Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 17 of 25

1756 ControlLogix I/O Specifications, Technical Data, pages 161 to 170

Pages 161 to 170 of 242

The original document is the PDF (7.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1756-IB16, Allen-Bradley 1756-OB16E and Allen-Bradley 1756-TBNH

Page 161

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OB16IEF (continued) Attribute

1756-OB16IEF

Current draw @ 24V

3 mA

Total backplane power

1.7 W

Power dissipation

4.9 W max (16 channels @ 1 A or 4 channels @ 2 A)

Thermal dissipation

16.71 BTU/hr

Off-state leakage current per point, max

< 0.1 mA per point

On-state voltage drop, max

0.2V DC @ 1 A 0.4V DC @ 2 A

Current per point, max

2 A @ 45 °C (113 °F) 4 channels max 1 A @ 60 °C (140 °F)

Current per module, max

16 A @ 60 °C (140 °F) 1 A max per channel 8 A @ 45 °C (113 °F) 2 A max per channel

Surge current per point

4 A for 10 ms per point, repeatable every 2 s

Load current, min

1 mA per point

Scheduled outputs

CIP Sync only

States in Fault mode per point

Hold last state, On or Off (Off is default)

Duration of Fault mode per point

1, 2, 5, 10 s, Forever (Forever is default)

Final state after Fault mode duration per point

On or Off (default is Off)

States in Program mode per point

Hold last state, On or Off (default is Off)

Isolation voltage

250V (continuous), reinforced insulation type, outputs-to-backplane 250V (continuous), basic insulation type, output-to-output Type tested at 2300V AC for 60 s outputs-to-backplane Type tested at 1500V AC for 60 s output-to-output

Module keying

Electronic, software configurable

Fusing

Electronically fused per point

Reverse polarity protection

No

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1 on signal ports(1)

North American temperature code

T4

IEC temperature code

T4

Enclosure type

None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

161

Page 162

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-OB16IEF Attribute

1756-OB16IEF

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-OB16IEF Certification(1)

1756-OB16IEF c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

162

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 163

1756 ControlLogix I/O Specifications

1756-OB16IEFS ControlLogix DC (10…30V) scheduled, electronically protected, sinking or sourcing, isolated, fast output module 1756-OB16IEFS

Simplified Schematic DC-0(+)

DC-0 (+)

DC-0 (+) DC-1 (+)

2

1

OUT-0

4

3

OUT-1

DC-2 (+)

DC-2 (+)

6

5

OUT-2

DC-3 (+)

8

7

OUT-3

DC-4 (+)

10

9

OUT-4

DC-5 (+)

12

11

OUT-5

DC-6 (+)

14

13

OUT-6

DC-7 (+)

16

15

OUT-7

DC-8 (+)

18

17

OUT-8

DC-9 (+)

20

19

OUT-9

DC-10 (+)

22

21

OUT-10

DC-11 (+)

24

23

OUT-11

DC-12 (+)

26

25

OUT-12

DC-13 (+) DC-14 (+)

28

27

30

29

OUT-13 OUT-14

DC-15 (+)

32

31

OUT-15

DC-15 (+) Not Used

34

33

36

35

Not Used Not Used

Isolator

OUT-0

Sinking Output Wiring DC-6 (+)

Fault Display

ControlLogix Backplane Interface

Jumper Bar (Cut to Length)

Surge Current Chart

Current

Nonisolated Wiring

Surge

4A

Isolated Sourcing Output Wiring

Isolated Wiring

Continuous 2 A @ 45 °C (113 °F)

DC(+)

2A

+

–

Continuous 1 A @ 60 °C (140 °F)

1A

DC-0 (-) DC-2 (-)

DC-6 (-)

Nonisolated Sourcing Output Wiring

DC(-)

Daisy Chain to Other RTBs

0

10 ms Time

Additional jumper bars can be purchased by using catalog number 1756-JMPR. DC OUTPUT ST 0 1 2 3 4 5 6 7 FLT 0 1 2 3 4 5 6 7

O K

ST 8 9 10 11 12 13 14 15 FLT 8 9 10 11 12 13 14 15

SCHEDULED

Technical Specifications - 1756-OB16IEFS Attribute

1756-OB16IEFS

Outputs

16 scheduled, individually isolated

Pilot duty

4 A inrush

Voltage category

12/24V DC sink/source

Operating voltage range

10…30V DC

Unscheduled output delay time (backplane to screw) Off to On On to Off

14 μs nom/23 μs max 14 μs nom/23 μs max

Schedule accuracy

± 10 μs nom when all components are synchronized to the current CIP Sync Grandmaster

PWM cycle time

1 ms min/1 hour max

PWM On time

200 μs min/1 hour max

PWM On-time accuracy

± 20 μs

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

163

Page 164

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OB16IEFS (continued) Attribute

1756-OB16IEFS

Current draw @ 5.1V

320 mA

Current draw @ 24V

3 mA

Total backplane power

1.7 W

Power dissipation

4.9 W max (16 channels @ 1 A or 4 channels @ 2 A)

Thermal dissipation

16.71 BTU/hr

Off-state leakage current per point, max

< 0.1 mA per point

On-state voltage drop, max

0.2V DC @ 1 A 0.4V DC @ 2 A

Current per point, max

2 A @ 45 °C (113 °F) 4 channels max 1 A @ 60 °C (140 °F)

Current per module, max

16 A @ 60 °C (140 °F) 1 A max per channel 8 A @ 45 °C (113 °F) 2 A max per channel

Surge current per point

4 A for 10 ms per point, repeatable every 2 s

Load current, min

1 mA per point

Scheduled outputs

CIP Sync only

States in Fault mode per point

Hold last state, On or Off (Off is default)

Duration of Fault mode per point

1, 2, 5, 10 s, Forever (Forever is default)

Final state after Fault mode duration per point

On or Off (default is Off)

States in Program mode per point

Hold last state, On or Off (default is Off)

Isolation voltage

250V (continuous), reinforced insulation type, outputs-to-backplane 250V (continuous), basic insulation type, output-to-output Type tested at 2300V AC for 60 s outputs-to-backplane Type tested at 1500V AC for 60 s output-to-output

Module keying

Electronic, software configurable

Fusing

Electronically fused per point

Reverse polarity protection

No

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1 on signal ports(1)

North American temperature code

T4

IEC temperature code

T4

Enclosure type

None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

164

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 165

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-OB16IEFS Attribute

1756-OB16IEFS

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-OB16IEFS Certification(1)

1756-OB16IEFS c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

165

Page 166

1756 ControlLogix I/O Specifications

1756-OB16IS ControlLogix 24V DC scheduled, isolated output module Simplified Schematic

1756-OB16IS DC-0(+)

DC-0 (+) DC-1 (+) DC-2 (+) DC-2 (+) DC-3 (+) DC-4 (+) Sinking Output Wiring DC-5 (+) DC-6 (+) DC-6 (+) + – DC-7 (+) Jumper Bar DC-8 (+) (Cut to Length) DC-9 (+) DC-10 (+) DC-11 (+) Nonisolated DC-12 (+) Wiring DC-13 (+) DC-14 (+) DC-15 (+) DC(+) DC-15 (+) Not Used DC-0 (+)

+5V

OUT-0 ControlLogix Backplane Interface Display

Surge Current Chart Surge

4A

Current

Isolated Wiring

Continuous @ 30 °C (86 °F)

2A

Continuous @ 60 °C (140 °F)

2

1

4

3

6

5

8

7

10

9

12

11

14

13

16

15

18

17

20

19

22

21

24

23

26

25

28

27

30

29

32

31

34

33

36

35

OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used

Daisy Chain to Other RTBs

0

10 ms Time Additional jumper bars are available as catalog number 1756-JMPR.

DC OUTPUT ST 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15

O K

Technical Specifications - 1756-OB16IS Attribute

1756-OB16IS

Outputs

16 individually isolated, 8 scheduled

Pilot duty

2 A (DC-13SQ)

Voltage category

12/24V DC sink/source

Operating voltage range(1)

10…30V DC

Output delay time Off to On On to Off

1 ms max 2 ms max

Current draw @ 5.1V

350 mA

Current draw @ 24V

2.5 mA

Total backplane power

1.8 W

Power dissipation, max

3.6 W @ 60 °C (140 °F)

Thermal dissipation

12.28 BTU/hr

Off-state leakage current per point, max

0.5 mA per point

166

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Isolated Sourcing Output Wiring DC-0 (-) DC-2 (-)

DC-6 (-)

Nonisolated Sourcing Output Wiring

DC(-)

Page 167

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OB16IS (continued) Attribute

1756-OB16IS

On-state voltage drop, max

1.2V DC @ 2 A

Current per point, max

2 A @ 30 °C (86 °F) 1 A @ 60 °C (140 °F) (linear derating)

Current per module, max

8 A @ 30 °C (86 °F) 4 A @ 60 °C (140 °F) (linear derating)

Surge current per point

4 A for 10 ms per point, repeatable every 2 s

Load current, min

1 mA per point

Scheduled outputs

Synchronization within 16.7 s max, reference to the Coordinated System Time

States in Fault mode per point

Hold last state, On or Off (Off is default)

States in Program mode per point

Hold last state, On or Off (Off is default)

Isolation voltage

250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Fusing

Not protected. A fused IFM can be used to help protect outputs. See publication 1492-TD008. However, the ControlLogix system has been agency certified using only the ControlLogix RTBs, that is, 1756-TBCH, 1756-TBNH, 1756-TBSH, and 1756-TBS6H. Any application that requires agency certification of the ControlLogix system that uses other wiring termination methods can require application-specific approval by the certifying agency.

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(2)

Wire type

Copper

North American temperature code

T4A

IEC temperature code

T4

Enclosure type

None (open-style)

(1) UL certification for 24V DC nominal. Rockwell Automation specified to 10…30V DC (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-OB16IS Attribute

1756-OB16IS

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

167

Page 168

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-OB16IS (continued) Attribute

1756-OB16IS

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-OB16IS Certification(1)

1756-OB16IS

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

168

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 169

1756 ControlLogix I/O Specifications

1756-OB32 ControlLogix DC (10…31.2V) output module Simplified Schematic

1756-OB32

DC-0(+)

+5V OUT-0

RTN OUT-0 ControlLogix Backplane Interface

Group 0

Daisy Chain to Other RTBs

Display

Surge Current Chart

Surge

Current

1A

Group 1 Continuous @ 60 °C (140 °F)

0.5 A

0

OUT-1 OUT-3 OUT-5 OUT-7 OUT-9 OUT-11

2

1

4

3

6

5

8

7

10

9

OUT-0 OUT-2 OUT-4 OUT-6 OUT-8 OUT-10

12 11

OUT-13 OUT-15 DC-0(+)

14 13

OUT-17 OUT-19 OUT-21 OUT-23 OUT-25 OUT-27

20 19

OUT-29 OUT-31 DC-1(+)

32 31

Group 0

OUT-12 OUT-14 RTN OUT-0

16 15 18 17

OUT-16 OUT-18 OUT-20 OUT-22 OUT-24 OUT-26

22 21 24 23 26 25 28 27 30 29

Group 1

OUT-28 OUT-30 RTN OUT-1

34 33 36 35

10 ms Time

+

_ DC COM

DC OUTPUT ST 0 1 2 3 4 5 6 7 1 11 11 1 ST 8 9 0 1 2 3 4 5 O K 1 1 1 12 22 2 ST 6 7 8 9 0 1 2 3 2 2 2 22 23 3 ST 4 5 6 7 8 9 0 1

Technical Specifications - 1756-OB32 Attribute

1756-OB32

Outputs

32 (16 points/group)

Voltage category

12/24V DC source

Operating voltage range

10…31.2V DC

Output delay time Off to On On to Off

60 s nom/1 ms max 200 s nom/1 ms max

Current draw @ 5.1V

300 mA

Current draw @ 24V

2 mA

Total backplane power

1.58 W

Power dissipation, max

4.8 W @ 60 °C (140 °F)

Thermal dissipation

16.37 BTU/hr

Off-state leakage current per point, max

0.5 mA per point

On-state voltage drop, max

200 mV DC @ 0.5 A

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

169

Page 170

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OB32 (continued) Attribute

1756-OB32

Current per point, max

0.5 A @ 50 °C (122 °F) linear derating 0.35 A @ 60 °C (140 °F)

Current per module, max

16 A @ 50 °C (122 °F) linear derating 10 A @ 60 °C (140 °F)

Surge current per point, max

1 A for 10 ms per point, repeatable every 2 s @ 60 °C (140 °F)

Load current, min

3 mA per point

Scheduled outputs

Synchronization within 16.7 s max, reference to the Coordinated System Time

States in Fault mode per point

Hold last state, On or Off (Off is default)

States in Program mode per point

Hold last state, On or Off (Off is default)

Isolation voltage

250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Fusing

Not protected. A fused IFM can be used to help protect outputs. See publication 1492-TD008. However, the ControlLogix system has been agency certified using only the ControlLogix RTBs, that is, 1756-TBCH, 1756-TBNH, 1756-TBSH, and 1756-TBS6H. Any application that requires agency certification of the ControlLogix system that uses other wiring termination methods can require application-specific approval by the certifying agency.

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(1)

North American temperature code

T3C

IEC temperature code

T3

Enclosure type

None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-OB32 Attribute

1756-OB32

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

170

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016