Page 121

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IV16 (continued) Attribute

1756-IV16

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-IV16 Certification(1)

1756-IV16

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

121

Page 122

1756 ControlLogix I/O Specifications

1756-IV32 ControlLogix DC (10…30V) sourcing input module 1756-IV32

Simplified Schematic +5V DC-0+

Group 0

IN-0

GND ControlLogix Backplane Interface

Display

Daisy Chain to Other RTBs

Jumper Wire

Group 1

DC INPUT ST 0 1 2 3 4 5 6 7 111 11 1 ST 8 9 0 1 2 3 4 5 O K 11 112 22 2 ST 6 7 8 9 0 1 2 3 22 222 23 3 ST 4 5 6 7 8 9 0 1

IN-1

2

1

IN-0

IN-3

4

3

IN-2

IN-5

6

5

IN-4

IN-7

8

7

IN-6

IN-9

10

9

IN-8

IN-11

12 11

IN-10

IN-13

14 13

IN-12

IN-15

16 15

IN-14

DC-0 (+)

18 17

DC-0 (+)

IN-17 IN-19

20 19

IN-16

22 21

IN-18

IN-21

24 23

IN-20

IN-23

26 25

IN-22

IN-25

28 27

IN-24

IN-27

30 29

IN-26

IN-29

32 31

IN-28

IN-31

34 33

IN-30

DC-1 (+)

36 35

DC-1 (+)

+

– DC COM

Technical Specifications - 1756-IV32 Attribute

1756-IV32

Inputs

32 (16 points/group)

Voltage category

12/24V DC source

Operating voltage range

10…30V DC

Input voltage, nom

24V DC

Input delay time (screw to backplane) Off to On On to Off

Hardware delay: 350 s nom/1 ms max + filter time User-selectable filter time: 0 ms, 1 ms, or 2 ms Hardware delay: 540 s nom/2 ms max + filter time User-selectable filter time: 0 ms, 1 ms, 2 ms, 9 ms, or 18 ms

Current draw @ 5.1V

120 mA

Current draw @ 24V

2 mA

Total backplane power

0.66 W

Power dissipation, max

4.1 W @ 60 °C (140 °F)

Thermal dissipation

14 BTU/hr @ 60 °C (140 °F)

Off-state voltage, max

5V

Off-state current, max

1.5 mA

On-state current, min

2 mA @ 10V DC

On-state current, max

3.5 mA @ 30V DC

Inrush current, max

250 mA (decaying to <37% in 22 ms, without activation)

122

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Group 0

Group 1

Page 123

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IV32 (continued) Attribute

1756-IV32

Input impedance, max

8.6 k @ 30V DC

Cyclic update time

200 s…750 ms

Change of state

Software configurable

Time stamp of inputs

±200 μs

Isolation voltage

250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1 - on signal ports(1)

North American temperature code

T4A

IEC temperature code

T4

Enclosure type

None (open-style)

Reverse polarity protection

Yes

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IV32 Attribute

1756-IV32

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1k Hz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

123

Page 124

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IV32 (continued) Attribute

1756-IV32

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-IV32 Certification(1)

1756-IV32

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

124

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 125

1756 ControlLogix I/O Specifications

1756-OA8 ControlLogix 120/240V AC output module 1756-OA8 Simplified Schematic +5V

L1-0

2

1

4

3

6

5

8

7

OUT-0

L1-0

OUT-1

L1-0

OUT-0

Group 0

Display

10

9

12

11

14

13

16

15

Not Used

L1-0

Surge Current Chart

OUT-4

L1-1

Surge

OUT-5

L1-1

Current

Group 1

Group 1

OUT-6

L1-1 18

17

20

19

OUT-7

L1-1

2A

Group 0

OUT-3

L1-0

ControlLogix Backplane Interface

20 A

OUT-2

L1-0

L1-1

Not Used L2

0

Time

43 ms Daisy Chain to Other RTBs L1

AC OUTPUT ST 0 1 2 3 4 5 6 7 O K

Technical Specifications - 1756-OA8 Attribute

1756-OA8

Outputs

8 (4 points/group)

Pilot duty

2A

Voltage category

120/240V AC 50/60 Hz

Operating voltage range(1)

74…265V AC 47…63 Hz

Output delay time Off to On On to Off

9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz

Current draw @ 5.1V

200 mA

Current draw @ 24V

2 mA

Total backplane power

1.07 W

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

125

Page 126

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OA8 (continued) Attribute

1756-OA8

Power dissipation, max

5.1 W @ 60 °C (140 °F)

Thermal dissipation

17.39 BTU/hr

Off-state leakage current, max

3 mA per point

On-state voltage drop, max

1.5V peak @ 2 A 6V peak @ <50 mA

Current per point, max

2 A @ 60 °C (140 °F) linear derating

Current per module, max

5 A @ 30 °C (86 °F) linear derating 4 A @ 60 °C (140 °F) linear derating

Surge current per point

20 A for 43 ms per point, repeatable every 2 s @ 60 °C (140 °F)

Load current, min

10 mA per point

Commutating voltage

4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(2)

Scheduled outputs

Synchronization within 16.7 s max, reference to the Coordinated System Time

States in Fault mode per point

Hold last state, On or Off (Off is default)

States in Program mode per point

Hold last state, On or Off (Off is default)

Isolation voltage

250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s

Inhibit voltage, max

Zero crossing 60V peak

Module keying

Electronic, software configurable

Fusing

Not protected. A fused IFM is recommended to help protect outputs

Removable terminal block

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(3)

North American temperature code

T4A

Enclosure type

None (open style)

(1) UL certification for 120/240V 50/60 Hz nominal. Rockwell Automation specified to 74…265, 47…63 Hz. (2) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/s for loads under 50 mA. The commutating dv/dt rating of the module for loads 50…500 mA (OUTPUT to L2) is 4V/s maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 10…50 mA range, a resistor can be added across the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it dissipates (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50…500 mA range, the L1 AC waveform could be at fault. Be sure that the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

126

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 127

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-OA8 Attribute

1756-OA8

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8k V air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-OA8 Certification(1)

1756-OA8

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

127

Page 128

1756 ControlLogix I/O Specifications

1756-OA8D ControlLogix 120V AC diagnostic output module 1756-OA8D

Simplified Schematic

ControlLogix Backplane Interface

L1 Group 0

GATE

Verify/ No Load

OUT

6

5

8

7

10

9

12

11

14

13

16

15

18

17

L2-0 OUT-0 OUT-1

Daisy Chain to Other RTBs

Surge @ 30 °C (86 °F)

OUT-3

L1-1

OUT-4

L1-1

OUT-5

L1-1 Group 1

OUT-6

L1-1

5A

L1-1

Group 1 OUT-7

20

Continuous @ 30 °C (86 °F)

1A

Group 0

OUT-2

L1-0

Surge @ 60 °C (140 °F) Current

3

L1-0

Loss of Field Power

Surge Current Chart

8A

4

L1-0

L2 Display

1

L1-0

VAC Short

2

Not Used

Diagnostic Control Block with Opto and Transformer Isolation

19

L2-1

Continuous @ 60 °C (140 °F)

500 mA

L2

0

43 ms

Daisy Chain to Other RTBs

Time

L1

AC OUTPUT ST 0 1 2 3 4 5 6 7 O FLT 0 1 2 3 4 5 6 7

K

DIAGNOSTIC

Diagnostic Specifications - 1756-OA8D Attribute

1756-OA8D

Short trip, min

12 A for 500 s

No load

Off-state detection only

Output verification

On-state detection only

Pulse test

Configurable maximum width and max time delay from zero cross

Field power loss (zero cross)

Detects at 25V peak min (firmware phase locked loop)

Time stamp of diagnostics

±1 ms

128

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 129

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OA8D Attribute

1756-OA8D

Outputs

8 diagnostic, electronic fusing (4 points/group)

Voltage category

120V AC 50/60 Hz

Operating voltage range(1)

74…132V AC 47…63 Hz

Output delay time Off to On

9.3 ms @ 60 Hz 11 ms @ 50 Hz

On to Off

9.3 ms @ 60 Hz 11 ms @ 50 Hz

Current draw @ 5.1V

175 mA

Current draw @ 24V

250 mA

Total backplane power

6.89 W

Power dissipation, max

5.3 W @ 60 °C (140 °F)

Thermal dissipation

18.0 BTU/hr

Off-state leakage current, max

3 mA per point

On-state voltage drop, max

2.5V peak @ 0.5 A 3V peak @ 1 A

Current per point, max

1 A @ 30 °C (86 °F) linear derating 0.5 A @ 60 °C (140 °F) linear derating

Current per module, max

8 A @ 30 °C (86 °F) linear derating 4 A @ 60 °C (140 °F) linear derating

Surge current per point

8 A for 43 ms per point, repeatable every 2 s @ 30 °C (86 °F) 5 A for 43 ms per point, repeatable every 1 s @ 60 °C (140 °F)

Load current, min

10 mA per point

Scheduled outputs

Synchronization within 16.7 s max, reference to the Coordinated System Time

States in Fault mode per point

Hold last state, On or Off (Off is default)

States in Program mode per point

Hold last state, On or Off (Off is default)

Isolation voltage

125V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1200V AC for 2 s

Inhibit voltage, max

Zero crossing 25V peak

Module keying

Electronic, software configurable

Fusing

Electronically fused per point

Removable terminal block

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(2)

North American temperature code

T4A

Enclosure type

None (open style)

(1) UL certification for 120V 50/60 Hz nominal. Rockwell Automation specified to 74…132V, 47…63 Hz. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

129

Page 130

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-OA8D Attribute

1756-OA8D

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-OA8D Certification(1)

1756-OA8D

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

130