Page 111

1756 ControlLogix I/O Specifications

1756-IT6I2 ControlLogix enhanced thermocouple analog input module 1756-IT6I Cold Junction Sensor Spade Lug

Wire

Not Used

Not Used

CJC–

CJC+

RTN-0

IN-0

RTN-1

IN-1

RTN-

IN-2

RTN-3

IN-3

RTN-

IN-4

RTN-5

IN-5

CJC–

CJC+

Not used

Not used

Thermocouple

Analog Input CAL

OK

Wire

Cold Junction Sensor

Spade Lug

Two CJCs, part number 94286501, are shipped with the module. Replacements can be ordered as RP-94286501.

Signal and User Counts - 1756-IT6I2 Range

Low Signal and User Counts

High Signal and User Counts

-12…30 mV

-15.80323 mV -32768 counts

31.396 mV 32767 counts

-12…78 mV

-15.15836 mV -32768 counts

79.241 mV 32767 counts

Technical Specifications - 1756-IT6I2 Attribute

1756-IT6I2

Inputs

Six individually isolated thermocouple 2 CJC

Input range

-12…78 mV (1.4 V per bit) -12…30 mV (0.7 V per bit – high-resolution range)

Resolution

16 bits -12…78 mV: 1.4 V/bit -12…30 mV: 0.7 V/bit

Thermocouples

B, E, J, K, R, S, T, N, C, D, L (TXK/XK)

Thermocouple linearization

ITS-90

Current draw @ 5.1V

200 mA

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

111

Page 112

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IT6I2 (continued) Attribute

1756-IT6I2

Current draw @ 24V

150 mA

Total backplane power

4.6 W

Power dissipation, max

4.6 W

Thermal dissipation

15.7 BTU/hr

Input impedance

>10 M

Open circuit detection time

Positive full scale reading within 2 s

Overvoltage protection, max

120V AC/DC

Normal mode noise rejection

60 dB at 60 Hz(1)

Common mode noise rejection

160 dB min, tested @ 600V AC/60 Hz applied with 100 differential resistance

Channel bandwidth

15 Hz(1)

Settling time

<80 ms to 5% of full scale(1)

Calibrated accuracy @ 25 °C

0.05% of full range @ 25 °C (77 °F) typical Better than 0.1% of range @ 25 °C (77 °F) worst case

Calibration interval

12 months

Local CJC sensor accuracy

±0.3 °C

Remote CJC sensor accuracy

±0.3 °C

Offset drift

0.5 V/°C

Gain drift with temperature, nom

15 ppm/°C 1.4 V/°C for -12…78 mV 0.6 V/°C for -12…30 mV

Gain drift with temperature, max

25 ppm/°C 2.3 V/°C for -12…78 mV 1.1 V/°C for -12…30 mV

Module error

0.15% of range

Module scan time

25 ms min floating point (millivolt) 50 ms min floating point (temperature) 10 ms min integer (millivolt)(1)

Data format

Integer mode (left justified, 2 s complement) IEEE 32-bit floating point

Module conversion method

Sigma-Delta

Isolation voltage

250V (continuous), basic insulation type, input channels-to-backplane, and input channel-to-channel Routine tested at 1350V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block

1756-TBNH only

RTB keying

User-defined mechanical

Slot width

1

Wire category

2(2)

North American temperature code

T4A

IEC temperature code

T4

Enclosure type

None (open-style)

(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

112

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 113

1756 ControlLogix I/O Specifications

Thermocouple Ranges - 1756-IT6I2 Attribute

1756-IT6I2

Thermocouple temperature/millivolt input range

-12…78 mV range

-12…30 mV range

Thermocouple Type B

300…1820 °C (572…3308 °F)

Full range

Thermocouple Type C

0…2315 °C (32…4199 °F)

0…1725 °C (32…3137 °F)

Thermocouple Type E

-270…+1000 °C (-454…+1832 °F)

-270…+415 °C (-454…+779 °F)

Thermocouple Type J

-210…+1200 °C (-346…+2192 °F)

-210…+550 °C (-346…+1022 °F)

Thermocouple Type K

-270…+1372 °C (-454…+2502 °F)

-270…+725 °C (-454…+1337 °F)

Thermocouple Type N

-270…+1300 °C (-454…+2372 °F)

-270…+840 °C (-454…+1544 °F)

Thermocouple Type R

-50…+1768 °C (-58…+3215 °F)

Full range

Thermocouple Type S

-50…+1768 °C (-58…+3215 °F)

Full range

Thermocouple Type T

-270…+400 °C (-454…+752 °F)

Full range

Thermocouple Type D

0…2320 °C (32…4208 °F)

0…1718 °C (32…3124 °F)

Thermocouple Type L (TXK/XK)

-200…+800 °C (-328…+1472 °F)

0…200…399 °C (392…750 °F) °C (32…3124 °F)

Thermocouple resolution over temperature range, nom

-12…78 mV range

-12…30 mV range

Type B, R, S, C

~0.15 °C (~0.28 °F)

~0.08 °C (~0.15 °F)

Type E, J, K, T, N

~0.05 °C (~0.09 °F)

~0.03 °C (~0.05 °F)

Type D

~0.07 °C (~0.13 °F)

~0.03 °C (~0.05 °F)

Type TXK/XK (L)

~0.02 °C (~0.04 °F)

~0.01 °C (~0.02 °F)

Environmental Specifications - 1756-IT6I2 Attribute

1756-IT6I2

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

113

Page 114

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IT6I2 (continued) Attribute

1756-IT6I2

EFT/B immunity IEC 61000-4-4

±2 kV at 5 kHz on shielded signal ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on shielded signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on shielded signal ports

Certifications - 1756-IT6I2 Certification(1)

1756-IT6I2

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

114

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 115

1756 ControlLogix I/O Specifications

1756-IT16 ControlLogix thermocouple analog input module. 1756-IT16 IMPORTANT: Remember the following:

• Connect the white end of the CJC sensor to the even-numbered terminal. Connect the orange end of the CJC sensor to the oddnumbered terminals. For CJC 0: –Orange end - Connected to terminal number 35 –Orange end - Connected to terminal number 35 –Orange end - Connected to terminal number 35 • CJC sensors do not come with the module. You must order the sensors, product catalog number 1756-CJC, separately. • If separate power sources are used, do not exceed the specific isolation voltage as listed in the specifications. –

1756-IT16 - Technical Specifications Attribute

1756-IT16

Inputs

16 channels, thermocouple mode Two CJC sensors for Thermocouple use. The CJC sensors, product catalog number 1756-CJC, do not come with the module. You must order the sensors separately.

Input range

-100…100 mV max 5VA

Resolution

24 bits -101…101 mV: 0.01 μV/count

Thermocouple types

B, C, D, E, J, K, N, R, S, T, TXK/XK (L)

Thermocouple linearization

ITS-90

Current draw @ 5.1V

200 mA

Current draw @ 24V

80 mA

Total backplane power

3W

Power dissipation, max

3W

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

115

Page 116

1756 ControlLogix I/O Specifications

1756-IT16 - Technical Specifications (continued) Attribute

1756-IT16

Thermal dissipation

9.9 BTU/hr

Input impedance, approx

1 G

Overvoltage protection, max

±30V DC

Normal mode noise rejection

75 dB at 60 Hz(1)

Common mode noise rejection

120 dB @ 60 Hz 1000 Ω differential 100 dB @ 50 Hz 1000 Ω differential

Channel bandwidth

Notch Filter configuration dependent See publication 1756-UM540 for possible values.

Settling time

Notch Filter configuration dependent See publication 1756-UM540 for possible values.

Open circuit detection

Positive full-scale reading within 2 s

Calibrated accuracy @ 25 °C

0.1%

Module error over full temperature range

0.2%

Local CJC sensor accuracy

± 0.3 °C

Remote CJC sensor, accuracy

± 0.3 °C

Module input scan time, min

50 ms

Data format

IEEE 32-bit floating point

Module conversion method

Sigma-Delta

Isolation voltage

250V (continuous), reinforced insulation type, inputs to backplane No isolation between individual inputs Type tested at 1800V AC for 60 s

Thermocouple type/temperature range Thermocouple Type B

21…1820 °C (68…3308 °F) 293…2093 °K 528…3768 °R

Thermocouple Type C

0…2320 °C (32…4208 °F) 273…2593 °K 492…4668 °R

Thermocouple Type D

0…2320 °C (32…4208 °F) 273…2593 °K 492…4668 °R

Thermocouple Type E

-270…+1000 °C (-454…+1832 °F) 3…1273 °K 6…2292 °R

Thermocouple Type J

-210…+1200 °C (-346…+2192 °F) 63…1473 °K 114…2652 °R

Thermocouple Type K

-270…+1372 °C (-454…+2502 °F) 3…1645 °K 6…2961 °R

Thermocouple Type N

-270…+1300 °C (-454…+2372 °F) 3…1573 °K 6…2832 °R

Thermocouple Type R

-50…+1768 °C (-58…+3215 °F) 223…2041 °K 402…3674 °R

116

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 117

1756 ControlLogix I/O Specifications

1756-IT16 - Technical Specifications (continued) Attribute

1756-IT16

Thermocouple Type S

-50…+1768 °C (-58…+3215 °F) 223…2041 °K 402…3674 °R

Thermocouple Type T

-270…+400 °C (-454…+752 °F) 3…673 °K 6…1212 °R

Thermocouple Type TXK/XK (L)

-200…+800 °C (-328…+1472 °F) 73…1073 °K 132…1932 °R

Thermocouple type/resolution, nom Type C, R

~0.03 °C (~0.05 °F)

Type B, S

~0.04 °C (~0.07 °F)

Type E, J, K, N, T, TXK/XK (L)

~0.01 °C (~0.02 °F)

Type D

~0.02 °C (~0.04 °F)

Module keying

Electronic, software configurable

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire size

0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max

Wire category

2 on shielded signal ports(2)

North American Temp Code

T4A

ATEX Temp Code

T4

IECEx Temp Code

T4

Enclosure type

None (open-style)

(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

1756-IT16 - Environmental Specifications Attribute

1756-IT16

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating -40…+85 °C (-40…+185 °F) IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

117

Page 118

1756 ControlLogix I/O Specifications

1756-IT16 - Environmental Specifications (continued) Attribute

1756-IT16

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions IEC 61000-6-4

CISPR 11, Class A

ESD Immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF Immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B Immunity IEC 61000-4-4

±2 kV at 5/100kHz on shielded ports

Surge Transient Immunity IEC 61000-4-5

±2 kV line-earth (CM) on shielded signal ports

Conducted RF Immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Enclosure Type Rating

None (open-style)

Certifications - 1756-IT16 Certification(1)

Description c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/EC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: • EN 61010-2-201; Control Equipment Safety Requirements

RCM

Australian Radiocommunications Act, compliant with: • EN 61000-6-4; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" II 3 G Ex nA IIC T4 Gc DEMKO15ATEX1482X

IECEx

IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" II 3 G Ex nA IIC T4 Gc IECEx UL 15.0053X

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3

EAC

Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation

(1) When marked. See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.

118

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 119

1756 ControlLogix I/O Specifications

1756-IV16 ControlLogix DC (10…30V) sourcing input module 1756-IV16 Simplified Schematic

2

1

4

3

6

5

IN-0

IN-1

+5V

IN-2

IN-3

DC-0+ Group 0

8

7

10

9

12

11

14

13

16

15

IN-6

IN-7

GND ControlLogix Backplane Interface

DC-0 +

DC-0 +

Display

IN-8

IN-9

IN-10

IN-11 Group 1

Group 0 IN-4

IN-5

IN-0

IN-12

IN-13 18

17

20

19

Group 1

IN-14

IN-15

DC INPUT

DC-1 +

DC-1 + ST 0 1 2 3 4 5 6 7 O ST 8 9 10 111213 1415 K

+

– DC COM

Daisy Chain to Other RTBs

Technical Specifications - 1756-IV16 Attribute

1756-IV16

Inputs

16 (8 points/group)

Voltage category

12/24V DC source

Operating voltage range

10…30V DC

Input voltage, nom

24V DC

Input delay time (screw to backplane) Off to On On to Off

Hardware delay: 280 s nom/1 ms max + filter time User-selectable filter time: 0 ms, 1 ms, or 2 ms Hardware delay: 540 s nom/2 ms max + filter time User-selectable filter time: 0 ms, 1 ms, 2 ms, 9 ms, or 18 ms

Current draw @ 5.1V

110 mA

Current draw @ 24V

2 mA

Total backplane power

0.61 W

Power dissipation, max

5.41 W @ 60 °C (140 °F)

Thermal dissipation

18.47 BTU/hr

Off-state voltage, max

5V DC

Off-state current, max

1.5 mA

On-state current, min

2 mA @ 10V DC

On-state current, max

10 mA @ 30V DC

Inrush current, max

250 mA

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

119

Page 120

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IV16 (continued) Attribute

1756-IV16

Input impedance, max

3.2 k @ 30V DC

Cyclic update time

200 s…750 ms

Change of state

Software configurable

Time stamp of inputs

±200 μs

Isolation voltage

250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block housing

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(1)

North American temperature code

T4A

IEC temperature code

T4

Enclosure type

None (open-style)

Reverse polarity protection

Yes

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IV16 Attribute

1756-IV16

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

120

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016