Page 11

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IA16I (continued) Attribute

1756-IA16I

On-state current, min

5 mA @ 79V AC, 47…63 Hz

On-state current, max

15 mA @ 132V AC, 47…63 Hz

Inrush current, max

250 mA

Input impedance, max

8.8 k @ 132V AC, 60 Hz

Cyclic update time

200 s…750 ms

Change of state

Software configurable

Time stamp of inputs

±200 μs

Isolation voltage

125V (continuous), basic insulation type, inputs-to-backplane, and input-to-input Routine tested @ 1200V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block housing

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(2)

North American temperature code

T4A

Enclosure type

None (open-style)

(1) UL certification for 120V 50/60 Hz nominal. Rockwell Automation specified to 74…132V, 47…63 Hz. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IA16I Attribute

1756-IA16I

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

11

Page 12

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IA16I (continued) Attribute

1756-IA16I

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Oscillatory surge withstand IEEE C37.90.1

3 kV

,

Certifications - 1756-IA16I Certification(1)

1756-IA16I

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

12

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 13

1756 ControlLogix I/O Specifications

1756-IA32 ControlLogix AC (74…132V) input module Simplified Schematic

1756-IA32

+5V

IN-O L2-0

Group 0

GND ControlLogix Backplane Interface

Display

Daisy Chain to Other RTBs

Group 1

AC INPUT ST 0 1 2 3 4 5 6 7

1 11 11 1 ST 8 9 0 1 2 3 4 5 O K 1 1 1 12 22 2 ST 6 7 8 9 0 1 2 3 2 2 2 22 23 3 ST 4 5 6 7 8 9 0 1

IN-1 IN-3 IN-5 IN-7 IN-9 IN-11 IN-13 IN-15 L2-0 IN-17 IN-19 IN-21 IN-23 IN-25 IN-27 IN-29 IN-31 L2-1

2

1

4

3

6

5

8

7

10

9

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

IN-0 IN-2 IN-4 IN-6 IN-8 IN-10 IN-12 IN-14 L2-0 IN-16 IN-18 IN-20 IN-22 IN-24 IN-26 IN-28 IN-30 L2-1

Group 0

Group 1

L1

L2

Technical Specifications - 1756-IA32 Attribute

1756-IA32

Inputs

32 (16 points/group)

Voltage category

120V AC 50/60 Hz

Operating voltage range

74…132V AC, 47…63 Hz

Input voltage, nom

120V AC 50/60 Hz

Input delay time (screw to backplane) Off to On On to Off

Hardware delay: 1.5 ms nom/10 ms max + filter time User-selectable filter time: 1 ms or 2 ms Hardware delay: 1 ms nom/8 ms max + filter time User-selectable filter time: 9 ms or 18 ms

Current draw @ 5.1V

165 mA

Current draw @ 24V

2 mA

Total backplane power

0.9 W

Power dissipation, max

6.1 W @ 60 °C (140 °F)

Thermal dissipation

20.8 BTU/hr

Off-state voltage, max

20V

Off-state current, max

2.5 mA

On-state current, min

5 mA @ 74V AC

On-state current, max

15 mA @ 132V AC

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

13

Page 14

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IA32 (continued) Attribute

1756-IA32

Inrush current, max

390 mA

Input impedance, max

14.0 k @ 132V AC, 60 Hz

Cyclic update time

200 s…750 ms

Change of stat

Software configurable

Time stamp of inputs

±200 μs

Isolation voltage

250V (continuous), basic insulation type, inputs-to-backplane 125V (continuous), basic insulation type, input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block housing

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(1)

North American temperature code

T4

Enclosure type

None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IA32 Attribute

1756-IA32

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

14

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 15

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IA32 (continued) Attribute

1756-IA32

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-IA32 Certification(1)

1756-IA32

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

15

Page 16

1756 ControlLogix I/O Specifications

1756-IB16 ControlLogix DC (10…31.2V) input module 1756-IB16 Simplified Schematic

IN-0

IN-1

+5V

Group 0

IN-0

IN-2

IN-3

Daisy Chain to Other RTBs

GND-0

IN-4

IN-5

IN-6

IN-7

GND ControlLogix Backplane Interface

GND-0

GND-0

Display

IN-9

IN-8 IN-10

IN-11

Group 1

DC INPUT ST 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15

IN-12

IN-13 IN-15

O K

IN14 GND-1

GND-1

DC COM

Technical Specifications - 1756-IB16 Attribute

1756-IB16

Inputs

16 (8 points/group)

Voltage category

12/24V DC sink

Operating voltage range

10…31.2V DC

Input voltage, nom

24V DC

Input delay time (screw to backplane) Off to On On to Off

Hardware delay: 290 s nom/1 ms max + filter time User-selectable filter time: 0 ms, 1 ms, or 2 ms Hardware delay: 700 s nom/2 ms max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms

Current draw @ 5.1V

100 mA

Current draw @ 24V

2 mA

Total backplane power

0.56 W

Power dissipation, max

5.1 W @ 60 °C (140 °F)

Thermal dissipation

17.39 BTU/hr

Off-state voltage, max

5V

Off-state current, max

1.5 mA

On-state current, min

2 mA @ 10V DC

On-state current, max

10 mA @ 31.2V DC

16

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Group 0

+

Group 1

Page 17

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IB16 (continued) Attribute

1756-IB16

Inrush current, max

250 mA peak (decaying to < 37% in 22 ms, without activation)

Input impedance, max

3.12 k @ 31.2V DC

Cyclic update time

200 s…750 ms

Change of state

Software configurable

Time stamp of inputs

±200 μs

Isolation voltage

250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block housing

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(1)

North American temperature code

T3C

IEC temperature code

T3

Enclosure type

None (open-style)

Reverse polarity protection

Yes

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IB16 Attribute

1756-IB16

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

17

Page 18

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IB16 (continued) Attribute

1756-IB16

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Oscillatory surge withstand IEEE C37.90.1

3 kV

Certifications - 1756-IB16 Certification(1)

1756-IB16

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T3 X Gc

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

18

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 19

1756 ControlLogix I/O Specifications

1756-IB16D ControlLogix DC (10…30V) diagnostic input module 1756-IB16D

Simplified Schematic Input

+5V

IN-0

ControlLogix Backplane Interface

Daisy Chain to Other RTBs

Display

Group 0

Group 1

GND-0 GND

Group 2

Open Wire

Group 3

GND-0 GND-0 GND-0

2

1

IN-0

4

3

6

5

IN-1 IN-2

GND-0

8

7

IN-3

GND-1 GND-1

10

9

12 11

IN-4 IN-5

GND-1

14 13

IN-6

GND-1

16 15

IN-7

GND-2

18 17

IN-8

GND-2 GND-2

20 19

IN-9 IN-10

GND-2 GND-3

24 23 26 25

IN-11 IN-12

GND-3

28 27

IN-13

GND-3 GND-3 GND-3

30 29

34 33

IN-14 IN-15 Not Used

Not Used

36 35

Not Used

22 21

32 31

Leakage Resistor

Group 0

Group 1

Leakage Resistor

Group 2

Group 3

DC INPUT –

+

DC COM

ST 0 1 2 3 4 5 6 7 FLT 0 1 2 3 4 5 6 7 O K ST 8 9 10 11 12 13 14 15 FLT 8 9 10 11 12 13 14 15 DIAGNOSTIC

Recommended Leakage Resistor Size 1/4 W, 5%

Supply Voltage

3.9K

10V DC

5.6K

12V DC

15K

24V DC

20K

30V DC

Diagnostic Specifications - 1756-IB16D Attribute

1756-IB16D

Open wire

Off-state leakage current 1.2 mA min

Time stamp of diagnostics

±1 ms

Technical Specifications - 1756-IB16D Attribute

1756-IB16D

Inputs

16 diagnostic (4 points/group)

Voltage category

12/24V DC sink

Operating voltage range

10…30V DC

Input voltage, nom

24V DC

Input delay time (screw to backplane) Off to On

On to Off

Hardware delay: 340 s nom/1 ms max + filter time User-selectable filter time: 0 ms, 1 ms, or 2 ms Hardware delay: 740 s nom/4 ms max + filter time User-selectable filter time: 0 ms, 1 ms, 9 ms, or 18 ms

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

19

Page 20

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IB16D (continued) Attribute

1756-IB16D

Current draw @ 5.1V

150 mA

Current draw @ 24V

3 mA

Total backplane power

0.84 W

Power dissipation, max

5.8 W @ 60 °C (140 °F)

Thermal dissipation

19.78 BTU/hr

Off-state voltage, max

5V

Off-state current, max

1.5 mA

On-state current, min

2 mA @ 10V DC

On-state current, max

13 mA @ 30V DC

Inrush current, max

250 mA

Input impedance, max

2.31 k @ 30V DC

Cyclic update time

200 s…750 ms

Change of state

Software configurable

Time stamp of inputs

±200 μs

Isolation voltage

250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block housing

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(1)

North American temperature code

T3C

IEC temperature code

T3

Enclosure type

None (open-style)

Reverse polarity protection

Yes

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IB16D Attribute

1756-IB16D

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

20

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016