Backplane Interface
Display
AC INPUT
L2-0
IN-9
IN-8
IN-11 Group 1
IN-10
IN-13
IN-12
IN-15
Group 1
IN-14
L2-1
ST 0 1 2 3 4 5 6 7 O FLT 0 1 2 3 4 5 6 7 K
Group 0
L2-1
L2
L1
Technical Specifications - 1756-IA16 Attribute
1756-IA16
Inputs
16 (8 points/group)
Voltage category
120V AC 50/60 Hz
Operating voltage range(1)
74…132V AC, 47…63 Hz
Input voltage, nom
120V AC 50/60 Hz
Input delay time (screw to backplane) Off to On On to Off
Hardware delay: 10 ms max + filter time User-selectable filter time: 1 ms or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 ms or 18 ms
Current draw @ 5.1V
100 mA
Current draw @ 24V
2 mA
Total backplane power
0.58 W
Power dissipation, max
5.8 W @ 60 °C (140 °F)
Thermal dissipation
18.41 BTU/hr
Off-state voltage, max
20V
Off-state current, max
2.5 mA
On-state current, min
5 mA @ 74V AC
On-state current, max
13 mA @ 132V AC
Inrush current, max
250 mA peak (decaying to <37% in 22 ms, without activation)
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
7
Page 8
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-IA16 (continued) Attribute
1756-IA16
Input impedance, max
10.15 k @ 132V AC, 60 Hz
Cyclic update time
200 s…750 ms
Change of state
Software configurable
Time stamp of inputs
±200 μs
Isolation voltage
125V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1400V AC for 2 s
Module keying
Electronic, software configurable
Removable terminal block housing
1756-TBNH 1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(2)
North American temperature code
T4
Enclosure type
None (open-style)
(1) UL certification for 120V 50/60 Hz nominal. Rockwell Automation specified to 74…132V, 47…63 Hz. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-IA16
8
Attribute
1756-IA16
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 9
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-IA16 (continued) Attribute
1756-IA16
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Oscillatory surge withstand IEEE C37.90.1
3 kV
Certifications - 1756-IA16 Certification(1)
1756-IA16
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
9
Page 10
1756 ControlLogix I/O Specifications
1756-IA16I ControlLogix 120V AC isolated input module Simplified Schematic IN-O
1756-IA161
Isolated Wiring
+5V
L2-0
L2-0
L2-2
GND
L2-4
ControlLogix Backplane Interface
Display
Additional jumper bars are available as catalog number 1756-JMPR.
Jumper Bar (Cut to Length)
Nonisolated Wiring
L2
AC INPUT
2
1 3
IN-0 IN-1
L1-0
4
L2-2
6
5
IN-2
L1-2
L2-3
8
7
IN-3
L2-4
10
9
IN-4
L2-5
12 11
IN-5
L2-6
14 13
IN-6
L2-7
16 15
IN-7
L2-8
18 17
IN-8
L2-9
20 19
IN-9
L2-10
22 21
IN-10
L2-11
24 23
IN-11
L2-12
26 25
IN-12
L2-13 L2-14
28 27 30 29
IN-13 IN-14
L2-15
32 31
IN-15
L2-15 Not Used
34 33
Not Used Not Used
L2-0 L2-1
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K
Daisy Chain to Other RTBs
Technical Specifications - 1756-IA16I Attribute
1756-IA16I
Inputs
16 individually isolated
Voltage category
120V AC 50/60 Hz
Operating voltage range(1)
79…132V AC, 47…63 Hz
Input voltage, nom
120V AC 50/60 Hz
Input delay time (screw to backplane) Off to On On to Off
Hardware delay: 10 ms max + filter time User-selectable filter time: 1 ms or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 ms or 18 ms
Current draw @ 5.1V
125 mA
Current draw @ 24V
3 mA
Total backplane power
0.71 W
Power dissipation, max
4.9 W @ 60 °C (140 °F)
Thermal dissipation
16.71 BTU/hr
Off-state voltage, max
20V
Off-state current, max
2.5 mA
10
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
36 35
L1-4