Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 1 of 25

1756 ControlLogix I/O Specifications, Technical Data, pages 1 to 10

Pages 1 to 10 of 242: 1756 ControlLogix I/O Specifications Technical Data; Back Cover

The original document is the PDF (7.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1756-IB16, Allen-Bradley 1756-OB16E and Allen-Bradley 1756-TBNH

Page 1

Technical Data

1756 ControlLogix I/O Specifications Topic

Page

Summary of Changes

2

Available 1756 I/O Modules

3

ControlLogix I/O Accessories

239

Additional Resources

241

The ControlLogix® architecture provides a wide range of input and output modules to span many applications, from high-speed digital to process control. The ControlLogix architecture uses Producer/Consumer technology, which allows input information and output status to be shared among multiple ControlLogix controllers. Each ControlLogix I/O module mounts in a ControlLogix chassis and requires either a removable terminal block (RTB) or a 1492 interface module (IFM) to connect all field-side wiring. RTBs and IFMs are not included with the I/O modules. They must be ordered separately.

Page 2

1756 ControlLogix I/O Specifications

Summary of Changes This publication contains new and updated information as indicated in the following table.

2

Topic

Page

Updated 1756-IF4FXOF2F specifications

37

Updated 1756-IF8 specifications

49

Updated 1756-IF8H specifications

54

Updated 1756-IF8IH specifications

61

Updated 1756-IF16 specifications

65

Updated 1756-IF16H specifications

70

Updated 1756-IF16IH specifications

73

Updated 1756-OF4 specifications

175

Updated 1756-OF8 specifications

185

Updated 1756-OF8H specifications

189

Updated 1756-OF8IH specifications

197

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 3

1756 ControlLogix I/O Specifications

Available 1756 I/O Modules You can select these types of digital I/O modules. Digital I/O Type

Description

Diagnostic

These modules provide diagnostic features to the point level. These modules have a D at the end of the catalog number.

Electronic fusing

These modules have internal electronic fusing to help prevent too much current from flowing through the module. These modules have an E at the end of the catalog number.

Individually isolated

These modules have individually isolated inputs or outputs. These modules have an I at the end of the catalog number.

I/O Type

Cat. No.

Page

Cat. No.

Page

AC digital

1756-IA8D 1756-IA16 1756-IA16I 1756-IA32 1756-IM16I 1756-IN16

4 7 10 13 86 89

1756-LSC8XIB8I 1756-OA8D 1756-OA8E 1756-OA16 1756-OA16I 1756-ON8

230 128 131 134 138 206

DC digital

1756-IB16 1756-IB16D 1756-IB16I 1756-IB16IF 1756-IB16ISOE 1756-IB32 1756-IC16 1756-IG16 1756-IH16I 1756-IH16ISOE 1756-IV16 1756-IV32 1756-OB8 1756-OB8EI

16 19 22 25 28 31 34 77 80 83 119 122 141 144

1756-OB8I 1756-OB16D 1756-OB16E 1756-OB16I 1756-OB16IEF 1756-OB16IEFS 1756-OB16IS 1756-OB32 1756-OC8 1756-OG16 1756-OH8I 1756-OV16E 1756-OV32E

147 150 153 157 160 163 166 169 172 200 203 209 212

1756-OW16I 1756-OX8I

215 218

Contact Analog

1756-IF6CIS 1756-IF6I 1756-IF8 1756-IF8I 1756-IF16 1756-IF4FXOF2F 1756-IR6I 1756-IRT8I 1756-IR12 1756-IT6I 1756-IT6I2 1756-IT16

41 45 49 57 65 37 92 97 103 107 111 115

1756-OF4 1756-OF6CI 1756-OF6VI 1756-OF8 1756-OF8I

175 179 182 185 193

HART interface

1756-IF8H 1756-IF8IH 1756-IF16H 1756-IF16IH

54 61 70 73

1756-OF8H 1756-OF8IH

189 197

Specialty

1756-CFM 1756-HSC

221 226

1756-LSC8XIB8I 1756-PLS

230 234

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

3

Page 4

1756 ControlLogix I/O Specifications

1756-IA8D ControlLogix 120V AC diagnostic input module Simplified Schematic

1756-IA8D +5V

2

1

4

3

6

5

8

7

10

9

12

11

14

13

16

15

18

17

20

19

Not Used Input Display

Daisy Chain to Other RTBs

GND

L2-0

IN-0

L2-0

+5V

ControlLogix Backplane Interface

Group 0

Open Wire

IN-1

L2-0

IN-2

L2-0

Display GND

L1-0 Loss of Field Power

IN-3

L2-1

ControlLogix Backplane Interface

IN-5

L2-1

IN-6

L2-1

AC INPUT L2-1 ST 0 1 2 3 4 5 6 7 O FLT 0 1 2 3 4 5 6 7 K

L2 L1

Diagnostic Specifications - 1756-IA8D Attribute

1756-IA8D

Open wire

Off-state leakage current 1.5 mA min

Loss of power

Transition range 46…85V AC

Time stamp of diagnostics

±1 ms

Technical Specifications - 1756-IA8D Attribute

1756-IA8D

Inputs

Eight diagnostic (4 points/group)

Voltage category

120V AC 50/60 Hz

Operating voltage range(1)

79…132V AC, 47…63 Hz

Input voltage, nom

120V AC 50/60 Hz

Input delay time (screw to backplane) Off to On On to Off

4

Hardware delay: 10 ms max + filter time User-selectable filter time: 1 ms or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 ms or 18 ms

Current draw @ 5.1V

100 mA

Current draw @ 24V

3 mA

Total backplane power

0.58 W

Power dissipation, max

4.5 W @ 60 °C (140 °F)

Thermal dissipation

15.35 BTU/hr

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

47 kΩ, 1/2 W, 5% Resistor

IN-4

L2-1

Group 1

Group 0

Group 1

47 kΩ, 1/2 W, 5% Resistor

IN-7 L1-1 Loss of Field Power

Page 5

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IA8D (continued) Attribute

1756-IA8D

Off-state voltage, max

20V

Off-state current, max

2.5 mA

On-state current, min

5 mA @ 74V AC

On-state current, max

16 mA @ 132V AC

Inrush current, max

250 mA

Input impedance, max

8.25 k @ 132V AC, 60 Hz

Cyclic update time

200 s…750 ms

Change of state

Software configurable

Time stamp of inputs

±200 μs

Isolation voltage

125V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1200V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block housing

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(2)

North American temperature code

T4A

Enclosure type

None (open-style)

(1) UL certification for 120V 50/60 Hz nominal. Rockwell Automation specified to 74…132V, 47…63 Hz. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IA8D Attribute

1756-IA8D

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

5

Page 6

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IA8D (continued) Attribute

1756-IA8D

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 Hz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-IA8D Certification(1)

1756-IA8D

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

6

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 7

1756 ControlLogix I/O Specifications

1756-IA16 ControlLogix 120V AC input module 1756-IA16 Simplified Schematic

1

4

3

6

5

8

7

10

9

12

11

14

13

16

15

18

17

20

19

IN-1

IN-0

Group 0

+5V

IN-O

2

Daisy Chain to Other RTBs

L2-0 GND

IN-3

IN-2

IN-5

IN-4

IN-7

IN-6

L2-0

ControlLogix Backplane Interface

Display

AC INPUT

L2-0

IN-9

IN-8

IN-11 Group 1

IN-10

IN-13

IN-12

IN-15

Group 1

IN-14

L2-1

ST 0 1 2 3 4 5 6 7 O FLT 0 1 2 3 4 5 6 7 K

Group 0

L2-1

L2

L1

Technical Specifications - 1756-IA16 Attribute

1756-IA16

Inputs

16 (8 points/group)

Voltage category

120V AC 50/60 Hz

Operating voltage range(1)

74…132V AC, 47…63 Hz

Input voltage, nom

120V AC 50/60 Hz

Input delay time (screw to backplane) Off to On On to Off

Hardware delay: 10 ms max + filter time User-selectable filter time: 1 ms or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 ms or 18 ms

Current draw @ 5.1V

100 mA

Current draw @ 24V

2 mA

Total backplane power

0.58 W

Power dissipation, max

5.8 W @ 60 °C (140 °F)

Thermal dissipation

18.41 BTU/hr

Off-state voltage, max

20V

Off-state current, max

2.5 mA

On-state current, min

5 mA @ 74V AC

On-state current, max

13 mA @ 132V AC

Inrush current, max

250 mA peak (decaying to <37% in 22 ms, without activation)

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

7

Page 8

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IA16 (continued) Attribute

1756-IA16

Input impedance, max

10.15 k @ 132V AC, 60 Hz

Cyclic update time

200 s…750 ms

Change of state

Software configurable

Time stamp of inputs

±200 μs

Isolation voltage

125V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1400V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block housing

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(2)

North American temperature code

T4

Enclosure type

None (open-style)

(1) UL certification for 120V 50/60 Hz nominal. Rockwell Automation specified to 74…132V, 47…63 Hz. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IA16

8

Attribute

1756-IA16

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 9

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IA16 (continued) Attribute

1756-IA16

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Oscillatory surge withstand IEEE C37.90.1

3 kV

Certifications - 1756-IA16 Certification(1)

1756-IA16

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

9

Page 10

1756 ControlLogix I/O Specifications

1756-IA16I ControlLogix 120V AC isolated input module Simplified Schematic IN-O

1756-IA161

Isolated Wiring

+5V

L2-0

L2-0

L2-2

GND

L2-4

ControlLogix Backplane Interface

Display

Additional jumper bars are available as catalog number 1756-JMPR.

Jumper Bar (Cut to Length)

Nonisolated Wiring

L2

AC INPUT

2

1 3

IN-0 IN-1

L1-0

4

L2-2

6

5

IN-2

L1-2

L2-3

8

7

IN-3

L2-4

10

9

IN-4

L2-5

12 11

IN-5

L2-6

14 13

IN-6

L2-7

16 15

IN-7

L2-8

18 17

IN-8

L2-9

20 19

IN-9

L2-10

22 21

IN-10

L2-11

24 23

IN-11

L2-12

26 25

IN-12

L2-13 L2-14

28 27 30 29

IN-13 IN-14

L2-15

32 31

IN-15

L2-15 Not Used

34 33

Not Used Not Used

L2-0 L2-1

ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K

Daisy Chain to Other RTBs

Technical Specifications - 1756-IA16I Attribute

1756-IA16I

Inputs

16 individually isolated

Voltage category

120V AC 50/60 Hz

Operating voltage range(1)

79…132V AC, 47…63 Hz

Input voltage, nom

120V AC 50/60 Hz

Input delay time (screw to backplane) Off to On On to Off

Hardware delay: 10 ms max + filter time User-selectable filter time: 1 ms or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 ms or 18 ms

Current draw @ 5.1V

125 mA

Current draw @ 24V

3 mA

Total backplane power

0.71 W

Power dissipation, max

4.9 W @ 60 °C (140 °F)

Thermal dissipation

16.71 BTU/hr

Off-state voltage, max

20V

Off-state current, max

2.5 mA

10

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

36 35

L1-4

L1