Page 21

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IB16D (continued) Attribute

1756-IB16D

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-IB16D Certifications(1)

1756-IB16D

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T3 X Gc

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

21

Page 22

1756 ControlLogix I/O Specifications

1756-IB16I ControlLogix DC (10…30V) isolated input module 1756-IB161 Simplified Schematic

Isolated Wiring

+5V

DC-0 (-) DC-1 (-)

IN-0 Source Input Wiring

GND-0

DC-5 (-) DC-6 (-)

GND Jumper Bar (Cut to Length)

ControlLogix Backplane Interface

Display Nonisolated Wiring

DC (-)

GND-0 GND-1

1

2

IN-0

DC-0 (+)

3

4

IN-1

DC-1 (+)

GND-2

5

6

IN-2

7

8

IN-3

GND-3 GND-4

10

9

IN-4

GND-5

12 11

IN-5

GND-6

14 13

IN-6

GND-7

16 15

IN-7

GND-8

18 17

IN-8

GND-9

20 19

IN-9

GND-10

22 21

IN-10

GND-11

24 23

IN-11

GND-12

26 25

IN-12

GND-13 GND-14

28 27

IN-13

30 29

IN-14

GND-15

32 31

IN-15

GND-15 Not Used

34 33

Not Used Not Used

Additional jumper bars are available as catalog number 1756-JMPR.

DC INPUT

Daisy Chain to Other RTBs

ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K

22

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

36 35

(+) DC-5 (+) (+) DC-6 (+)

Sink Input Wiring

DC (+)

Page 23

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IB16I Attribute

1756-IB16I

Inputs

16 individually isolated

Voltage category

12/24V DC sink/source

Operating voltage range

10…30V DC

Input voltage, nom

24V DC

Input delay time (screw to backplane) Off to On On to Off

Hardware delay: 1 ms max + filter time User-selectable filter time: 0 ms, 1 ms, or 2 ms Hardware delay: 4 ms max + filter time User-selectable filter time: 0 ms, 1 ms, 2 ms, 9 ms, or 18 ms

Current draw @ 5.1V

100 mA

Current draw @ 24V

3 mA

Total backplane power

0.58 W

Power dissipation, max

5 W @ 60 °C (140 °F)

Thermal dissipation

17.05 BTU/hr

Off-state voltage, max

5V

Off-state current, max

1.5 mA

On-state current, min

2 mA @ 10V DC

On-state current, max

10 mA @ 30V DC

Inrush current, max

250 mA peak (decaying to < 37% in 22 ms, without activation)

Input impedance, max

3 k @ 30V DC

Cyclic update time

200 s…750 ms

Change of stat

Software configurable

Time stamp of inputs

±200 μs

Isolation voltage

250V (continuous), basic insulation type, inputs-to-backplane, and input-to-input Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block housing

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(1)

North American temperature code

T4

IEC temperature code

T4

Enclosure type

None (open-style)

Reverse polarity protection

Yes

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

23

Page 24

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IB16I Attribute

1756-IB16I

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 1, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Oscillatory surge withstand IEEE C37.90.1

3 kV

Certifications - 1756-IB16I Certification(1)

1756-IB16I

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

24

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 25

1756 ControlLogix I/O Specifications

1756-IB16IF ControlLogix DC (10…30V) sinking or sourcing, isolated, fast input module Simplified Schematic Current Limiter

IN-x

Opto-isolator

Display ControlLogix Backplane Interface

GND-x

Isolated Wiring

1756-IB16IF GND-0 GND-1

2

1

IN-0

DC-1 (-)

4

3

IN-1

DC-1 (+)

DC-2 (-)

GND-2

6

5

IN-2

DC-2 (+)

GND-3

8

7

IN-3

Source Input Wiring

GND-4

10

9

IN-4

DC-5 (-)

GND-5

12 11

IN-5

DC-6 (-)

GND-6

14 13

IN-6

Jumper Bar Cut to Length

GND-7 GND-8

16 15

IN-7

18 17

IN-8

GND-9

20 19

IN-9

GND-10

22 21

IN-10

GND-11

24 23

IN-11

GND-12

26 25

IN-12

GND-13 GND-14

28 27

IN-13

30 29

IN-14

GND-15

32 31

IN-15

GND-15

34 33

Not Used

36 35

Not Used Not Used

Nonisolated Wiring

DC (-)

(+) DC-5 (+) (+) DC-6 (+)

Sink Input Wiring

DC (+)

Additional jumper bars can be purchased by using catalog number 1756-JMPR.

Daisy Chain to Other RTBs DC INPUT

ST

01 2 3 4 5 6 7

ST

8 9 10 11 12 13 14 15

O K

PEER DEVICE

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

25

Page 26

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IB16IF Attribute

1756-IB16IF

Inputs

16 individually isolated

Voltage category

12/24V DC sink/source

Operating voltage range

10…30V DC

Input voltage, nom

24V DC

Input delay time (screw to backplane) Off to On On to Off

14 μs nom/23 μs max + user-configurable filter time of 0…30,000 μs 14 μs nom/23 μs max + user-configurable filter time of 0…30,000 μs

Current draw @ 5.1V

275 mA

Current draw @ 24V

3 mA

Total backplane power

1.47 W

Power dissipation

3.8 W @ 60 °C (140 °F)

Thermal dissipation

12.97 BTU/hr

Off-state voltage, max

5V

Off-state current, max

1.5 mA

On-state current, min

2 mA @ 10V DC

On-state current, max

5 mA @ 30V DC

Input impedance, max

6 k @ 30V DC

Cyclic update time

200 μs…750 ms

Change of state

Software configurable

Time stamp of inputs

± 4 μs for inputs < 4 kHz ± 13 μs for inputs > 4 kHz

Isolation voltage

250V (continuous), reinforced insulation type, inputs-to-backplane 250V (continuous), basic insulation type, input-to-input Type tested @ 2300V AC for 60 s inputs-to-backplane Type tested @ 1500V AC for 60 s input-to-input

Module keying

Electronic, software configurable

Removable terminal block housing

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1 on signal ports(1)

North American temperature code

T4A

IEC temperature code

T4

Enclosure type

None (open-style)

Reverse polarity protection

Yes

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

26

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 27

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IB16IF Attribute

1756-IB16IF

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 1, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-IB16IF Certification(1)

1756-IB16IF c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

27

Page 28

1756 ControlLogix I/O Specifications

1756-IB16ISOE ControlLogix DC (10…55V) sequence of events input module Simplified Schematic

Electronic Current Limit Circuit IN-0

GND-0

1756-IB16ISOE Isolated Wiring

GND-0 GND-1 +5V GND-2 GND-3 Source Input Wiring GND-4 DC-5 (-) GND-5 GND-6 DC-6 (-) GND-7 GND-8 Jumper Bar GND-9 (Cut to Length) ControlLogix Display GND-10 Backplane GND-11 Nonisolated Interface GND-12 Wiring GND-13 GND-14 GND-15 Additional jumper bars are available GND-15 DC (-) as catalog number 1756-JMPR. Not Used DC-0 (-)

2

1

4

3

6

5

8

7

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Daisy Chain to Other RTBs

SOE INPUT ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K

Technical Specifications - 1756-IB16ISOE Attribute

1756-IB16ISOE

Inputs

16 individually isolated, sequence of events

Voltage category

24/48V DC sink/source

Operating voltage range

10…55V DC

Input voltage, nom

24V DC

Input delay time (screw to backplane) Off to On

On to Off

Hardware delay: 10 s nom/20 s max + firmware scan: up to 25 μs + filter time: 0…50 ms + ASIC delay: 175 s (FIFO) or 625 s (Coordinated System Time per point) Hardware delay: 25 μs nom/50 μs max + firmware scan: up to 25 μs + filter time: 0…50 ms + ASIC delay: 175 s (FIFO) or 625 s (Coordinated System Time per point)

Current draw @ 5.1V

320 mA

Current draw @ 24V

2 mA

Total backplane power

1.7 W

Power dissipation, max

5.5 W @ 60 °C (140 °F)

Thermal dissipation

17.22 BTU/hr

28

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Sink Input Wiring IN-0 DC-0 (+) IN-1 DC-1 (+) IN-2 IN-3 Source Input Wiring IN-4 DC-5 (+) IN-5 IN-6 DC-6 (+) IN-7 IN-8 Sink Input Wiring IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used DC (+)

Page 29

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IB16ISOE (continued) Attribute

1756-IB16ISOE

Off-state voltage, max

5V

Off-state current, max

1.5 mA

On-state current, min

2.0 mA @ 9V DC

On-state current, nom

4.5 mA @ 24…31V DC

On-state current, max

5.1 mA @ 48…55V DC

Input impedance, max

10.8 k @ 55V DC

Cyclic update time

200 s…750 ms

Change of state

Software configurable

Time stamp of inputs

±100 μs

Isolation voltage

250V (continuous), basic insulation type, inputs-to-backplane 125V (continuous), basic insulation type, input-to-input Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(1)

North American temperature code

T4

IEC temperature code

T4

Enclosure type

None (open-style)

Reverse polarity protection

Yes

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IB16ISOE Attribute

1756-IB16ISOE

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

29

Page 30

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IB16ISOE (continued) Attribute

1756-IB16ISOE

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Oscillatory surge withstand IEEE C37.90.1

2.5 kV

Certifications - 1756-IB16ISOE Certification(1)

1756-IB16ISOE

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

30

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016