Page 161
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OB16IEF (continued) Attribute
1756-OB16IEF
Current draw @ 24V
3 mA
Total backplane power
1.7 W
Power dissipation
4.9 W max (16 channels @ 1 A or 4 channels @ 2 A)
Thermal dissipation
16.71 BTU/hr
Off-state leakage current per point, max
< 0.1 mA per point
On-state voltage drop, max
0.2V DC @ 1 A 0.4V DC @ 2 A
Current per point, max
2 A @ 45 °C (113 °F) 4 channels max 1 A @ 60 °C (140 °F)
Current per module, max
16 A @ 60 °C (140 °F) 1 A max per channel 8 A @ 45 °C (113 °F) 2 A max per channel
Surge current per point
4 A for 10 ms per point, repeatable every 2 s
Load current, min
1 mA per point
Scheduled outputs
CIP Sync only
States in Fault mode per point
Hold last state, On or Off (Off is default)
Duration of Fault mode per point
1, 2, 5, 10 s, Forever (Forever is default)
Final state after Fault mode duration per point
On or Off (default is Off)
States in Program mode per point
Hold last state, On or Off (default is Off)
Isolation voltage
250V (continuous), reinforced insulation type, outputs-to-backplane 250V (continuous), basic insulation type, output-to-output Type tested at 2300V AC for 60 s outputs-to-backplane Type tested at 1500V AC for 60 s output-to-output
Module keying
Electronic, software configurable
Fusing
Electronically fused per point
Reverse polarity protection
No
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire category
1 on signal ports(1)
North American temperature code
T4
IEC temperature code
T4
Enclosure type
None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
161
Page 162
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OB16IEF Attribute
1756-OB16IEF
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-OB16IEF Certification(1)
1756-OB16IEF c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
162
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 163
1756 ControlLogix I/O Specifications
1756-OB16IEFS ControlLogix DC (10…30V) scheduled, electronically protected, sinking or sourcing, isolated, fast output module 1756-OB16IEFS
Simplified Schematic DC-0(+)
DC-0 (+)
DC-0 (+) DC-1 (+)
2
1
OUT-0
4
3
OUT-1
DC-2 (+)
DC-2 (+)
6
5
OUT-2
DC-3 (+)
8
7
OUT-3
DC-4 (+)
10
9
OUT-4
DC-5 (+)
12
11
OUT-5
DC-6 (+)
14
13
OUT-6
DC-7 (+)
16
15
OUT-7
DC-8 (+)
18
17
OUT-8
DC-9 (+)
20
19
OUT-9
DC-10 (+)
22
21
OUT-10
DC-11 (+)
24
23
OUT-11
DC-12 (+)
26
25
OUT-12
DC-13 (+) DC-14 (+)
28
27
30
29
OUT-13 OUT-14
DC-15 (+)
32
31
OUT-15
DC-15 (+) Not Used
34
33
36
35
Not Used Not Used
Isolator
OUT-0
Sinking Output Wiring DC-6 (+)
Fault Display
ControlLogix Backplane Interface
Jumper Bar (Cut to Length)
Surge Current Chart
Current
Nonisolated Wiring
Surge
4A
Isolated Sourcing Output Wiring
Isolated Wiring
Continuous 2 A @ 45 °C (113 °F)
DC(+)
2A
+
–
Continuous 1 A @ 60 °C (140 °F)
1A
DC-0 (-) DC-2 (-)
DC-6 (-)
Nonisolated Sourcing Output Wiring
DC(-)
Daisy Chain to Other RTBs
0
10 ms Time
Additional jumper bars can be purchased by using catalog number 1756-JMPR. DC OUTPUT ST 0 1 2 3 4 5 6 7 FLT 0 1 2 3 4 5 6 7
O K
ST 8 9 10 11 12 13 14 15 FLT 8 9 10 11 12 13 14 15
SCHEDULED
Technical Specifications - 1756-OB16IEFS Attribute
1756-OB16IEFS
Outputs
16 scheduled, individually isolated
Pilot duty
4 A inrush
Voltage category
12/24V DC sink/source
Operating voltage range
10…30V DC
Unscheduled output delay time (backplane to screw) Off to On On to Off
14 μs nom/23 μs max 14 μs nom/23 μs max
Schedule accuracy
± 10 μs nom when all components are synchronized to the current CIP Sync Grandmaster
PWM cycle time
1 ms min/1 hour max
PWM On time
200 μs min/1 hour max
PWM On-time accuracy
± 20 μs
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
163
Page 164
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OB16IEFS (continued) Attribute
1756-OB16IEFS
Current draw @ 5.1V
320 mA
Current draw @ 24V
3 mA
Total backplane power
1.7 W
Power dissipation
4.9 W max (16 channels @ 1 A or 4 channels @ 2 A)
Thermal dissipation
16.71 BTU/hr
Off-state leakage current per point, max
< 0.1 mA per point
On-state voltage drop, max
0.2V DC @ 1 A 0.4V DC @ 2 A
Current per point, max
2 A @ 45 °C (113 °F) 4 channels max 1 A @ 60 °C (140 °F)
Current per module, max
16 A @ 60 °C (140 °F) 1 A max per channel 8 A @ 45 °C (113 °F) 2 A max per channel
Surge current per point
4 A for 10 ms per point, repeatable every 2 s
Load current, min
1 mA per point
Scheduled outputs
CIP Sync only
States in Fault mode per point
Hold last state, On or Off (Off is default)
Duration of Fault mode per point
1, 2, 5, 10 s, Forever (Forever is default)
Final state after Fault mode duration per point
On or Off (default is Off)
States in Program mode per point
Hold last state, On or Off (default is Off)
Isolation voltage
250V (continuous), reinforced insulation type, outputs-to-backplane 250V (continuous), basic insulation type, output-to-output Type tested at 2300V AC for 60 s outputs-to-backplane Type tested at 1500V AC for 60 s output-to-output
Module keying
Electronic, software configurable
Fusing
Electronically fused per point
Reverse polarity protection
No
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire category
1 on signal ports(1)
North American temperature code
T4
IEC temperature code
T4
Enclosure type
None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
164
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 165
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OB16IEFS Attribute
1756-OB16IEFS
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-OB16IEFS Certification(1)
1756-OB16IEFS c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
165
Page 166
1756 ControlLogix I/O Specifications
1756-OB16IS ControlLogix 24V DC scheduled, isolated output module Simplified Schematic
1756-OB16IS DC-0(+)
DC-0 (+) DC-1 (+) DC-2 (+) DC-2 (+) DC-3 (+) DC-4 (+) Sinking Output Wiring DC-5 (+) DC-6 (+) DC-6 (+) + – DC-7 (+) Jumper Bar DC-8 (+) (Cut to Length) DC-9 (+) DC-10 (+) DC-11 (+) Nonisolated DC-12 (+) Wiring DC-13 (+) DC-14 (+) DC-15 (+) DC(+) DC-15 (+) Not Used DC-0 (+)
+5V
OUT-0 ControlLogix Backplane Interface Display
Surge Current Chart Surge
4A
Current
Isolated Wiring
Continuous @ 30 °C (86 °F)
2A
Continuous @ 60 °C (140 °F)
2
1
4
3
6
5
8
7
10
9
12
11
14
13
16
15
18
17
20
19
22
21
24
23
26
25
28
27
30
29
32
31
34
33
36
35
OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used
Daisy Chain to Other RTBs
0
10 ms Time Additional jumper bars are available as catalog number 1756-JMPR.
DC OUTPUT ST 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15
O K
Technical Specifications - 1756-OB16IS Attribute
1756-OB16IS
Outputs
16 individually isolated, 8 scheduled
Pilot duty
2 A (DC-13SQ)
Voltage category
12/24V DC sink/source
Operating voltage range(1)
10…30V DC
Output delay time Off to On On to Off
1 ms max 2 ms max
Current draw @ 5.1V
350 mA
Current draw @ 24V
2.5 mA
Total backplane power
1.8 W
Power dissipation, max
3.6 W @ 60 °C (140 °F)
Thermal dissipation
12.28 BTU/hr
Off-state leakage current per point, max
0.5 mA per point
166
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Isolated Sourcing Output Wiring DC-0 (-) DC-2 (-)
DC-6 (-)
Nonisolated Sourcing Output Wiring
DC(-)
Page 167
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OB16IS (continued) Attribute
1756-OB16IS
On-state voltage drop, max
1.2V DC @ 2 A
Current per point, max
2 A @ 30 °C (86 °F) 1 A @ 60 °C (140 °F) (linear derating)
Current per module, max
8 A @ 30 °C (86 °F) 4 A @ 60 °C (140 °F) (linear derating)
Surge current per point
4 A for 10 ms per point, repeatable every 2 s
Load current, min
1 mA per point
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Fusing
Not protected. A fused IFM can be used to help protect outputs. See publication 1492-TD008. However, the ControlLogix system has been agency certified using only the ControlLogix RTBs, that is, 1756-TBCH, 1756-TBNH, 1756-TBSH, and 1756-TBS6H. Any application that requires agency certification of the ControlLogix system that uses other wiring termination methods can require application-specific approval by the certifying agency.
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(2)
Wire type
Copper
North American temperature code
T4A
IEC temperature code
T4
Enclosure type
None (open-style)
(1) UL certification for 24V DC nominal. Rockwell Automation specified to 10…30V DC (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-OB16IS Attribute
1756-OB16IS
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
167
Page 168
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OB16IS (continued) Attribute
1756-OB16IS
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-OB16IS Certification(1)
1756-OB16IS
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
168
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 169
1756 ControlLogix I/O Specifications
1756-OB32 ControlLogix DC (10…31.2V) output module Simplified Schematic
1756-OB32
DC-0(+)
+5V OUT-0
RTN OUT-0 ControlLogix Backplane Interface
Group 0
Daisy Chain to Other RTBs
Display
Surge Current Chart
Surge
Current
1A
Group 1 Continuous @ 60 °C (140 °F)
0.5 A
0
OUT-1 OUT-3 OUT-5 OUT-7 OUT-9 OUT-11
2
1
4
3
6
5
8
7
10
9
OUT-0 OUT-2 OUT-4 OUT-6 OUT-8 OUT-10
12 11
OUT-13 OUT-15 DC-0(+)
14 13
OUT-17 OUT-19 OUT-21 OUT-23 OUT-25 OUT-27
20 19
OUT-29 OUT-31 DC-1(+)
32 31
Group 0
OUT-12 OUT-14 RTN OUT-0
16 15 18 17
OUT-16 OUT-18 OUT-20 OUT-22 OUT-24 OUT-26
22 21 24 23 26 25 28 27 30 29
Group 1
OUT-28 OUT-30 RTN OUT-1
34 33 36 35
10 ms Time
+
_ DC COM
DC OUTPUT ST 0 1 2 3 4 5 6 7 1 11 11 1 ST 8 9 0 1 2 3 4 5 O K 1 1 1 12 22 2 ST 6 7 8 9 0 1 2 3 2 2 2 22 23 3 ST 4 5 6 7 8 9 0 1
Technical Specifications - 1756-OB32 Attribute
1756-OB32
Outputs
32 (16 points/group)
Voltage category
12/24V DC source
Operating voltage range
10…31.2V DC
Output delay time Off to On On to Off
60 s nom/1 ms max 200 s nom/1 ms max
Current draw @ 5.1V
300 mA
Current draw @ 24V
2 mA
Total backplane power
1.58 W
Power dissipation, max
4.8 W @ 60 °C (140 °F)
Thermal dissipation
16.37 BTU/hr
Off-state leakage current per point, max
0.5 mA per point
On-state voltage drop, max
200 mV DC @ 0.5 A
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
169
Page 170
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OB32 (continued) Attribute
1756-OB32
Current per point, max
0.5 A @ 50 °C (122 °F) linear derating 0.35 A @ 60 °C (140 °F)
Current per module, max
16 A @ 50 °C (122 °F) linear derating 10 A @ 60 °C (140 °F)
Surge current per point, max
1 A for 10 ms per point, repeatable every 2 s @ 60 °C (140 °F)
Load current, min
3 mA per point
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Fusing
Not protected. A fused IFM can be used to help protect outputs. See publication 1492-TD008. However, the ControlLogix system has been agency certified using only the ControlLogix RTBs, that is, 1756-TBCH, 1756-TBNH, 1756-TBSH, and 1756-TBS6H. Any application that requires agency certification of the ControlLogix system that uses other wiring termination methods can require application-specific approval by the certifying agency.
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
North American temperature code
T3C
IEC temperature code
T3
Enclosure type
None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-OB32 Attribute
1756-OB32
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
170
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016