The text of a spec sheet · part 16 of 25
1756 ControlLogix I/O Specifications, Technical Data, pages 151 to 160
Pages 151 to 160 of 242
The original document is the PDF (7.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-IB16, Allen-Bradley 1756-OB16E and Allen-Bradley 1756-TBNH
Page 151
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OB16D Attribute
1756-OB16D
Outputs
16 diagnostic (8 points/group)
Pilot duty
2 A (DC-13SQ)
Voltage category
24V DC source
Operating voltage range
19.2…30V DC
Output delay time Off to On On to Off
60 s nom/1 ms max 630 s nom/5 ms max
Current draw @ 5.1V
250 mA
Current draw @ 24V
140 mA
Total backplane power
4.64 W
Power dissipation, max
3.3 W @ 60 °C (140 °F)
Thermal dissipation
11.25 BTU/hr
Off-state leakage current per point, max
1 mA per point
On-state voltage drop, max
1.2V DC @ 2 A
Current per point, max
2 A @ 30 °C (86 °F) linear derating 1 A @ 60 °C (140 °F) linear derating
Current per module, max
8 A @ 30 °C (86 °F) linear derating 4 A @ 60 °C (140 °F) linear derating
Surge current per point
4 A for 10 ms per point, repeatable every 1 s
Load current, min
3 mA per point
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Fusing
Electronically fused per point
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
North American temperature code
T4A
IEC temperature code
T4
Enclosure type
None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
151
Page 152
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OB16D Attribute
1756-OB16D
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1k Hz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-OB16D Certification(1)
1756-OB16D
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
152
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 153
1756 ControlLogix I/O Specifications
1756-OB16E ControlLogix DC (10…31.2V) electronically fused output module 1756-OB16E
Simplified Schematic Display
Optoisolation
DC-0(+)
2
1
4
3
6
5
8
7
10
9
12
11
14
13
16
15
18
17
OUT-0
OUT-1 Group 0 OUT-0 ControlLogix Backplane Interface
Daisy Chain to Other RTBs
RTN OUT-0
Electronic Fuse Circuitry
OUT-3
OUT-2
OUT-5
OUT-4 OUT-6
OUT-7
RTN OUT-0
DC-0(+)
OUT-8
OUT-9 OUT-11
DC OUTPUT
OUT-10 OUT-12
OUT-13
ST 0 1 2 3 4 5 6 7 O K ST 8 9 10 11 12 13 14 15
Group 1
FUSE
Group 1 OUT-14
OUT-15 20
FUSE ELECTRONICALLY FUSED
Group 0
19
DC-1(+)
RTN OUT-1
+
– DC COM
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
153
Page 154
1756 ControlLogix I/O Specifications
Surge Current Charts
Technical Specifications - 1756-OB16E Attribute
1756-OB16E
Outputs
16 electronically fused (8 points/group)
Voltage category
12/24V DC source
Operating voltage range
10…31.2V DC
Output delay time Off to On On to Off
70 s nom/1 ms max 360 s nom/1 ms max
Current draw @ 5.1V
250 mA
Current draw @ 24V
2 mA
Total backplane power
1.32 W
Power dissipation, max
4.1 W @ 60 °C (140 °F)
Thermal dissipation
13.98 BTU/hr
154
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 155
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OB16E (continued) Attribute
1756-OB16E
Off-state leakage current per point, max
1 mA per point
On-state voltage drop, max
400 mV DC @ 1 A
Current per point, max
1 A @ 60 °C (140 °F)
Current per module, max
8 A @ 60 °C (140 °F)
Surge current per point, typical
2 A for 10 ms per point, repeatable every 2 s @ 0 °C (32 °F) @ 24V DC
Load current, min
3 mA per point
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Fusing
Electronically fused per group
Removable terminal block
1756-TBNH 1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
North American temperature code
T4
IEC temperature code
T4
Enclosure type
None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-OB16E Attribute
1756-OB16E
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
155
Page 156
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OB16E (continued) Attribute
1756-OB16E
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Oscillatory surge withstand IEEE C37.90.1
3 kV
Certifications - 1756-OB16E Certification(1)
1756-OB16E
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
156
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 157
1756 ControlLogix I/O Specifications
1756-OB16I ControlLogix 24V DC isolated output module 1756-OB16I
Simplified Schematic DC-0(+)
Isolated Sourcing Output Wiring
Isolated Wiring DC-0 (+)
DC-0 (+)
+5V DC-2 (+)
OUT-0
DC-6 (+)
ControlLogix Backplane Interface Display
Current
+
Jumper Bar (Cut to Length)
Surge Current Chart
Nonisolated Wiring
Surge
4A
Sinking Output Wiring
Continuous @ 30 °C (86 °F)
2A
DC(+)
–
1
OUT-0
4
3
OUT-1
6
5
OUT-2
DC-3 (+)
8
7
OUT-3
DC-4 (+)
10
9
OUT-4
DC-5 (+)
12
11
OUT-5
DC-6 (+)
14
13
OUT-6
DC-7 (+)
16
15
OUT-7
DC-8 (+)
18
17
OUT-8
DC-9 (+)
20
19
OUT-9
DC-10 (+)
22
21
OUT-10
DC-11 (+)
24
23
OUT-11
DC-12 (+)
26
25
OUT-12
DC-13 (+)
28
27
DC-14 (+)
30
29
OUT-13 OUT-14
DC-15 (+)
32
31
OUT-15
DC-15 (+) Not Used
34
33
36
35
Not Used Not Used
DC-1 (+) DC-2 (+)
2
Continuous @ 60 °C (140 °F)
1A
DC-0 (-) DC-2 (-)
DC-6 (-)
Nonisolated Sourcing Output Wiring
DC(-)
Daisy Chain to Other RTBs
0
10 ms Time Additional jumper bars are available as catalog number 1756-JMPR.
DC OUTPUT ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K
Technical Specifications - 1756-OB16I Attribute
1756-OB16I
Outputs
16 individually isolated
Pilot duty
2 A (DC-13SQ)
Voltage category
12/24V DC sink/source
Operating voltage range(1)
10…30V DC
Output delay time Off to On On to Off
1 ms max 2 ms max
Current draw @ 5.1V
350 mA
Current draw @ 24V
2.5 mA
Total backplane power
1.8 W
Power dissipation, max
3.6 W @ 60 °C (140 °F)
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
157
Page 158
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OB16I (continued) Attribute
1756-OB16I
Thermal dissipation
12.28 BTU/hr
Off-state leakage current per point, max
0.5 mA per point
On-state voltage drop, max
1.2V DC @ 2 A
Current per point, max
2 A @ 30 °C (86 °F) 1 A @ 60 °C (140 °F) (linear derating)
Current per module, max
8 A @ 30 °C (86 °F) 4 A @ 60 °C (140 °F) (linear derating)
Surge current per point
4 A for 10 ms per point, repeatable every 2 s
Load current, min
1 mA per point
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane 125V (continuous), basic insulation type, output-to-output Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Fusing
Not protected. A fused IFM is recommended to help protect outputs.
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(2)
North American temperature code
T4A
IEC temperature code
T4
Enclosure type
None (open-style)
(1) UL certification for 24V DC nominal. Rockwell Automation specified to 10…30V DC. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-OB16I Attribute
1756-OB16I
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
158
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 159
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OB16I (continued) Attribute
1756-OB16I
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-OB16I Certification(1)
1756-OB16I
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
159
Page 160
1756 ControlLogix I/O Specifications
1756-OB16IEF ControlLogix DC (10…30V) electronically protected, sinking or sourcing, isolated, fast output module 1756-OB16IEF
Simplified Schematic DC-0(+)
DC-0 (+)
DC-0 (+) DC-1 (+)
2
1
OUT-0
4
3
OUT-1
DC-2 (+)
DC-2 (+)
6
5
OUT-2
DC-3 (+)
8
7
OUT-3
DC-4 (+)
10
9
OUT-4
DC-5 (+)
12
11
OUT-5
DC-6 (+)
14
13
OUT-6
DC-7 (+)
16
15
OUT-7
DC-8 (+)
18
17
OUT-8
DC-9 (+)
20
19
OUT-9
DC-10 (+)
22
21
OUT-10
DC-11 (+)
24
23
OUT-11
DC-12 (+)
26
25
OUT-12
DC-13 (+) DC-14 (+)
28
27
30
29
OUT-13 OUT-14
DC-15 (+)
32
31
OUT-15
DC-15 (+) Not Used
34
33
36
35
Not Used Not Used
Isolator
OUT-0
Sinking Output Wiring DC-6 (+)
Fault Display
ControlLogix Backplane Interface
Jumper Bar (Cut to Length)
Surge Current Chart
Current
Nonisolated Wiring
Surge
4A
Isolated Sourcing Output Wiring
Isolated Wiring
Continuous 2 A @ 45 °C (113 °F) 2A
DC(+)
+
–
Continuous 1 A @ 60 °C (140 °F)
1A
Daisy Chain to Other RTBs
0
10 ms Time
Additional jumper bars can be purchased by using catalog number 1756-JMPR.
DC OUTPUT ST DIAG
01 2 3 4 56 7 01 2 3 4 5 6 7
ST DIAG
8 9 10 11 12 13 14 15 8 9 10 11 12 13 14 15
O K
PEER DEVICE
Technical Specifications - 1756-OB16IEF Attribute
1756-OB16IEF
Outputs
16 individually isolated
Pilot duty
4 A inrush
Voltage category
12/24V DC sink/source
Operating voltage range
10…30V DC
Output delay time (backplane to screw) Off to On On to Off
14 μs nom/23 μs max 14 μs nom/23 μs max
PWM cycle time
1 ms min/1 hour max
PWM On time
200 μs min/1 hour max
PWM On time accuracy
± 20 μs
Current draw @ 5.1V
320 mA
160
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
DC-0 (-) DC-2 (-)
DC-6 (-)
Nonisolated Sourcing Output Wiring
DC(-)