Page 141
1756 ControlLogix I/O Specifications
1756-OB8 ControlLogix DC (10…30V) output module 1756-OB8
Simplified Schematic
Daisy Chain to Other RTBs
DC-0(+) +5V
2
1
4
3
6
5
8
7
10
9
12
11
14
13
16
15
DC-0 (+)
OUT-0 Group 0
OUT-0
DC-0 (+)
OUT-1
DC-0 (+)
RTN OUT-0
ControlLogix Backplane Interface
OUT-2
DC-0 (+)
OUT-3
Display RTN OUT-0
RTN OUT-0
Surge Current Chart DC-1 (+)
OUT-4
Surge
4A
DC-1 (+)
OUT-5
Current
Group 1
Continuous @ 60 °C (140 °F)
Group 1
DC-1 (+)
OUT-6
2A
18
17
20
19
DC-1 (+)
OUT-7
RTN OUT-1
0
Group 0
RTN OUT-1
10 ms Daisy Chain to Other RTBs
Time
+
DC OUTPUT
– DC COM
ST 0 1 2 3 4 5 6 7 O K
Technical Specifications - 1756-OB8 Attribute
1756-OB8
Outputs
8 (4 points/common)
Pilot duty
Yes
Voltage category
12/24V DC source
Operating voltage range
10…30V DC
Output delay time Off to On On to Off
1 ms max 2 ms max
Current draw @ 5.1V
165 mA
Current draw @ 24V
2 mA
Total backplane power
0.89 W
Power dissipation, max
2.5 W @ 60 °C (140 °F)
Thermal dissipation
8.53 BTU/hr
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
141
Page 142
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OB8 (continued) Attribute
1756-OB8
Off-state leakage current, max
1 mA per point
On-state voltage drop, max
1.2V DC @ 2 A
Current per point, max
2 A @ 60 °C (140 °F)
Current per module, max
8 A @ 60 °C (140 °F)
Surge current per point
4 A for 10 ms each, repeatable every 1 s @ 60 °C (140 °F)
Load current, min
2 mA per point
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Fusing
Not protected. A fused IFM is recommended to help protect outputs
Removable terminal block
1756-TBNH 1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
North American temperature code
T4A
IEC temperature code
T4
Enclosure type
None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-OB8 Attribute
1756-OB8
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
142
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 143
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OB8 (continued) Attribute
1756-OB8
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-OB8 Certification(1)
1756-OB8
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
143
Page 144
1756 ControlLogix I/O Specifications
1756-OB8EI ControlLogix DC (10…30V) electronically fused, isolated output module Simplified Schematic
+5V
1756-OB8EI DC-0(+) +
OUT-0
+
OUT-0 Display ControlLogix Backplane Interface
Nonisolated Wiring
Surge Current Chart Surge
4A
Current
-
RTN OUT-0
Output Device
Daisy Chain to Other RTBs
Continuous @ 60 °C (140 °F) 2A Daisy Chain to Other RTBs
0
-
Isolated Wiring
DC-0 (+)
2
1
OUT-0
RTN OUT-0
4
3
OUT-0
DC-1 (+)
6
5
OUT-1
RTN OUT-1
8
7
OUT-1
DC-2 (+)
10
9
OUT-2
RTN OUT-2
12 11
OUT-2
DC-3 (+)
14 13
OUT-3
RTN OUT-3
16 15
OUT-3
DC-4 (+)
18 17
OUT-4
RTN OUT-4
20 19
DC-5 (+)
22 21
OUT-4 OUT-5
RTN OUT-5
24 23
OUT-5
DC-6 (+)
26 25
OUT-6
RTN OUT-6
28 27
OUT-6
DC-7 (+)
30 29
OUT-7
RTN OUT-7
32 31
OUT-7
Not Used
34 33
Not Used
Not Used
36 35
Not Used
10 ms Time +
DC OUTPUT
– DC COM
ST 0 1 2 3 4 5 6 7 O FUSE 0 1 2 3 4 5 6 7 K
ELECTRONICALLY FUSED
Diagnostic Specifications - 1756-OB8EI Attribute
1756-OB8EI
Short trip
> 4.5 A for 500 s max (output on, then short) > 4.5 A for 1.5 ms max (output on into short)
Time stamp of diagnostics
±1 ms
=
Technical Specifications - 1756-OB8EI Attribute
1756-OB8EI
Outputs
8 individually isolated
Pilot duty
Yes
Voltage category
12/24V DC source
Operating voltage range
10…30V DC
144
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 145
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OB8EI (continued) Attribute
1756-OB8EI
Output delay time Off to On On to Off
1 ms max 5 ms max
Current draw @ 5.1V
250 mA
Current draw @ 24V
2 mA
Total backplane power
1.30 W
Power dissipation, max
4.7 W @ 60 °C (140 °F)
Thermal dissipation
16.03 BTU/hr
Off-state leakage current, max
1 mA per point
On-state voltage drop, max
1.2V DC @ 2 A
Current per point, max
2 A @ 60 °C (140 °F)
Current per module, max
10 A @ 60 °C (140 °F) 16 A @ 55 °C (131 °F) linear derating
Surge current per point
4 A for 10 ms each, repeatable every 2 s
Load current, min
3 mA
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Fusing
Electronically fused per point
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
North American temperature code
T4A
IEC temperature code
T4
Enclosure type
None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-OB8EI Attribute
1756-OB8EI
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
145
Page 146
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OB8EI (continued) Attribute
1756-OB8EI
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-OB8EI Certification(1)
1756-OB8EI
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
146
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 147
1756 ControlLogix I/O Specifications
1756-OB8I ControlLogix DC (10…30V) isolated output module 1756-OB8I
Simplified Schematic
+5V
DC-0(+)
Isolated Wiring
OUT-0 OUT-0 Display
RTN OUT-0
Output Device
ControlLogix Backplane Interface
Surge Current Chart Surge
Current
4A
Nonisolated Wiring
Continuous @ 60 °C (140 °F) 2A
0
Daisy Chain to Other RTBs
Daisy Chain to Other RTBs
DC-0 (+) RTN OUT-0 DC-1 (+) RTN OUT-1 DC-2 (+) RTN OUT-2 DC-3 (+) RTN OUT-3 DC-4 (+) RTN OUT-4 DC-5 (+) RTN OUT-5 DC-6 (+) RTN OUT-6 DC-7 (+) RTN OUT-7 Not Used Not Used
2 1 4 3 6 5 8 7 10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
OUT-0 OUT-0 OUT-1 OUT-1 OUT-2 OUT-2 OUT-3 OUT-3 OUT-4 OUT-4 OUT-5 OUT-5 OUT-6 OUT-6 OUT-7 OUT-7 Not Used Not Used
10 ms Time
DC OUTPUT ST
01234567 O K
Technical Specifications - 1756-OB8I Attribute
1756-OB8I
Outputs
8 individually isolated
Pilot duty
Yes
Voltage category
12/24V DC source
Operating voltage range
10…30V DC
Output delay time Off to On On to Off
1 ms max 2 ms max
Current draw @ 5.1V
165 mA
Current draw @ 24V
2 mA
Total backplane power
0.89 W
Power dissipation, max
4.6 W @ 60 °C (140 °F)
Thermal dissipation
15.70 BTU/hr
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
147
Page 148
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OB8I (continued) Attribute
1756-OB8I
Off-state leakage current, max
0.5 mA per point
On-state voltage drop, max
0.5V DC @ 2 A
Current per point, max
2 A @ 60 °C (140 °F)
Current per module, max
16 A @ 60 °C (140 °F)
Surge current per point
4 A for 10 ms each, repeatable every 1 s @ 60 °C (140 °F)
Load current, min
2 mA
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), reinforced insulation type, outputs-to-backplane 250V (continuous), basic insulation type, output-to-output Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Fusing
Not protected. A fused IFM is recommended to help protect outputs.
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
North American temperature code
T4A
Enclosure type
None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-OB8I Attribute
1756-OB8I
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8k V air discharges
148
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 149
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OB8I (continued) Attribute
1756-OB8I
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1k Hz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-OB8I Certification(1)
1756-OB8I
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
149
Page 150
1756 ControlLogix I/O Specifications
1756-OB16D ControlLogix DC (19.2…30V) diagnostic output module Simplified Schematic +5V +5V
1756-OB16D
+ DC
Short Circuit Detect Optoisolation
Daisy Chain to Other RTBs
+5V
OUT ControlLogix Backplane Interface
Group 0
RTN Display
Output Verify/No Load Surge Current Chart
Surge
Current
4A
Continuous @ 30 °C (86 °F)
2A
Group 1
Continuous @ 60 °C (140 °F)
0
+DC-0
2
1
OUT-0
+DC-0
4
3
OUT-1
+DC-0
6
5
OUT-2
+DC-0
8
7
OUT-3
+DC-0
10
9
OUT-4
+DC-0
12
11
OUT-5
+DC-0
14
13
OUT-6
GND-0
16
15
OUT-7
+DC-1
18
17
OUT-8
+DC-1 +DC-1
20
19
OUT-9
22
21
OUT-10
+DC-1
24
23
OUT-11
+DC-1
26
25
OUT-12
+DC-1
28
27
OUT-13
+DC-1
30
29
OUT-14
GND-1
32
31
OUT-15
GND-1
34
33
Not Used
Not Used
36
35
Not Used
Daisy Chain to Other RTBs
10 ms Time
+
DC OUTPUT ST 0 1 2 3 4 5 6 7 O FLT 0 1 2 3 4 5 6 7 K ST 8 9 10 11 12 13 14 15 FLT 8 9 10 11 12 13 14 15 DIAGNOSTIC
Diagnostic Specifications - 1756-OB16D Attribute
1756-OB16D
Short trip
8 A for 180 ms, min 10 A for 120 ms, min
No load
Off-state detection only
Output verification
On-state detection only
Pulse test
Configurable maximum pulse width
Time stamp of diagnostics
±1 ms
150
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
– DC COM
Group 0
Group 1