The text of a spec sheet · part 13 of 25
1756 ControlLogix I/O Specifications, Technical Data, pages 121 to 130
Pages 121 to 130 of 242
The original document is the PDF (7.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-IB16, Allen-Bradley 1756-OB16E and Allen-Bradley 1756-TBNH
Page 121
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-IV16 (continued) Attribute
1756-IV16
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-IV16 Certification(1)
1756-IV16
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
121
Page 122
1756 ControlLogix I/O Specifications
1756-IV32 ControlLogix DC (10…30V) sourcing input module 1756-IV32
Simplified Schematic +5V DC-0+
Group 0
IN-0
GND ControlLogix Backplane Interface
Display
Daisy Chain to Other RTBs
Jumper Wire
Group 1
DC INPUT ST 0 1 2 3 4 5 6 7 111 11 1 ST 8 9 0 1 2 3 4 5 O K 11 112 22 2 ST 6 7 8 9 0 1 2 3 22 222 23 3 ST 4 5 6 7 8 9 0 1
IN-1
2
1
IN-0
IN-3
4
3
IN-2
IN-5
6
5
IN-4
IN-7
8
7
IN-6
IN-9
10
9
IN-8
IN-11
12 11
IN-10
IN-13
14 13
IN-12
IN-15
16 15
IN-14
DC-0 (+)
18 17
DC-0 (+)
IN-17 IN-19
20 19
IN-16
22 21
IN-18
IN-21
24 23
IN-20
IN-23
26 25
IN-22
IN-25
28 27
IN-24
IN-27
30 29
IN-26
IN-29
32 31
IN-28
IN-31
34 33
IN-30
DC-1 (+)
36 35
DC-1 (+)
+
– DC COM
Technical Specifications - 1756-IV32 Attribute
1756-IV32
Inputs
32 (16 points/group)
Voltage category
12/24V DC source
Operating voltage range
10…30V DC
Input voltage, nom
24V DC
Input delay time (screw to backplane) Off to On On to Off
Hardware delay: 350 s nom/1 ms max + filter time User-selectable filter time: 0 ms, 1 ms, or 2 ms Hardware delay: 540 s nom/2 ms max + filter time User-selectable filter time: 0 ms, 1 ms, 2 ms, 9 ms, or 18 ms
Current draw @ 5.1V
120 mA
Current draw @ 24V
2 mA
Total backplane power
0.66 W
Power dissipation, max
4.1 W @ 60 °C (140 °F)
Thermal dissipation
14 BTU/hr @ 60 °C (140 °F)
Off-state voltage, max
5V
Off-state current, max
1.5 mA
On-state current, min
2 mA @ 10V DC
On-state current, max
3.5 mA @ 30V DC
Inrush current, max
250 mA (decaying to <37% in 22 ms, without activation)
122
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Group 0
Group 1
Page 123
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-IV32 (continued) Attribute
1756-IV32
Input impedance, max
8.6 k @ 30V DC
Cyclic update time
200 s…750 ms
Change of state
Software configurable
Time stamp of inputs
±200 μs
Isolation voltage
250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire category
1 - on signal ports(1)
North American temperature code
T4A
IEC temperature code
T4
Enclosure type
None (open-style)
Reverse polarity protection
Yes
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-IV32 Attribute
1756-IV32
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1k Hz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
123
Page 124
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-IV32 (continued) Attribute
1756-IV32
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-IV32 Certification(1)
1756-IV32
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
124
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 125
1756 ControlLogix I/O Specifications
1756-OA8 ControlLogix 120/240V AC output module 1756-OA8 Simplified Schematic +5V
L1-0
2
1
4
3
6
5
8
7
OUT-0
L1-0
OUT-1
L1-0
OUT-0
Group 0
Display
10
9
12
11
14
13
16
15
Not Used
L1-0
Surge Current Chart
OUT-4
L1-1
Surge
OUT-5
L1-1
Current
Group 1
Group 1
OUT-6
L1-1 18
17
20
19
OUT-7
L1-1
2A
Group 0
OUT-3
L1-0
ControlLogix Backplane Interface
20 A
OUT-2
L1-0
L1-1
Not Used L2
0
Time
43 ms Daisy Chain to Other RTBs L1
AC OUTPUT ST 0 1 2 3 4 5 6 7 O K
Technical Specifications - 1756-OA8 Attribute
1756-OA8
Outputs
8 (4 points/group)
Pilot duty
2A
Voltage category
120/240V AC 50/60 Hz
Operating voltage range(1)
74…265V AC 47…63 Hz
Output delay time Off to On On to Off
9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz
Current draw @ 5.1V
200 mA
Current draw @ 24V
2 mA
Total backplane power
1.07 W
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
125
Page 126
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OA8 (continued) Attribute
1756-OA8
Power dissipation, max
5.1 W @ 60 °C (140 °F)
Thermal dissipation
17.39 BTU/hr
Off-state leakage current, max
3 mA per point
On-state voltage drop, max
1.5V peak @ 2 A 6V peak @ <50 mA
Current per point, max
2 A @ 60 °C (140 °F) linear derating
Current per module, max
5 A @ 30 °C (86 °F) linear derating 4 A @ 60 °C (140 °F) linear derating
Surge current per point
20 A for 43 ms per point, repeatable every 2 s @ 60 °C (140 °F)
Load current, min
10 mA per point
Commutating voltage
4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(2)
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s
Inhibit voltage, max
Zero crossing 60V peak
Module keying
Electronic, software configurable
Fusing
Not protected. A fused IFM is recommended to help protect outputs
Removable terminal block
1756-TBNH 1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(3)
North American temperature code
T4A
Enclosure type
None (open style)
(1) UL certification for 120/240V 50/60 Hz nominal. Rockwell Automation specified to 74…265, 47…63 Hz. (2) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/s for loads under 50 mA. The commutating dv/dt rating of the module for loads 50…500 mA (OUTPUT to L2) is 4V/s maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 10…50 mA range, a resistor can be added across the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it dissipates (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50…500 mA range, the L1 AC waveform could be at fault. Be sure that the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
126
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 127
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OA8 Attribute
1756-OA8
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8k V air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-OA8 Certification(1)
1756-OA8
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
127
Page 128
1756 ControlLogix I/O Specifications
1756-OA8D ControlLogix 120V AC diagnostic output module 1756-OA8D
Simplified Schematic
ControlLogix Backplane Interface
L1 Group 0
GATE
Verify/ No Load
OUT
6
5
8
7
10
9
12
11
14
13
16
15
18
17
L2-0 OUT-0 OUT-1
Daisy Chain to Other RTBs
Surge @ 30 °C (86 °F)
OUT-3
L1-1
OUT-4
L1-1
OUT-5
L1-1 Group 1
OUT-6
L1-1
5A
L1-1
Group 1 OUT-7
20
Continuous @ 30 °C (86 °F)
1A
Group 0
OUT-2
L1-0
Surge @ 60 °C (140 °F) Current
3
L1-0
Loss of Field Power
Surge Current Chart
8A
4
L1-0
L2 Display
1
L1-0
VAC Short
2
Not Used
Diagnostic Control Block with Opto and Transformer Isolation
19
L2-1
Continuous @ 60 °C (140 °F)
500 mA
L2
0
43 ms
Daisy Chain to Other RTBs
Time
L1
AC OUTPUT ST 0 1 2 3 4 5 6 7 O FLT 0 1 2 3 4 5 6 7
K
DIAGNOSTIC
Diagnostic Specifications - 1756-OA8D Attribute
1756-OA8D
Short trip, min
12 A for 500 s
No load
Off-state detection only
Output verification
On-state detection only
Pulse test
Configurable maximum width and max time delay from zero cross
Field power loss (zero cross)
Detects at 25V peak min (firmware phase locked loop)
Time stamp of diagnostics
±1 ms
128
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 129
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OA8D Attribute
1756-OA8D
Outputs
8 diagnostic, electronic fusing (4 points/group)
Voltage category
120V AC 50/60 Hz
Operating voltage range(1)
74…132V AC 47…63 Hz
Output delay time Off to On
9.3 ms @ 60 Hz 11 ms @ 50 Hz
On to Off
9.3 ms @ 60 Hz 11 ms @ 50 Hz
Current draw @ 5.1V
175 mA
Current draw @ 24V
250 mA
Total backplane power
6.89 W
Power dissipation, max
5.3 W @ 60 °C (140 °F)
Thermal dissipation
18.0 BTU/hr
Off-state leakage current, max
3 mA per point
On-state voltage drop, max
2.5V peak @ 0.5 A 3V peak @ 1 A
Current per point, max
1 A @ 30 °C (86 °F) linear derating 0.5 A @ 60 °C (140 °F) linear derating
Current per module, max
8 A @ 30 °C (86 °F) linear derating 4 A @ 60 °C (140 °F) linear derating
Surge current per point
8 A for 43 ms per point, repeatable every 2 s @ 30 °C (86 °F) 5 A for 43 ms per point, repeatable every 1 s @ 60 °C (140 °F)
Load current, min
10 mA per point
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
125V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1200V AC for 2 s
Inhibit voltage, max
Zero crossing 25V peak
Module keying
Electronic, software configurable
Fusing
Electronically fused per point
Removable terminal block
1756-TBNH 1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(2)
North American temperature code
T4A
Enclosure type
None (open style)
(1) UL certification for 120V 50/60 Hz nominal. Rockwell Automation specified to 74…132V, 47…63 Hz. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
129
Page 130
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OA8D Attribute
1756-OA8D
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-OA8D Certification(1)
1756-OA8D
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
130