The text of a spec sheet · part 14 of 25
1756 ControlLogix I/O Specifications, Technical Data, pages 131 to 140
Pages 131 to 140 of 242
The original document is the PDF (7.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-IB16, Allen-Bradley 1756-OB16E and Allen-Bradley 1756-TBNH
Page 131
1756 ControlLogix I/O Specifications
1756-OA8E ControlLogix 120V AC electronically fused output module Simplified Schematic
1756-OA8E
Opto and Transformer Isolation
ControlLogix Backplane Interface
L1
VAC Short
2
1
4
3
6
5
8
7
10
9
12
11
14
13
16
15
18
17
20
19
Not Used
GATE
L2-0
L1-0
OUT L2
Group 0
OUT-0
L1-0
OUT-1
L1-0
Loss of Field Power
Display
OUT-2
L1-0
Surge Current Chart Daisy Chain to Other RTBs
Surge
20 A
OUT-3
L1-1
OUT-4
L1-1
OUT-5
Current
L1-1 Group 1
2A
OUT-6
L1-1
OUT-7
L1-1
0
Time
Group 0
Group 1
L2-1 L2
43 ms
Daisy Chain to Other RTBs L1
AC OUTPUT ST 0 1 2 3 4 5 6 7 O FUSE 0 1 2 3 4 5 6 7K
ELECTRONICALLY FUSED
Diagnostic Specifications - 1756-OA8E Attribute
1756-OA8E
Short trip, min
>20 A for 100 ms
Field power loss (zero cross)
Detects at 25V peak min (firmware phase locked loop)
Time stamp of diagnostics
±1 ms
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
131
Page 132
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OA8E Attribute
1756-OA8E
Outputs
Eight electronic fusing (four points/group)
Pilot duty
Yes
Voltage category Operating voltage range
120V AC 50/60 Hz (1)
Output delay time Off to On
74…132V AC 47…63 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz
On to Off
9.3 ms @ 60 Hz 11 ms @ 50 Hz
Current draw @ 5.1V
200 mA
Current draw @ 24V
250 mA
Total backplane power
7.02 W
Power dissipation, max
5.5 W @ 60 °C (140 °F)
Thermal dissipation
18.76 BTU/hr
Off-state leakage current, max
3 mA per point
On-state voltage drop, max
4V peak @ 2 A
Current per point, max
2 A @ 60 °C (140 °F)
Current per group, max
4 A @ 30 °C (86 °F) linear derating 2 A @ 60 °C (140 °F) linear derating
Current per module, max
8 A @ 30 °C (86 °F) linear derating 4 A @ 60 °C (140 °F) linear derating
Surge current per point
20 A for 43 ms per point, repeatable every 2 s @ 60 °C (140 °F)
Load current, min
10 mA per point
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (default is Off)
States in Program mode per point
Hold last state, On or Off (default is Off)
Isolation voltage
125V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1200V AC for 2 s
Inhibit voltage, max
Zero crossing 25V peak
Module keying
Electronic, software configurable
Fusing
Electronically fused per point
Removable terminal block
1756-TBNH 1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(2)
North American temperature code
T4A
Enclosure type
None (open style)
(1) UL certification for 120V 50/60Hz nominal. Rockwell Automation specified to 74…132V, 47…63 Hz. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
132
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 133
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OA8E Attribute
1756-OA8E
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1k V line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-OA8E Certification(1)
1756-OA8E
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
133
Page 134
1756 ControlLogix I/O Specifications
1756-OA16 ControlLogix 120/240V AC output module 1756-OA16
Simplified Schematic ControlLogix Backplane Interface
L1-0 2
1
4
3
6
5
8
7
10
9
12
11
14
13
16
15
18
17
OUT-1
+5V
Group 0
L2-0
(Fused per Group) Display
Daisy Chain to Other RTBs
OUT-0
OUT-3
OUT-2
OUT-5 OUT-7
OUT-6
L1-0 OUT-0
L2-0
OUT-9
OUT-8
ControlLogix Backplane Interface
OUT-11 Group 1
Surge Current Chart
OUT-10
OUT-13
OUT-12
L1
OUT-15
Current
OUT-14
Per Group
Surge
20
20 A
L2-1
Per Group
0
43 ms
L1
Time
AC OUTPUT ST 0 1 2 3 4 5 6 7 FUSE ST 8 9 10 11 12 13 14 15
O K
FUSE
Diagnostic Specifications - 1756-OA16 Attribute
1756-OA16
Time stamp of diagnostics
±1 ms
Fuse blown
One fuse and indicator/group
134
19
L1-1
5A 2A 500 mA
Group 0
OUT-4
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
L2
Group 1
Page 135
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OA16 Attribute
1756-OA16
Outputs
16 mechanically fused/group (8 points/group)
Pilot duty
0.5 A
Voltage category
120/240V AC 50/60 Hz
Operating voltage range(1)
74…265V AC 47…63 Hz
Output delay time Off to On
9.3 ms @ 60 Hz 11 ms @ 50 Hz
On to Off
9.3 ms @ 60 Hz 11 ms @ 50 Hz
Current draw @ 5.1V
400 mA
Current draw @ 24V
2 mA
Total backplane power
2.1 W
Power dissipation, max
6.5 W @ 60 °C (140 °F)
Thermal dissipation
22.17 BTU/hr
Off-state leakage current, max
3 mA per point
On-state voltage drop, max
1.5V @ 0.5 A 5.7V @ load current < 50 mA
Current per point, max
0.5 A @ 60 °C (140 °F)
Current per group, max
2 A @ 60 °C (140 °F)
Current per module, max
4 A @ 60 °C (140 °F)
Surge current per point
5 A for 43 ms per point, repeatable every 2 s @ 60 °C (140 °F)
Surge current per group
15 A for 43 ms per point, repeatable every 2 s @ 60 °C (140 °F)
Load current, min
10 mA per point
Commutating voltage
4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(2)
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1400V AC for 2 s
Inhibit voltage, max
Zero crossing 60V peak
Module keying
Electronic, software configurable
Fusing
Mechanically fused/group, 3.15 A @ 250V AC slow blow, 1500 A interruption current, Littelfuse p/n H2153.15
Removable terminal block
1756-TBNH 1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
135
Page 136
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OA16 (continued) Attribute
1756-OA16
Wire category
1(3)
North American temperature code
T4
Enclosure type
None (open style)
(1) UL certification for 120/240V 50/60 Hz nominal. Rockwell Automation specified to 74…265V, 47…63 Hz. (2) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/s for loads under 50 mA. The commutating dv/dt rating of the module for loads 50…500 mA (OUTPUT to L2) is 4V/s maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 10…50 mA range, a resistor can be added AC across the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it dissipates (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50…500 mA range, the L1 AC waveform could be at fault. Be sure that the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-OA16 Attribute
1756-OA16
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Oscillatory surge withstand IEEE C37.90.1
3 kV
136
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 137
1756 ControlLogix I/O Specifications
Certifications - 1756-OA16 Certification(1)
1756-OA16
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
137
Page 138
1756 ControlLogix I/O Specifications
1756-OA16I ControlLogix 120/240V AC isolated output module Simplified Schematic +5V
1756-OA161
L1-0 Isolated Wiring L1-0
OUT-0
L1-2
ControlLogix Backplane Interface
L1-4
Display Surge Current Chart Jumper Bar (Cut to Length)
20 A
Current
Nonisolated Wiring
Continuous @ 30 °C (86 °F)
2A 1A
Continuous @ 60 °C (140 °F) 0
L1
L1-0
2
1
OUT-0
L1-1
4
3
OUT-1
L1-2
6
5
OUT-2
L1-3
8
7
OUT-3
L1-4
10
9
OUT-4
L1-5
12 11
OUT-5
L1-6
14 13
OUT-6
L1-7
16 15
OUT-7
L1-8
18 17
OUT-8
L1-9
20 19
OUT-9
L1-10
22 21
OUT-10
L1-11
24 23
OUT-11
L1-12
26 25
OUT-12
L1-13 L1-14
28 27 30 29
OUT-13 OUT-14
L1-15
32 31
OUT-15
L1-15 Not Used
34 33
Not Used Not Used
36 35
AC OUTPUT Daisy Chain to Other RTBs
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K
Additional jumper bars are available as catalog number 1756-JMPR.
Technical Specifications - 1756-OA16I Attribute
1756-OA16I
Outputs
16 individually isolated
Pilot duty
Yes
Voltage category
120/240V AC 50/60 Hz
Operating voltage range(1)
74…265V AC 47…63 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz
On to Off
9.3 ms @ 60 Hz 11 ms @ 50 Hz
Current draw @ 5.1V
300 mA
Current draw @ 24V
2.5 mA
Total backplane power
1.59 W
Power dissipation, max
5.5 W @ 60 °C (140 °F)
138
L2-2 L2-4
L2
43 ms Time
Output delay time Off to On
L2-0
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 139
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OA16I (continued) Attribute
1756-OA16I
Thermal dissipation
18.76 BTU/hr
Off-state leakage current, max
3 mA per point
On-state voltage drop, max
1.5V peak @ 2 A 6V peak @ load current < 50 mA
Current per point, max
2 A @ 30 °C (86 °F) linear derating 1 A @ 60 °C (140 °F) linear derating
Current per module, max
5 A @ 30 °C (86 °F) linear derating 4 A @ 60 °C (140 °F) linear derating
Surge current per point
20 A for 43 ms per point, repeatable every 2 s @ 60 °C (140 °F)
Load current, min
10 mA per point
Commutating voltage
4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(2)
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output Routine tested @ 1350V AC for 2 s
Inhibit voltage, max
Zero crossing 60V peak
Module keying
Electronic, software configurable
Fusing
Not protected. A fused IFM is recommended to help protect outputs
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(3)
North American temperature code
T4A
Enclosure type
None (open style)
(1) UL certification for 120/240V 50/60 Hz nominal. Rockwell Automation specified to 74…265V, 47…63 Hz. (2) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/s for loads under 50 mA. The commutating dv/dt rating of the module for loads 50…500 mA (OUTPUT to L2) is 4V/s maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 10…50 mA range, a resistor can be added AC across the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it dissipates (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50…500 mA range, the L1 AC waveform could be at fault. Be sure that the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-OA16I Attribute
1756-OA16I
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
139
Page 140
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OA16I (continued) Attribute
1756-OA16I
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Oscillatory surge withstand IEEE C37.90.1
3 kV
Certifications - 1756-OA16I Certification(1)
1756-OA16I
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
140
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016