The text of a spec sheet · part 12 of 25
1756 ControlLogix I/O Specifications, Technical Data, pages 111 to 120
Pages 111 to 120 of 242
The original document is the PDF (7.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-IB16, Allen-Bradley 1756-OB16E and Allen-Bradley 1756-TBNH
Page 111
1756 ControlLogix I/O Specifications
1756-IT6I2 ControlLogix enhanced thermocouple analog input module 1756-IT6I Cold Junction Sensor Spade Lug
Wire
Not Used
Not Used
CJC–
CJC+
RTN-0
IN-0
RTN-1
IN-1
RTN-
IN-2
RTN-3
IN-3
RTN-
IN-4
RTN-5
IN-5
CJC–
CJC+
Not used
Not used
Thermocouple
Analog Input CAL
OK
Wire
Cold Junction Sensor
Spade Lug
Two CJCs, part number 94286501, are shipped with the module. Replacements can be ordered as RP-94286501.
Signal and User Counts - 1756-IT6I2 Range
Low Signal and User Counts
High Signal and User Counts
-12…30 mV
-15.80323 mV -32768 counts
31.396 mV 32767 counts
-12…78 mV
-15.15836 mV -32768 counts
79.241 mV 32767 counts
Technical Specifications - 1756-IT6I2 Attribute
1756-IT6I2
Inputs
Six individually isolated thermocouple 2 CJC
Input range
-12…78 mV (1.4 V per bit) -12…30 mV (0.7 V per bit – high-resolution range)
Resolution
16 bits -12…78 mV: 1.4 V/bit -12…30 mV: 0.7 V/bit
Thermocouples
B, E, J, K, R, S, T, N, C, D, L (TXK/XK)
Thermocouple linearization
ITS-90
Current draw @ 5.1V
200 mA
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
111
Page 112
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-IT6I2 (continued) Attribute
1756-IT6I2
Current draw @ 24V
150 mA
Total backplane power
4.6 W
Power dissipation, max
4.6 W
Thermal dissipation
15.7 BTU/hr
Input impedance
>10 M
Open circuit detection time
Positive full scale reading within 2 s
Overvoltage protection, max
120V AC/DC
Normal mode noise rejection
60 dB at 60 Hz(1)
Common mode noise rejection
160 dB min, tested @ 600V AC/60 Hz applied with 100 differential resistance
Channel bandwidth
15 Hz(1)
Settling time
<80 ms to 5% of full scale(1)
Calibrated accuracy @ 25 °C
0.05% of full range @ 25 °C (77 °F) typical Better than 0.1% of range @ 25 °C (77 °F) worst case
Calibration interval
12 months
Local CJC sensor accuracy
±0.3 °C
Remote CJC sensor accuracy
±0.3 °C
Offset drift
0.5 V/°C
Gain drift with temperature, nom
15 ppm/°C 1.4 V/°C for -12…78 mV 0.6 V/°C for -12…30 mV
Gain drift with temperature, max
25 ppm/°C 2.3 V/°C for -12…78 mV 1.1 V/°C for -12…30 mV
Module error
0.15% of range
Module scan time
25 ms min floating point (millivolt) 50 ms min floating point (temperature) 10 ms min integer (millivolt)(1)
Data format
Integer mode (left justified, 2 s complement) IEEE 32-bit floating point
Module conversion method
Sigma-Delta
Isolation voltage
250V (continuous), basic insulation type, input channels-to-backplane, and input channel-to-channel Routine tested at 1350V AC for 2 s
Module keying
Electronic, software configurable
Removable terminal block
1756-TBNH only
RTB keying
User-defined mechanical
Slot width
1
Wire category
2(2)
North American temperature code
T4A
IEC temperature code
T4
Enclosure type
None (open-style)
(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
112
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 113
1756 ControlLogix I/O Specifications
Thermocouple Ranges - 1756-IT6I2 Attribute
1756-IT6I2
Thermocouple temperature/millivolt input range
-12…78 mV range
-12…30 mV range
Thermocouple Type B
300…1820 °C (572…3308 °F)
Full range
Thermocouple Type C
0…2315 °C (32…4199 °F)
0…1725 °C (32…3137 °F)
Thermocouple Type E
-270…+1000 °C (-454…+1832 °F)
-270…+415 °C (-454…+779 °F)
Thermocouple Type J
-210…+1200 °C (-346…+2192 °F)
-210…+550 °C (-346…+1022 °F)
Thermocouple Type K
-270…+1372 °C (-454…+2502 °F)
-270…+725 °C (-454…+1337 °F)
Thermocouple Type N
-270…+1300 °C (-454…+2372 °F)
-270…+840 °C (-454…+1544 °F)
Thermocouple Type R
-50…+1768 °C (-58…+3215 °F)
Full range
Thermocouple Type S
-50…+1768 °C (-58…+3215 °F)
Full range
Thermocouple Type T
-270…+400 °C (-454…+752 °F)
Full range
Thermocouple Type D
0…2320 °C (32…4208 °F)
0…1718 °C (32…3124 °F)
Thermocouple Type L (TXK/XK)
-200…+800 °C (-328…+1472 °F)
0…200…399 °C (392…750 °F) °C (32…3124 °F)
Thermocouple resolution over temperature range, nom
-12…78 mV range
-12…30 mV range
Type B, R, S, C
~0.15 °C (~0.28 °F)
~0.08 °C (~0.15 °F)
Type E, J, K, T, N
~0.05 °C (~0.09 °F)
~0.03 °C (~0.05 °F)
Type D
~0.07 °C (~0.13 °F)
~0.03 °C (~0.05 °F)
Type TXK/XK (L)
~0.02 °C (~0.04 °F)
~0.01 °C (~0.02 °F)
Environmental Specifications - 1756-IT6I2 Attribute
1756-IT6I2
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
113
Page 114
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-IT6I2 (continued) Attribute
1756-IT6I2
EFT/B immunity IEC 61000-4-4
±2 kV at 5 kHz on shielded signal ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on shielded signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on shielded signal ports
Certifications - 1756-IT6I2 Certification(1)
1756-IT6I2
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
114
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 115
1756 ControlLogix I/O Specifications
1756-IT16 ControlLogix thermocouple analog input module. 1756-IT16 IMPORTANT: Remember the following:
• Connect the white end of the CJC sensor to the even-numbered terminal. Connect the orange end of the CJC sensor to the oddnumbered terminals. For CJC 0: –Orange end - Connected to terminal number 35 –Orange end - Connected to terminal number 35 –Orange end - Connected to terminal number 35 • CJC sensors do not come with the module. You must order the sensors, product catalog number 1756-CJC, separately. • If separate power sources are used, do not exceed the specific isolation voltage as listed in the specifications. –
1756-IT16 - Technical Specifications Attribute
1756-IT16
Inputs
16 channels, thermocouple mode Two CJC sensors for Thermocouple use. The CJC sensors, product catalog number 1756-CJC, do not come with the module. You must order the sensors separately.
Input range
-100…100 mV max 5VA
Resolution
24 bits -101…101 mV: 0.01 μV/count
Thermocouple types
B, C, D, E, J, K, N, R, S, T, TXK/XK (L)
Thermocouple linearization
ITS-90
Current draw @ 5.1V
200 mA
Current draw @ 24V
80 mA
Total backplane power
3W
Power dissipation, max
3W
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
115
Page 116
1756 ControlLogix I/O Specifications
1756-IT16 - Technical Specifications (continued) Attribute
1756-IT16
Thermal dissipation
9.9 BTU/hr
Input impedance, approx
1 G
Overvoltage protection, max
±30V DC
Normal mode noise rejection
75 dB at 60 Hz(1)
Common mode noise rejection
120 dB @ 60 Hz 1000 Ω differential 100 dB @ 50 Hz 1000 Ω differential
Channel bandwidth
Notch Filter configuration dependent See publication 1756-UM540 for possible values.
Settling time
Notch Filter configuration dependent See publication 1756-UM540 for possible values.
Open circuit detection
Positive full-scale reading within 2 s
Calibrated accuracy @ 25 °C
0.1%
Module error over full temperature range
0.2%
Local CJC sensor accuracy
± 0.3 °C
Remote CJC sensor, accuracy
± 0.3 °C
Module input scan time, min
50 ms
Data format
IEEE 32-bit floating point
Module conversion method
Sigma-Delta
Isolation voltage
250V (continuous), reinforced insulation type, inputs to backplane No isolation between individual inputs Type tested at 1800V AC for 60 s
Thermocouple type/temperature range Thermocouple Type B
21…1820 °C (68…3308 °F) 293…2093 °K 528…3768 °R
Thermocouple Type C
0…2320 °C (32…4208 °F) 273…2593 °K 492…4668 °R
Thermocouple Type D
0…2320 °C (32…4208 °F) 273…2593 °K 492…4668 °R
Thermocouple Type E
-270…+1000 °C (-454…+1832 °F) 3…1273 °K 6…2292 °R
Thermocouple Type J
-210…+1200 °C (-346…+2192 °F) 63…1473 °K 114…2652 °R
Thermocouple Type K
-270…+1372 °C (-454…+2502 °F) 3…1645 °K 6…2961 °R
Thermocouple Type N
-270…+1300 °C (-454…+2372 °F) 3…1573 °K 6…2832 °R
Thermocouple Type R
-50…+1768 °C (-58…+3215 °F) 223…2041 °K 402…3674 °R
116
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 117
1756 ControlLogix I/O Specifications
1756-IT16 - Technical Specifications (continued) Attribute
1756-IT16
Thermocouple Type S
-50…+1768 °C (-58…+3215 °F) 223…2041 °K 402…3674 °R
Thermocouple Type T
-270…+400 °C (-454…+752 °F) 3…673 °K 6…1212 °R
Thermocouple Type TXK/XK (L)
-200…+800 °C (-328…+1472 °F) 73…1073 °K 132…1932 °R
Thermocouple type/resolution, nom Type C, R
~0.03 °C (~0.05 °F)
Type B, S
~0.04 °C (~0.07 °F)
Type E, J, K, N, T, TXK/XK (L)
~0.01 °C (~0.02 °F)
Type D
~0.02 °C (~0.04 °F)
Module keying
Electronic, software configurable
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire size
0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max
Wire category
2 on shielded signal ports(2)
North American Temp Code
T4A
ATEX Temp Code
T4
IECEx Temp Code
T4
Enclosure type
None (open-style)
(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
1756-IT16 - Environmental Specifications Attribute
1756-IT16
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating -40…+85 °C (-40…+185 °F) IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
117
Page 118
1756 ControlLogix I/O Specifications
1756-IT16 - Environmental Specifications (continued) Attribute
1756-IT16
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions IEC 61000-6-4
CISPR 11, Class A
ESD Immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF Immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B Immunity IEC 61000-4-4
±2 kV at 5/100kHz on shielded ports
Surge Transient Immunity IEC 61000-4-5
±2 kV line-earth (CM) on shielded signal ports
Conducted RF Immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Enclosure Type Rating
None (open-style)
Certifications - 1756-IT16 Certification(1)
Description c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2004/108/EC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: • EN 61010-2-201; Control Equipment Safety Requirements
RCM
Australian Radiocommunications Act, compliant with: • EN 61000-6-4; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" II 3 G Ex nA IIC T4 Gc DEMKO15ATEX1482X
IECEx
IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" II 3 G Ex nA IIC T4 Gc IECEx UL 15.0053X
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3
EAC
Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When marked. See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.
118
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 119
1756 ControlLogix I/O Specifications
1756-IV16 ControlLogix DC (10…30V) sourcing input module 1756-IV16 Simplified Schematic
2
1
4
3
6
5
IN-0
IN-1
+5V
IN-2
IN-3
DC-0+ Group 0
8
7
10
9
12
11
14
13
16
15
IN-6
IN-7
GND ControlLogix Backplane Interface
DC-0 +
DC-0 +
Display
IN-8
IN-9
IN-10
IN-11 Group 1
Group 0 IN-4
IN-5
IN-0
IN-12
IN-13 18
17
20
19
Group 1
IN-14
IN-15
DC INPUT
DC-1 +
DC-1 + ST 0 1 2 3 4 5 6 7 O ST 8 9 10 111213 1415 K
+
– DC COM
Daisy Chain to Other RTBs
Technical Specifications - 1756-IV16 Attribute
1756-IV16
Inputs
16 (8 points/group)
Voltage category
12/24V DC source
Operating voltage range
10…30V DC
Input voltage, nom
24V DC
Input delay time (screw to backplane) Off to On On to Off
Hardware delay: 280 s nom/1 ms max + filter time User-selectable filter time: 0 ms, 1 ms, or 2 ms Hardware delay: 540 s nom/2 ms max + filter time User-selectable filter time: 0 ms, 1 ms, 2 ms, 9 ms, or 18 ms
Current draw @ 5.1V
110 mA
Current draw @ 24V
2 mA
Total backplane power
0.61 W
Power dissipation, max
5.41 W @ 60 °C (140 °F)
Thermal dissipation
18.47 BTU/hr
Off-state voltage, max
5V DC
Off-state current, max
1.5 mA
On-state current, min
2 mA @ 10V DC
On-state current, max
10 mA @ 30V DC
Inrush current, max
250 mA
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
119
Page 120
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-IV16 (continued) Attribute
1756-IV16
Input impedance, max
3.2 k @ 30V DC
Cyclic update time
200 s…750 ms
Change of state
Software configurable
Time stamp of inputs
±200 μs
Isolation voltage
250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Removable terminal block housing
1756-TBNH 1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
North American temperature code
T4A
IEC temperature code
T4
Enclosure type
None (open-style)
Reverse polarity protection
Yes
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-IV16 Attribute
1756-IV16
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
120
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016