Page 21
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-IB16D (continued) Attribute
1756-IB16D
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-IB16D Certifications(1)
1756-IB16D
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T3 X Gc
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
21
Page 22
1756 ControlLogix I/O Specifications
1756-IB16I ControlLogix DC (10…30V) isolated input module 1756-IB161 Simplified Schematic
Isolated Wiring
+5V
DC-0 (-) DC-1 (-)
IN-0 Source Input Wiring
GND-0
DC-5 (-) DC-6 (-)
GND Jumper Bar (Cut to Length)
ControlLogix Backplane Interface
Display Nonisolated Wiring
DC (-)
GND-0 GND-1
1
2
IN-0
DC-0 (+)
3
4
IN-1
DC-1 (+)
GND-2
5
6
IN-2
7
8
IN-3
GND-3 GND-4
10
9
IN-4
GND-5
12 11
IN-5
GND-6
14 13
IN-6
GND-7
16 15
IN-7
GND-8
18 17
IN-8
GND-9
20 19
IN-9
GND-10
22 21
IN-10
GND-11
24 23
IN-11
GND-12
26 25
IN-12
GND-13 GND-14
28 27
IN-13
30 29
IN-14
GND-15
32 31
IN-15
GND-15 Not Used
34 33
Not Used Not Used
Additional jumper bars are available as catalog number 1756-JMPR.
DC INPUT
Daisy Chain to Other RTBs
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K
22
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
36 35
(+) DC-5 (+) (+) DC-6 (+)
Sink Input Wiring
DC (+)
Page 23
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-IB16I Attribute
1756-IB16I
Inputs
16 individually isolated
Voltage category
12/24V DC sink/source
Operating voltage range
10…30V DC
Input voltage, nom
24V DC
Input delay time (screw to backplane) Off to On On to Off
Hardware delay: 1 ms max + filter time User-selectable filter time: 0 ms, 1 ms, or 2 ms Hardware delay: 4 ms max + filter time User-selectable filter time: 0 ms, 1 ms, 2 ms, 9 ms, or 18 ms
Current draw @ 5.1V
100 mA
Current draw @ 24V
3 mA
Total backplane power
0.58 W
Power dissipation, max
5 W @ 60 °C (140 °F)
Thermal dissipation
17.05 BTU/hr
Off-state voltage, max
5V
Off-state current, max
1.5 mA
On-state current, min
2 mA @ 10V DC
On-state current, max
10 mA @ 30V DC
Inrush current, max
250 mA peak (decaying to < 37% in 22 ms, without activation)
Input impedance, max
3 k @ 30V DC
Cyclic update time
200 s…750 ms
Change of stat
Software configurable
Time stamp of inputs
±200 μs
Isolation voltage
250V (continuous), basic insulation type, inputs-to-backplane, and input-to-input Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Removable terminal block housing
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
North American temperature code
T4
IEC temperature code
T4
Enclosure type
None (open-style)
Reverse polarity protection
Yes
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
23
Page 24
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-IB16I Attribute
1756-IB16I
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 1, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Oscillatory surge withstand IEEE C37.90.1
3 kV
Certifications - 1756-IB16I Certification(1)
1756-IB16I
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
24
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 25
1756 ControlLogix I/O Specifications
1756-IB16IF ControlLogix DC (10…30V) sinking or sourcing, isolated, fast input module Simplified Schematic Current Limiter
IN-x
Opto-isolator
Display ControlLogix Backplane Interface
GND-x
Isolated Wiring
1756-IB16IF GND-0 GND-1
2
1
IN-0
DC-1 (-)
4
3
IN-1
DC-1 (+)
DC-2 (-)
GND-2
6
5
IN-2
DC-2 (+)
GND-3
8
7
IN-3
Source Input Wiring
GND-4
10
9
IN-4
DC-5 (-)
GND-5
12 11
IN-5
DC-6 (-)
GND-6
14 13
IN-6
Jumper Bar Cut to Length
GND-7 GND-8
16 15
IN-7
18 17
IN-8
GND-9
20 19
IN-9
GND-10
22 21
IN-10
GND-11
24 23
IN-11
GND-12
26 25
IN-12
GND-13 GND-14
28 27
IN-13
30 29
IN-14
GND-15
32 31
IN-15
GND-15
34 33
Not Used
36 35
Not Used Not Used
Nonisolated Wiring
DC (-)
(+) DC-5 (+) (+) DC-6 (+)
Sink Input Wiring
DC (+)
Additional jumper bars can be purchased by using catalog number 1756-JMPR.
Daisy Chain to Other RTBs DC INPUT
ST
01 2 3 4 5 6 7
ST
8 9 10 11 12 13 14 15
O K
PEER DEVICE
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
25
Page 26
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-IB16IF Attribute
1756-IB16IF
Inputs
16 individually isolated
Voltage category
12/24V DC sink/source
Operating voltage range
10…30V DC
Input voltage, nom
24V DC
Input delay time (screw to backplane) Off to On On to Off
14 μs nom/23 μs max + user-configurable filter time of 0…30,000 μs 14 μs nom/23 μs max + user-configurable filter time of 0…30,000 μs
Current draw @ 5.1V
275 mA
Current draw @ 24V
3 mA
Total backplane power
1.47 W
Power dissipation
3.8 W @ 60 °C (140 °F)
Thermal dissipation
12.97 BTU/hr
Off-state voltage, max
5V
Off-state current, max
1.5 mA
On-state current, min
2 mA @ 10V DC
On-state current, max
5 mA @ 30V DC
Input impedance, max
6 k @ 30V DC
Cyclic update time
200 μs…750 ms
Change of state
Software configurable
Time stamp of inputs
± 4 μs for inputs < 4 kHz ± 13 μs for inputs > 4 kHz
Isolation voltage
250V (continuous), reinforced insulation type, inputs-to-backplane 250V (continuous), basic insulation type, input-to-input Type tested @ 2300V AC for 60 s inputs-to-backplane Type tested @ 1500V AC for 60 s input-to-input
Module keying
Electronic, software configurable
Removable terminal block housing
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire category
1 on signal ports(1)
North American temperature code
T4A
IEC temperature code
T4
Enclosure type
None (open-style)
Reverse polarity protection
Yes
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
26
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 27
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-IB16IF Attribute
1756-IB16IF
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 1, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-IB16IF Certification(1)
1756-IB16IF c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
27
Page 28
1756 ControlLogix I/O Specifications
1756-IB16ISOE ControlLogix DC (10…55V) sequence of events input module Simplified Schematic
Electronic Current Limit Circuit IN-0
GND-0
1756-IB16ISOE Isolated Wiring
GND-0 GND-1 +5V GND-2 GND-3 Source Input Wiring GND-4 DC-5 (-) GND-5 GND-6 DC-6 (-) GND-7 GND-8 Jumper Bar GND-9 (Cut to Length) ControlLogix Display GND-10 Backplane GND-11 Nonisolated Interface GND-12 Wiring GND-13 GND-14 GND-15 Additional jumper bars are available GND-15 DC (-) as catalog number 1756-JMPR. Not Used DC-0 (-)
2
1
4
3
6
5
8
7
10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Daisy Chain to Other RTBs
SOE INPUT ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K
Technical Specifications - 1756-IB16ISOE Attribute
1756-IB16ISOE
Inputs
16 individually isolated, sequence of events
Voltage category
24/48V DC sink/source
Operating voltage range
10…55V DC
Input voltage, nom
24V DC
Input delay time (screw to backplane) Off to On
On to Off
Hardware delay: 10 s nom/20 s max + firmware scan: up to 25 μs + filter time: 0…50 ms + ASIC delay: 175 s (FIFO) or 625 s (Coordinated System Time per point) Hardware delay: 25 μs nom/50 μs max + firmware scan: up to 25 μs + filter time: 0…50 ms + ASIC delay: 175 s (FIFO) or 625 s (Coordinated System Time per point)
Current draw @ 5.1V
320 mA
Current draw @ 24V
2 mA
Total backplane power
1.7 W
Power dissipation, max
5.5 W @ 60 °C (140 °F)
Thermal dissipation
17.22 BTU/hr
28
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Sink Input Wiring IN-0 DC-0 (+) IN-1 DC-1 (+) IN-2 IN-3 Source Input Wiring IN-4 DC-5 (+) IN-5 IN-6 DC-6 (+) IN-7 IN-8 Sink Input Wiring IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used DC (+)
Page 29
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-IB16ISOE (continued) Attribute
1756-IB16ISOE
Off-state voltage, max
5V
Off-state current, max
1.5 mA
On-state current, min
2.0 mA @ 9V DC
On-state current, nom
4.5 mA @ 24…31V DC
On-state current, max
5.1 mA @ 48…55V DC
Input impedance, max
10.8 k @ 55V DC
Cyclic update time
200 s…750 ms
Change of state
Software configurable
Time stamp of inputs
±100 μs
Isolation voltage
250V (continuous), basic insulation type, inputs-to-backplane 125V (continuous), basic insulation type, input-to-input Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
North American temperature code
T4
IEC temperature code
T4
Enclosure type
None (open-style)
Reverse polarity protection
Yes
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-IB16ISOE Attribute
1756-IB16ISOE
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
29
Page 30
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-IB16ISOE (continued) Attribute
1756-IB16ISOE
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Oscillatory surge withstand IEEE C37.90.1
2.5 kV
Certifications - 1756-IB16ISOE Certification(1)
1756-IB16ISOE
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
30
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016