Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of 1756 ControlLogix I/O Specifications, Technical Data

Spec sheet · Allen-Bradley

1756 ControlLogix I/O Specifications, Technical Data

Spec sheet242 pagesPDF 7.7 MB

Technical data for the Allen-Bradley 1756 ControlLogix I/O modules, including the 1756-IB16 DC input and 1756-OB16E output.

Download the PDF7.7 MB

Names · 3 models

The models it names

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

Rockwell Automation technical data covering the full range of 1756 ControlLogix I/O modules: AC and DC digital inputs and outputs (such as the 1756-IB16 and 1756-OB16E), analog, temperature, counter and other specialty modules. Each module has a simplified schematic and a table of technical specifications. The last pages list ControlLogix I/O accessories, including the 1756 removable terminal blocks and wiring systems.

Its parts

  1. Summary of Changes
  2. Available 1756 I/O Modules
  3. ControlLogix I/O Accessories
  4. Additional Resources

From the sheet

Key facts from this sheet

Each line names its page in the PDF.

Rockwell Automation technical data (publication 1756-TD002J-EN-P, November 2016) with specifications for the whole range of 1756 ControlLogix digital, analog and specialty I/O modules. Among them are the 1756-IB16 DC input module, the 1756-OB16E electronically fused DC output module and the 1756 removable terminal blocks such as the 1756-TBNH. It helps the reader choose a module, its terminal block, a chassis and a power supply.

Read for this summary: pages 1 to 3, 16 to 18, 153 to 156 and 239 to 240 of 242.

IB16 inputs
1756-IB16: 16 DC inputs, 8 points per group, 12/24V DC sink p. 16
OB16E outputs
1756-OB16E: 16 electronically fused outputs, 8 points per group, 12/24V DC source p. 154
TBNH block
1756-TBNH: 20-position NEMA screw-clamp removable terminal block p. 240
Terminal blocks
1756-IB16 and 1756-OB16E: 1756-TBNH or 1756-TBSH removable terminal block p. 17, 155
Operating voltage
1756-IB16 and 1756-OB16E: 10…31.2V DC; 1756-IB16 nominal 24V DC p. 16, 154
OB16E output current
1756-OB16E: 1 A per point, 8 A per module, at 60 °C (140 °F) p. 155
OB16E fusing
1756-OB16E: electronically fused per group p. 155
Operating temperature
1756-IB16 and 1756-OB16E: 0…60 °C (32…140 °F) p. 17, 155
Isolation
1756-IB16 and 1756-OB16E: 250V continuous between groups and to the backplane; none within a group p. 17, 155
IB16 backplane current
1756-IB16: 100 mA at 5.1V and 2 mA at 24V p. 16
OB16E backplane current
1756-OB16E: 250 mA at 5.1V and 2 mA at 24V p. 154
OB16E fault states
1756-OB16E: in fault or program mode each point holds last state, turns on or turns off (off is default) p. 155
Chassis
1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 p. 239
Power supplies
Standard: 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B; redundant: 1756-PA75R, 1756-PB75R p. 239

What this sheet walks you through

  • Choosing a 1756 I/O module by type p. 3
  • 1756-IB16 schematic, specifications and certifications p. 16, 17, 18
  • 1756-OB16E schematic, specifications and certifications p. 153, 154, 155, 156
  • Choosing a chassis and power supply p. 239
  • Choosing a screw-clamp or spring-clamp removable terminal block p. 240

Good to know

  • Removable terminal blocks and interface modules do not come with the I/O modules and must be ordered separately. p. 1
  • The standard terminal block housing is not deep enough for 2.5 mm2 (14 AWG) wire; that needs the 1756-TBE extended housing. p. 240
  • With separate power sources, do not exceed the isolation voltage specified for each module. p. 240

Questions this sheet answers

What terminal block does the 1756-IB16 use?

A 1756-TBNH or 1756-TBSH removable terminal block, which is ordered separately from the module. p. 1, 17

What input voltage does the 1756-IB16 accept?

It is a 12/24V DC sinking input module working from 10 to 31.2V DC, 24V DC nominal. p. 16

How much current can a 1756-OB16E output carry?

Up to 1 A per point and 8 A per module at 60 °C (140 °F). p. 155

Are 1756-OB16E outputs fused?

Yes, they are electronically fused per group. p. 155

Which chassis hold 1756 I/O modules?

The 1756-A4, 1756-A7, 1756-A10, 1756-A13 and 1756-A17 chassis; a module can go in any slot and each chassis needs a power supply. p. 239

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1756 ControlLogix I/O Specifications Technical Data1
    1. Summary of Changes2
    2. Available 1756 I/O Modules3
    3. ControlLogix I/O Accessories239
    4. Additional Resources241
  2. Back Cover242

From the PDF’s own bookmarks.

The whole text · 25 parts

Read the sheet here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 4031-40
  5. Pages 41 to 5041-50
  6. Pages 51 to 6051-60
  7. Pages 61 to 7061-70
  8. Pages 71 to 8071-80
  9. Pages 81 to 9081-90
  10. Pages 91 to 10091-100
  11. Pages 101 to 110101-110
  12. Pages 111 to 120111-120
  13. Pages 121 to 130121-130
  14. Pages 131 to 140131-140
  15. Pages 141 to 150141-150
  16. Pages 151 to 160151-160
  17. Pages 161 to 170161-170
  18. Pages 171 to 180171-180
  19. Pages 181 to 190181-190
  20. Pages 191 to 200191-200
  21. Pages 201 to 210201-210
  22. Pages 211 to 220211-220
  23. Pages 221 to 230221-230
  24. Pages 231 to 240231-240
  25. Pages 241 to 242241-242

The file

Revision and size

Part no.1756-TD002J-EN-P
RevisionNovember 2016
PublisherRockwell Automation
Pages242
PDF7.7 MB
TextText from the PDF itself.
1756-TD002J-EN-P

The first pages · 4 of 242

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 242
Page 2
Page 2of 242
Page 3
Page 3of 242
Page 4
Page 4of 242