Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 4 of 25

1756 ControlLogix I/O Specifications, Technical Data, pages 31 to 40

Pages 31 to 40 of 242

The original document is the PDF (7.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1756-IB16, Allen-Bradley 1756-OB16E and Allen-Bradley 1756-TBNH

Page 31

1756 ControlLogix I/O Specifications

1756-IB32 ControlLogix DC (10…31.2V) input module 1756-IB32

Simplified Schematic

IN-0

+5V

Current Limiter

GND-0

Group 0

GND

Daisy Chain to Other RTBs

ControlLogix Backplane Interface

Display

Group 1

DC INPUT ST 0 1 2 3 4 5 6 7

1 11 11 1 ST 8 9 0 1 2 3 4 5 O K 1 1 1 12 22 2 ST 6 7 8 9 0 1 2 3

IN-21 IN-23 IN-25 IN-27 IN-29 IN-31

24 23

34 33

IN-0 IN-2 IN-4 IN-6 IN-8 IN-10 IN-12 IN-14 GND-0 IN-16 IN-18 IN-20 IN-22 IN-24 IN-26 IN-28 IN-30

GND-1

36 35

GND-1

IN-1 IN-3 IN-5 IN-7 IN-9 IN-11 IN-13 IN-15 GND-0 IN-17 IN-19

DC COM –

2 2 2 22 23 3 ST 4 5 6 7 8 9 0 1

2

1

4

3

6

5

8

7

10

9

12 11 14 13 16 15 18 17 20 19 22 21

26 25 28 27 30 29 32 31

Group 0

Group 1

+

Technical Specifications - 1756-IB32 Attribute

1756-IB32

Inputs

32 (16 points/group)

Voltage category

12/24V DC sink

Operating voltage range

10…31.2V DC

Input voltage, nom

24V DC

Input delay time (screw to backplane) Off to On On to Off

Hardware delay: 380 s max + filter time User-selectable filter time: 0 ms, 1 ms, or 2 ms Hardware delay: 420 s max + filter time User-selectable filter time: 0 ms, 1 ms, 2 ms, 9 ms, or 18 ms

Current draw @ 5.1V

120 mA

Current draw @ 24V

2 mA

Total backplane power

0.66 W

Power dissipation, max

6.2 W @ 60 °C (140 °F)

Thermal dissipation

21.1 BTU/hr @ 60 °C (140 °F)

Off-state voltage, max

5V

Off-state current, max

2.27 mA

On-state current, min

4.8 mA @ 10V DC

On-state current, max

5.5 mA @ 31.2V DC

Inrush current, max

250 mA (decaying to < 37% in 22 ms, without activation)

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

31

Page 32

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IB32 (continued) Attribute

1756-IB32

Input impedance, max

5.67 k @ 31.2V DC

Cyclic update time

200 s…750 ms

Change of state

Software configurable

Time stamp of inputs

±200 μs

Isolation voltage

250V (continuous), reinforced insulation type, inputs-to-backplane 250V (continuous), basic insulation type, input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1 - on signal ports(1)

North American temperature code

T4

IEC temperature code

T4

Enclosure type

None (open-style)

Reverse polarity protection

Yes

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IB32 Attribute

1756-IB32

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

32

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 33

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IB32 (continued) Attribute

1756-IB32

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Oscillatory surge withstand IEEE C37.90.1

3 kV

Certifications - 1756-IB32 Certification(1)

1756-IB32 c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

33

Page 34

1756 ControlLogix I/O Specifications

1756-IC16 ControlLogix DC (30…60V) input module 1756-IC16 Simplified Schematic

2

1

4

3

6

5

8

7

10

9

12

11

14

13

16

15

18

17

20

19

IN-0

IN-1

+5V IN-0

IN-2

IN-3

GND-0

IN-4

IN-5

Group 0

GND

IN-6

IN-7

ControlLogix Backplane Interface

GND-0

GND-0

Display

IN-8

IN-9

IN-10

IN-11

IN-11

IN-13

Group 1

IN-14

IN-15

DC INPUT

GND-1

GND-1 ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

Daisy Chain to Other RTBs

– DC COM

Technical Specifications - 1756-IC16 Attribute

1756-IC16

Inputs

16 (8 points/group)

Voltage category

48V DC sink

Operating voltage range

30…55V DC @ 60 °C (140 °F) 30…60V DC @ 55 °C (131 °F)

Input voltage, nom

48V DC

Input delay time (screw to backplane) Off to On On to Off

Hardware delay: 1 ms max + filter time User-selectable filter time: 0 ms, 1 ms, or 2 ms Hardware delay: 4 ms max + filter time User-selectable filter time: 0 ms, 1 ms, 2 ms, 9 ms, or 18 ms

Current draw @ 5.1V

100 mA

Current draw @ 24V

3 mA

Total backplane power

0.58 W

Power dissipation, max

5.2 W @ 60 °C (140 °F)

Thermal dissipation

17.73 BTU/hr

Off-state voltage, max

10V

Off-state current, max

1.5 mA

On-state current, min

2 mA @ 30V DC

On-state current, max

7 mA @ 60V DC

34

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Group 0

+

Group 1

Page 35

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IC16 (continued) Attribute

1756-IC16

Inrush current, max

250 mA

Input impedance, max

8.57 k @ 60V DC

Cyclic update time

200 s…750 ms

Change of state

Software configurable

Time stamp of inputs

±200 μs

Isolation voltage

250V (continuous), basic insulation type, inputs-to-backplane 125V (continuous), basic insulation type, input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s, inputs-to-backplane Routine tested @ 924V AC for 2 s, input group-to-group

Module keying

Electronic, software configurable

Removable terminal block housing

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(1)

North American temperature code

T4

IEC temperature code

T4

Enclosure type

None (open-style)

Reverse polarity protection

Yes

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IC16 Attribute

1756-IC16

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

35

Page 36

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IC16 (continued) Attribute

1756-IC16

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ± 2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Oscillatory surge withstand IEEE C37.90.1

3 kV

Certifications - 1756-IC16 Certification(1)

1756-IC16

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

36

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 37

1756 ControlLogix I/O Specifications

1756-IF4FXOF2F ControlLogix high-speed input/output analog module 1756-IF4FXOF2F Current (-) i

(+)

(+) User Analog Input Device

+IN-1/V IN-1/I -IN-1

2 1 4 3 6 5

+IN-0/V IN-0/I -IN-0

+IN-3/V IN-3/I -IN-3 Not Used Not Used V OUT-1

8 7 10 9 12 11

+IN-2/V IN-2/I -IN-2

14 13 16 15 18 17

Not Used Not Used V OUT-0 i

2-wire A Transmitter A

1756-IF4FXOF2F Voltage (+)

I OUT-1 RTN-1 Not Used Not Used Not Used Not Used Not Used Not Used Not Used

20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

(-) Shield Ground

Curren Output Load

A

I OUT-0 RTN-0 Not Used Not Used Not Used Not Used

Shield Ground

Not Used Not Used Not Used

+IN-1/V IN-1/I

2 1 4 3

+IN-0/V IN-0/I

-IN-1

6 5

-IN-0

+IN-3/V

8 7

+IN-2/V

IN-3/I -IN-3

10 9

IN-2/I

12 11

-IN-2

Not Used

14 13

Not Used

Not Used V OUT-1

16 15

Not Used

18 17

V OUT-0

I OUT-1

20 19

I OUT-0

RTN-1

22 21

RTN-0

Not Used

24 23

Not Used (-)

Not Used

26 25

Not Used

Not Used

28 27

Not Used

Not Used

30 29

Not Used

Not Used Not Used

32 31

Not Used

34 33

Not Used

Not Used

36 35

Not Used

(+)

Shield Ground

A = Inline field device (such as a strip chart recorder or meter)

ANALOG INPUT ANALOG OUTPUT CAL OK

Technical Specifications - 1756-IF4FXOF2F Attribute

1756-IF4FXOF2F

Current draw at 5.1V

375 mA

Current draw at 24V

100 mA

Voltage and current ratings

Backplane: 375 mA @ 5.1V DC, 100 mA @ 24V DC Analog inputs: -10…+10V, 4…20 mA Analog outputs: -10…+10V, 4…20 mA

Power consumption

4.3 W

Power dissipation

Voltage: 4.3 W Current: 4.7 W

Thermal dissipation

Voltage: 14.66 BTU/hr Current: 16.02 BTU/hr

Data format

Integer mode (left justified, 2 s complement) IEEE 32-bit floating point

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

37

Page 38

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IF4FXOF2F (continued) Attribute

1756-IF4FXOF2F

Isolation voltage

250V (continuous) Reinforced insulation type, Inputs and Outputs to Backplane No isolation between individual Inputs or Outputs Routine tested at 1800V AC for 1 s

Module keying

Electronic, software configurable

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire size

1756-TBCH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.) insulation max 1756-TBS6H Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.) insulation max

Terminal block torque specs

1756-TBCH: 0.5 Nm (4.4 pound-inches)

Wiring category(1)

2 - on signal ports

North American temp code

T4A

ATEX temp code

T4

IECEx temperature code

T4

Enclosure type

None (open-style)

(1) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Input Specifications - 1756-IF4FXOF2F Attribute

1756-IF4FXOF2F

Number

4 high-speed, submillisecond, differential

Input range

± 10V 0…10V 0…5V 0…20 mA (Overrange indication when exceeded)

Resolution

Approx 14 bits across ±10.5V DC (21V total) ±10.5V range: 1.3 mV/bit, 14-bit effective 0…10.5V range: 1.3 mV/bit, 13-bit effective 0…5.25V range: 1.3 mV/bit, 12-bit effective Approx 12 bits across 21 mA 0…21 mA range: 5.25 A/bit

Repeatability

±1 Least Significant Bit (LSB)(1)

Input impedance

Voltage: >1 M Current: 249

Open circuit detection

Positive full-scale reading within 1 s

Overvoltage protection

Voltage: 30V DC Current: 8V AC/DC

Calibrated accuracy @ 25 °C (77 °F)

0.05% of range immediately after calibration Better than 0.1% of range within calibration interval

Calibration interval

12 months

38

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 39

1756 ControlLogix I/O Specifications

Input Specifications - 1756-IF4FXOF2F (continued) Attribute

1756-IF4FXOF2F

Gain drift with temperature

Voltage: 25 ppm/°C max Current: 35 ppm/°C max

Module error

0.2% of range

Module scan time

300 s min(2)

Input conversion method

Successive approximation

(1) Repeatability is defined as the stability of the input channel reading when a steady state signal is applied, for example, ±1 LSB is one count (1.3 mV) from the nominal reading. (2) 300 s min for 1756-IF4FXOF2F/B, firmware revision 3.x or greater. 400 s min for 1756-IF4FXOF2F/A, firmware revision 1.x.

Output Specifications - 1756-IF4FXOF2F Attribute

1756-IF4FXOF2F

Number

2 high-speed voltage or current

Output range

± 10V 0…20 mA

Resolution

13 bits across 21 mA = 2.8 A/bit 14 bits across 21.8V = 1.3 mV/bit

Open circuit detection

Current output only (Output must be set to >0.1 mA)

Overvoltage protection

24V DC

Short circuit protection

Electronically current limited to 21 mA or less

Drive capability

Voltage: >2000 Current: 0…750

Output settling time

< 2 ms to 95% of final value with resistive loads

Calibrated accuracy @ 25 °C (77 °F)

0.05% of range immediately after calibration Better than 0.1% of range within calibration interval

Calibration interval

12 months

Offset drift

50 V/° C 1 A/° C

Gain drift with temperature

Voltage: 25 ppm/°C max Current: 50 ppm/°C max

Module error

Voltage: 0.2% of range Current: 0.3% of range

Update period for all channels (RPI), min

1 ms

Output conversion method

R-Ladder DAC, monotonicity with no missing codes

Environmental Specifications - 1756-IF4FXOF2F Attribute

1756-IF4FXOF2F

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

39

Page 40

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IF4FXOF2F (continued) Attribute

1756-IF4FXOF2F

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

IEC 61000-6-4

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±2 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on shielded ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-IF4FXOF2F Certification(1)

1756-IF4FXOF2F

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

CE

European Union 2014/30/EU EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2014/35/EU LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

RCM

Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions

Ex

European Union 2014/34/EU ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • DEMKO15ATEX1482X

IECEx

IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • IECEx UL 15.0053X

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

EAC

Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation

(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

40