Page 151

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OB16D Attribute

1756-OB16D

Outputs

16 diagnostic (8 points/group)

Pilot duty

2 A (DC-13SQ)

Voltage category

24V DC source

Operating voltage range

19.2…30V DC

Output delay time Off to On On to Off

60 s nom/1 ms max 630 s nom/5 ms max

Current draw @ 5.1V

250 mA

Current draw @ 24V

140 mA

Total backplane power

4.64 W

Power dissipation, max

3.3 W @ 60 °C (140 °F)

Thermal dissipation

11.25 BTU/hr

Off-state leakage current per point, max

1 mA per point

On-state voltage drop, max

1.2V DC @ 2 A

Current per point, max

2 A @ 30 °C (86 °F) linear derating 1 A @ 60 °C (140 °F) linear derating

Current per module, max

8 A @ 30 °C (86 °F) linear derating 4 A @ 60 °C (140 °F) linear derating

Surge current per point

4 A for 10 ms per point, repeatable every 1 s

Load current, min

3 mA per point

Scheduled outputs

Synchronization within 16.7 s max, reference to the Coordinated System Time

States in Fault mode per point

Hold last state, On or Off (Off is default)

States in Program mode per point

Hold last state, On or Off (Off is default)

Isolation voltage

250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Fusing

Electronically fused per point

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(1)

North American temperature code

T4A

IEC temperature code

T4

Enclosure type

None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

151

Page 152

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-OB16D Attribute

1756-OB16D

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1k Hz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-OB16D Certification(1)

1756-OB16D

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

152

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 153

1756 ControlLogix I/O Specifications

1756-OB16E ControlLogix DC (10…31.2V) electronically fused output module 1756-OB16E

Simplified Schematic Display

Optoisolation

DC-0(+)

2

1

4

3

6

5

8

7

10

9

12

11

14

13

16

15

18

17

OUT-0

OUT-1 Group 0 OUT-0 ControlLogix Backplane Interface

Daisy Chain to Other RTBs

RTN OUT-0

Electronic Fuse Circuitry

OUT-3

OUT-2

OUT-5

OUT-4 OUT-6

OUT-7

RTN OUT-0

DC-0(+)

OUT-8

OUT-9 OUT-11

DC OUTPUT

OUT-10 OUT-12

OUT-13

ST 0 1 2 3 4 5 6 7 O K ST 8 9 10 11 12 13 14 15

Group 1

FUSE

Group 1 OUT-14

OUT-15 20

FUSE ELECTRONICALLY FUSED

Group 0

19

DC-1(+)

RTN OUT-1

+

– DC COM

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

153

Page 154

1756 ControlLogix I/O Specifications

Surge Current Charts

Technical Specifications - 1756-OB16E Attribute

1756-OB16E

Outputs

16 electronically fused (8 points/group)

Voltage category

12/24V DC source

Operating voltage range

10…31.2V DC

Output delay time Off to On On to Off

70 s nom/1 ms max 360 s nom/1 ms max

Current draw @ 5.1V

250 mA

Current draw @ 24V

2 mA

Total backplane power

1.32 W

Power dissipation, max

4.1 W @ 60 °C (140 °F)

Thermal dissipation

13.98 BTU/hr

154

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 155

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OB16E (continued) Attribute

1756-OB16E

Off-state leakage current per point, max

1 mA per point

On-state voltage drop, max

400 mV DC @ 1 A

Current per point, max

1 A @ 60 °C (140 °F)

Current per module, max

8 A @ 60 °C (140 °F)

Surge current per point, typical

2 A for 10 ms per point, repeatable every 2 s @ 0 °C (32 °F) @ 24V DC

Load current, min

3 mA per point

Scheduled outputs

Synchronization within 16.7 s max, reference to the Coordinated System Time

States in Fault mode per point

Hold last state, On or Off (Off is default)

States in Program mode per point

Hold last state, On or Off (Off is default)

Isolation voltage

250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Fusing

Electronically fused per group

Removable terminal block

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(1)

North American temperature code

T4

IEC temperature code

T4

Enclosure type

None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-OB16E Attribute

1756-OB16E

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

155

Page 156

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-OB16E (continued) Attribute

1756-OB16E

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Oscillatory surge withstand IEEE C37.90.1

3 kV

Certifications - 1756-OB16E Certification(1)

1756-OB16E

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

156

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 157

1756 ControlLogix I/O Specifications

1756-OB16I ControlLogix 24V DC isolated output module 1756-OB16I

Simplified Schematic DC-0(+)

Isolated Sourcing Output Wiring

Isolated Wiring DC-0 (+)

DC-0 (+)

+5V DC-2 (+)

OUT-0

DC-6 (+)

ControlLogix Backplane Interface Display

Current

+

Jumper Bar (Cut to Length)

Surge Current Chart

Nonisolated Wiring

Surge

4A

Sinking Output Wiring

Continuous @ 30 °C (86 °F)

2A

DC(+)

–

1

OUT-0

4

3

OUT-1

6

5

OUT-2

DC-3 (+)

8

7

OUT-3

DC-4 (+)

10

9

OUT-4

DC-5 (+)

12

11

OUT-5

DC-6 (+)

14

13

OUT-6

DC-7 (+)

16

15

OUT-7

DC-8 (+)

18

17

OUT-8

DC-9 (+)

20

19

OUT-9

DC-10 (+)

22

21

OUT-10

DC-11 (+)

24

23

OUT-11

DC-12 (+)

26

25

OUT-12

DC-13 (+)

28

27

DC-14 (+)

30

29

OUT-13 OUT-14

DC-15 (+)

32

31

OUT-15

DC-15 (+) Not Used

34

33

36

35

Not Used Not Used

DC-1 (+) DC-2 (+)

2

Continuous @ 60 °C (140 °F)

1A

DC-0 (-) DC-2 (-)

DC-6 (-)

Nonisolated Sourcing Output Wiring

DC(-)

Daisy Chain to Other RTBs

0

10 ms Time Additional jumper bars are available as catalog number 1756-JMPR.

DC OUTPUT ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

Technical Specifications - 1756-OB16I Attribute

1756-OB16I

Outputs

16 individually isolated

Pilot duty

2 A (DC-13SQ)

Voltage category

12/24V DC sink/source

Operating voltage range(1)

10…30V DC

Output delay time Off to On On to Off

1 ms max 2 ms max

Current draw @ 5.1V

350 mA

Current draw @ 24V

2.5 mA

Total backplane power

1.8 W

Power dissipation, max

3.6 W @ 60 °C (140 °F)

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

157

Page 158

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OB16I (continued) Attribute

1756-OB16I

Thermal dissipation

12.28 BTU/hr

Off-state leakage current per point, max

0.5 mA per point

On-state voltage drop, max

1.2V DC @ 2 A

Current per point, max

2 A @ 30 °C (86 °F) 1 A @ 60 °C (140 °F) (linear derating)

Current per module, max

8 A @ 30 °C (86 °F) 4 A @ 60 °C (140 °F) (linear derating)

Surge current per point

4 A for 10 ms per point, repeatable every 2 s

Load current, min

1 mA per point

Scheduled outputs

Synchronization within 16.7 s max, reference to the Coordinated System Time

States in Fault mode per point

Hold last state, On or Off (Off is default)

States in Program mode per point

Hold last state, On or Off (Off is default)

Isolation voltage

250V (continuous), basic insulation type, outputs-to-backplane 125V (continuous), basic insulation type, output-to-output Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Fusing

Not protected. A fused IFM is recommended to help protect outputs.

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(2)

North American temperature code

T4A

IEC temperature code

T4

Enclosure type

None (open-style)

(1) UL certification for 24V DC nominal. Rockwell Automation specified to 10…30V DC. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-OB16I Attribute

1756-OB16I

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

158

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 159

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-OB16I (continued) Attribute

1756-OB16I

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-OB16I Certification(1)

1756-OB16I

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

159

Page 160

1756 ControlLogix I/O Specifications

1756-OB16IEF ControlLogix DC (10…30V) electronically protected, sinking or sourcing, isolated, fast output module 1756-OB16IEF

Simplified Schematic DC-0(+)

DC-0 (+)

DC-0 (+) DC-1 (+)

2

1

OUT-0

4

3

OUT-1

DC-2 (+)

DC-2 (+)

6

5

OUT-2

DC-3 (+)

8

7

OUT-3

DC-4 (+)

10

9

OUT-4

DC-5 (+)

12

11

OUT-5

DC-6 (+)

14

13

OUT-6

DC-7 (+)

16

15

OUT-7

DC-8 (+)

18

17

OUT-8

DC-9 (+)

20

19

OUT-9

DC-10 (+)

22

21

OUT-10

DC-11 (+)

24

23

OUT-11

DC-12 (+)

26

25

OUT-12

DC-13 (+) DC-14 (+)

28

27

30

29

OUT-13 OUT-14

DC-15 (+)

32

31

OUT-15

DC-15 (+) Not Used

34

33

36

35

Not Used Not Used

Isolator

OUT-0

Sinking Output Wiring DC-6 (+)

Fault Display

ControlLogix Backplane Interface

Jumper Bar (Cut to Length)

Surge Current Chart

Current

Nonisolated Wiring

Surge

4A

Isolated Sourcing Output Wiring

Isolated Wiring

Continuous 2 A @ 45 °C (113 °F) 2A

DC(+)

+

–

Continuous 1 A @ 60 °C (140 °F)

1A

Daisy Chain to Other RTBs

0

10 ms Time

Additional jumper bars can be purchased by using catalog number 1756-JMPR.

DC OUTPUT ST DIAG

01 2 3 4 56 7 01 2 3 4 5 6 7

ST DIAG

8 9 10 11 12 13 14 15 8 9 10 11 12 13 14 15

O K

PEER DEVICE

Technical Specifications - 1756-OB16IEF Attribute

1756-OB16IEF

Outputs

16 individually isolated

Pilot duty

4 A inrush

Voltage category

12/24V DC sink/source

Operating voltage range

10…30V DC

Output delay time (backplane to screw) Off to On On to Off

14 μs nom/23 μs max 14 μs nom/23 μs max

PWM cycle time

1 ms min/1 hour max

PWM On time

200 μs min/1 hour max

PWM On time accuracy

± 20 μs

Current draw @ 5.1V

320 mA

160

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

DC-0 (-) DC-2 (-)

DC-6 (-)

Nonisolated Sourcing Output Wiring

DC(-)