The text of a spec sheet · part 14 of 25

1756 ControlLogix I/O Specifications, Technical Data, pages 131 to 140

Pages 131 to 140 of 242

The original document is the PDF (7.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1756-IB16, Allen-Bradley 1756-OB16E and Allen-Bradley 1756-TBNH

Page 131

1756 ControlLogix I/O Specifications

1756-OA8E ControlLogix 120V AC electronically fused output module Simplified Schematic

1756-OA8E

Opto and Transformer Isolation

ControlLogix Backplane Interface

L1

VAC Short

2

1

4

3

6

5

8

7

10

9

12

11

14

13

16

15

18

17

20

19

Not Used

GATE

L2-0

L1-0

OUT L2

Group 0

OUT-0

L1-0

OUT-1

L1-0

Loss of Field Power

Display

OUT-2

L1-0

Surge Current Chart Daisy Chain to Other RTBs

Surge

20 A

OUT-3

L1-1

OUT-4

L1-1

OUT-5

Current

L1-1 Group 1

2A

OUT-6

L1-1

OUT-7

L1-1

0

Time

Group 0

Group 1

L2-1 L2

43 ms

Daisy Chain to Other RTBs L1

AC OUTPUT ST 0 1 2 3 4 5 6 7 O FUSE 0 1 2 3 4 5 6 7K

ELECTRONICALLY FUSED

Diagnostic Specifications - 1756-OA8E Attribute

1756-OA8E

Short trip, min

>20 A for 100 ms

Field power loss (zero cross)

Detects at 25V peak min (firmware phase locked loop)

Time stamp of diagnostics

±1 ms

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

131

Page 132

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OA8E Attribute

1756-OA8E

Outputs

Eight electronic fusing (four points/group)

Pilot duty

Yes

Voltage category Operating voltage range

120V AC 50/60 Hz (1)

Output delay time Off to On

74…132V AC 47…63 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz

On to Off

9.3 ms @ 60 Hz 11 ms @ 50 Hz

Current draw @ 5.1V

200 mA

Current draw @ 24V

250 mA

Total backplane power

7.02 W

Power dissipation, max

5.5 W @ 60 °C (140 °F)

Thermal dissipation

18.76 BTU/hr

Off-state leakage current, max

3 mA per point

On-state voltage drop, max

4V peak @ 2 A

Current per point, max

2 A @ 60 °C (140 °F)

Current per group, max

4 A @ 30 °C (86 °F) linear derating 2 A @ 60 °C (140 °F) linear derating

Current per module, max

8 A @ 30 °C (86 °F) linear derating 4 A @ 60 °C (140 °F) linear derating

Surge current per point

20 A for 43 ms per point, repeatable every 2 s @ 60 °C (140 °F)

Load current, min

10 mA per point

Scheduled outputs

Synchronization within 16.7 s max, reference to the Coordinated System Time

States in Fault mode per point

Hold last state, On or Off (default is Off)

States in Program mode per point

Hold last state, On or Off (default is Off)

Isolation voltage

125V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1200V AC for 2 s

Inhibit voltage, max

Zero crossing 25V peak

Module keying

Electronic, software configurable

Fusing

Electronically fused per point

Removable terminal block

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(2)

North American temperature code

T4A

Enclosure type

None (open style)

(1) UL certification for 120V 50/60Hz nominal. Rockwell Automation specified to 74…132V, 47…63 Hz. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

132

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 133

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-OA8E Attribute

1756-OA8E

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1k V line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-OA8E Certification(1)

1756-OA8E

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

133

Page 134

1756 ControlLogix I/O Specifications

1756-OA16 ControlLogix 120/240V AC output module 1756-OA16

Simplified Schematic ControlLogix Backplane Interface

L1-0 2

1

4

3

6

5

8

7

10

9

12

11

14

13

16

15

18

17

OUT-1

+5V

Group 0

L2-0

(Fused per Group) Display

Daisy Chain to Other RTBs

OUT-0

OUT-3

OUT-2

OUT-5 OUT-7

OUT-6

L1-0 OUT-0

L2-0

OUT-9

OUT-8

ControlLogix Backplane Interface

OUT-11 Group 1

Surge Current Chart

OUT-10

OUT-13

OUT-12

L1

OUT-15

Current

OUT-14

Per Group

Surge

20

20 A

L2-1

Per Group

0

43 ms

L1

Time

AC OUTPUT ST 0 1 2 3 4 5 6 7 FUSE ST 8 9 10 11 12 13 14 15

O K

FUSE

Diagnostic Specifications - 1756-OA16 Attribute

1756-OA16

Time stamp of diagnostics

±1 ms

Fuse blown

One fuse and indicator/group

134

19

L1-1

5A 2A 500 mA

Group 0

OUT-4

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

L2

Group 1

Page 135

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OA16 Attribute

1756-OA16

Outputs

16 mechanically fused/group (8 points/group)

Pilot duty

0.5 A

Voltage category

120/240V AC 50/60 Hz

Operating voltage range(1)

74…265V AC 47…63 Hz

Output delay time Off to On

9.3 ms @ 60 Hz 11 ms @ 50 Hz

On to Off

9.3 ms @ 60 Hz 11 ms @ 50 Hz

Current draw @ 5.1V

400 mA

Current draw @ 24V

2 mA

Total backplane power

2.1 W

Power dissipation, max

6.5 W @ 60 °C (140 °F)

Thermal dissipation

22.17 BTU/hr

Off-state leakage current, max

3 mA per point

On-state voltage drop, max

1.5V @ 0.5 A 5.7V @ load current < 50 mA

Current per point, max

0.5 A @ 60 °C (140 °F)

Current per group, max

2 A @ 60 °C (140 °F)

Current per module, max

4 A @ 60 °C (140 °F)

Surge current per point

5 A for 43 ms per point, repeatable every 2 s @ 60 °C (140 °F)

Surge current per group

15 A for 43 ms per point, repeatable every 2 s @ 60 °C (140 °F)

Load current, min

10 mA per point

Commutating voltage

4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(2)

Scheduled outputs

Synchronization within 16.7 s max, reference to the Coordinated System Time

States in Fault mode per point

Hold last state, On or Off (Off is default)

States in Program mode per point

Hold last state, On or Off (Off is default)

Isolation voltage

250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1400V AC for 2 s

Inhibit voltage, max

Zero crossing 60V peak

Module keying

Electronic, software configurable

Fusing

Mechanically fused/group, 3.15 A @ 250V AC slow blow, 1500 A interruption current, Littelfuse p/n H2153.15

Removable terminal block

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

135

Page 136

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OA16 (continued) Attribute

1756-OA16

Wire category

1(3)

North American temperature code

T4

Enclosure type

None (open style)

(1) UL certification for 120/240V 50/60 Hz nominal. Rockwell Automation specified to 74…265V, 47…63 Hz. (2) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/s for loads under 50 mA. The commutating dv/dt rating of the module for loads 50…500 mA (OUTPUT to L2) is 4V/s maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 10…50 mA range, a resistor can be added AC across the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it dissipates (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50…500 mA range, the L1 AC waveform could be at fault. Be sure that the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-OA16 Attribute

1756-OA16

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Oscillatory surge withstand IEEE C37.90.1

3 kV

136

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 137

1756 ControlLogix I/O Specifications

Certifications - 1756-OA16 Certification(1)

1756-OA16

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

137

Page 138

1756 ControlLogix I/O Specifications

1756-OA16I ControlLogix 120/240V AC isolated output module Simplified Schematic +5V

1756-OA161

L1-0 Isolated Wiring L1-0

OUT-0

L1-2

ControlLogix Backplane Interface

L1-4

Display Surge Current Chart Jumper Bar (Cut to Length)

20 A

Current

Nonisolated Wiring

Continuous @ 30 °C (86 °F)

2A 1A

Continuous @ 60 °C (140 °F) 0

L1

L1-0

2

1

OUT-0

L1-1

4

3

OUT-1

L1-2

6

5

OUT-2

L1-3

8

7

OUT-3

L1-4

10

9

OUT-4

L1-5

12 11

OUT-5

L1-6

14 13

OUT-6

L1-7

16 15

OUT-7

L1-8

18 17

OUT-8

L1-9

20 19

OUT-9

L1-10

22 21

OUT-10

L1-11

24 23

OUT-11

L1-12

26 25

OUT-12

L1-13 L1-14

28 27 30 29

OUT-13 OUT-14

L1-15

32 31

OUT-15

L1-15 Not Used

34 33

Not Used Not Used

36 35

AC OUTPUT Daisy Chain to Other RTBs

ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K

Additional jumper bars are available as catalog number 1756-JMPR.

Technical Specifications - 1756-OA16I Attribute

1756-OA16I

Outputs

16 individually isolated

Pilot duty

Yes

Voltage category

120/240V AC 50/60 Hz

Operating voltage range(1)

74…265V AC 47…63 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz

On to Off

9.3 ms @ 60 Hz 11 ms @ 50 Hz

Current draw @ 5.1V

300 mA

Current draw @ 24V

2.5 mA

Total backplane power

1.59 W

Power dissipation, max

5.5 W @ 60 °C (140 °F)

138

L2-2 L2-4

L2

43 ms Time

Output delay time Off to On

L2-0

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 139

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OA16I (continued) Attribute

1756-OA16I

Thermal dissipation

18.76 BTU/hr

Off-state leakage current, max

3 mA per point

On-state voltage drop, max

1.5V peak @ 2 A 6V peak @ load current < 50 mA

Current per point, max

2 A @ 30 °C (86 °F) linear derating 1 A @ 60 °C (140 °F) linear derating

Current per module, max

5 A @ 30 °C (86 °F) linear derating 4 A @ 60 °C (140 °F) linear derating

Surge current per point

20 A for 43 ms per point, repeatable every 2 s @ 60 °C (140 °F)

Load current, min

10 mA per point

Commutating voltage

4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(2)

Scheduled outputs

Synchronization within 16.7 s max, reference to the Coordinated System Time

States in Fault mode per point

Hold last state, On or Off (Off is default)

States in Program mode per point

Hold last state, On or Off (Off is default)

Isolation voltage

250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output Routine tested @ 1350V AC for 2 s

Inhibit voltage, max

Zero crossing 60V peak

Module keying

Electronic, software configurable

Fusing

Not protected. A fused IFM is recommended to help protect outputs

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(3)

North American temperature code

T4A

Enclosure type

None (open style)

(1) UL certification for 120/240V 50/60 Hz nominal. Rockwell Automation specified to 74…265V, 47…63 Hz. (2) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/s for loads under 50 mA. The commutating dv/dt rating of the module for loads 50…500 mA (OUTPUT to L2) is 4V/s maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 10…50 mA range, a resistor can be added AC across the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it dissipates (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50…500 mA range, the L1 AC waveform could be at fault. Be sure that the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-OA16I Attribute

1756-OA16I

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

139

Page 140

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-OA16I (continued) Attribute

1756-OA16I

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Oscillatory surge withstand IEEE C37.90.1

3 kV

Certifications - 1756-OA16I Certification(1)

1756-OA16I

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

140

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016