Page 171
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OB32 (continued) Attribute
1756-OB32
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-OB32 Certification(1)
1756-OB32
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T3 X Gc
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
171
Page 172
1756 ControlLogix I/O Specifications
1756-OC8 ControlLogix DC (30…60V) output module Simplified Schematic
DC-0(+)
1756-OC8 Daisy Chain to Other RTBs
+5V OUT-0
2
1
4
3
6
5
DC-0 (+)
OUT-0
DC-0 (+)
RTN OUT-0
Group 0
OUT-1 Group 0
DC-0 (+)
ControlLogix Backplane Interface
OUT-2 8
7
10
9
12
11
14
13
16
15
DC-0 (+)
Display
OUT-3
RTN OUT-0
RTN OUT-0
DC-1(+)
Surge Current Chart
OUT-4
DC-1(+)
Surge
4A
Group 1
OUT-5 Group 1
Current
DC-1(+)
Continuous @ 60 °C (140 °F)
2A
OUT-6 18
17
20
19
DC-1(+)
OUT-7
RTN OUT-1
0
10 ms
RTN OUT-1
+
Time
DC COM
DC OUTPUT ST 0 1 2 3 4 5 6 7 O K
Technical Specifications - 1756-OC8 Attribute
1756-OC8
Outputs
8 (4 points/group)
Pilot duty
2A
Voltage category
48V DC source
Operating voltage range
30…60V DC
Output delay time Off to On On to Off
1 ms, max 2 ms, max
Current draw @ 5.1V
165 mA
Current draw @ 24V
2 mA
Total backplane power
0.89 W
Power dissipation, max
4.9 W @ 60 °C (140 °F)
172
–
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Daisy Chain to Other RTBs
Page 173
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OC8 (continued) Attribute
1756-OC8
Thermal dissipation
16.71 BTU/hr
Off-state leakage current, max
1 mA per point
On-state voltage drop, max
2V DC @ 2 A
Current per point, max
2 A @ 60 °C (140 °F)
Current per module, max
8 A @ 60 °C (140 °F)
Surge current per point
4 A for 10 ms per point, repeatable every 1 s @ 60 °C (140 °F)
Load current, min
2 mA per point
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested at 1350V AC for 2 s
Module keying
Electronic, software configurable
Fusing
Not protected. A fused IFM is recommended to help protect outputs
Removable terminal block
1756-TBNH 1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
North American temperature code
T4
IEC temperature code
T4
Enclosure type
None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-OC8 Attribute
1756-OC8
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
173
Page 174
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OC8 (continued) Attribute
1756-OC8
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-OC8 Certification(1)
1756-OC8
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
174
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 175
1756 ControlLogix I/O Specifications
1756-OF4 ControlLogix voltage/current output analog module 1756-OF4 Current 2
2
1
Not Used
VOUT-0 4
IOUT-0 6
RTN
Current Output Load
A
5
RTN 8
7
Not Used 10
11
Not Used
Shield Ground
VOUT-2 14
13
Not Used
18
8
7
10
9
VOUT-1 IOUT-1 12
11
14
13
16
15
18
17
20
19
IOUT-2 RTN VOUT-3
Not Used
19
Shield Ground
VOUT-2
Not Used
17
–
RTN
RTN
VOUT-3 20
IOUT-0
Not Used
RTN
Not Used
5
Not Used
15
RTN
6
RTN
IOUT-2 16
3
Not Used
IOUT-1 12
4
Not Used
9
Not Used
VOUT-0
Not Used
VOUT-1
+
1
Not Used i
3
Not Used
Not Used
1756-OF4 Voltage
IOUT-3
IOUT-3
• Place additional loop devices (such as strip chart recorders) at the A location noted in the drawing. • All terminals marked RTN are connected internally.
All terminals marked RTN are connected internally.
ANALOG OUTPUT CAL OK
Signal and User Counts - 1756-OF4 Range
Low Signal and User Counts
High Signal and User Counts
0…20 mA
0 mA -32768 counts
21.2916 mA 32767 counts
±10V
-10.4336V -32768 counts
10.4336V 32767 counts
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
175
Page 176
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OF4 Attribute
1756-OF4
Outputs
Four voltage or current outputs
Output range
±10V 4…20 mA
Resolution
Voltage: 15 bits across 10.5V, 320 V/bit Current: 15 bits across 21 mA, 650 nA/bit
Voltage and current ratings
Backplane: 5.1V DC, 150 mA max 24V DC, 210 mA max Output voltage: -10…+10V Output current: 4…20 mA
Current draw @ 5.1V
150 mA
Current draw @ 24V
120 mA
Total backplane power
5.8 W
Power consumption
3.7 W backplane power
Power dissipation, max
3.7 W to 2.4 W; 0 to 750 ohm load
Thermal dissipation
10.91 BTU/hr
Open circuit detection
Current output only (Output must be set to >0.1 mA)
Overvoltage protection
24V DC
Short circuit protection
Electronically current limited to 21 mA or less
Drive capability
Voltage: >2000 Current: 0…750
Settling time
<2 ms to 95% of final value with resistive loads
Calibrated accuracy
Better than 0.05% of range from 4…21 mA, -10.4…10.4V
Calibration interval
12 months typical
Offset drift
50 V/ °C 100 nA/°C
Gain drift with temperature
Voltage: 25 ppm/°C, 520 V/°C Current: 50 ppm/°C, 1050 A/°C
Module error
Voltage: 0.15% of range Current: 0.3% of range
Module scan time
12 ms floating point 8 ms integer
Data format
Integer mode (left justified, 2 s complement) IEEE 32-bit floating point
Module conversion method
R-Ladder DAC, monotonicity with no missing codes
Isolation voltage
250V (continuous), Reinforced insulation type, Output Channels to Backplane No isolation between individual Output Channels Routine tested at 1350V AC for 2 s
Module keying
Electronic, software configurable
Removable terminal block
1756-TBNH 1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
176
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 177
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OF4 (continued) Attribute
1756-OF4
Wire size
1756-TBNH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max. Double wire connection: 0.33…1.3 mm² (22…16 AWG) solid or stranded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max. Do not wire more than two conductors on any terminal. 1756-TBSH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max. Do not wire multiple conductors on any terminal.
Terminal block torque specs Wiring category
(1)
1756-TBNH: 1.36 N•m (12 lb•in) 1 - on signal ports
North American temp code
T4A
ATEX temp code
T4
IECEx temp code
T4
Enclosure type
None (open-style)
(1) Use this conductor category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-OF4 Attribute
1756-OF4
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0 °C < Ta < 60 °C (+32 °F < Ta < +140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
IEC 61000-6-4
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
177
Page 178
1756 ControlLogix I/O Specifications
Certifications - 1756-OF4 Certification(1)
1756-OF4
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
178
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 179
1756 ControlLogix I/O Specifications
1756-OF6CI ControlLogix current loop output analog module 1756-OF6CI 0…550 Ω 2
2
1
OUT-1
OUT-0 4
3
6 i User Analog Output Device
8
9
12
11
14
13
16
15
Not Used
Shield Ground
Not Used
OUT-5 18
7
10
9
12
11
14
13
17
OUT-2
ALT-2 RTN-2 Shield Ground Not Used 16
15
18
17
20
19
OUT-4 ALT-4
ALT-5
19
User Analog Output Device
RTN-0
OUT-5
ALT-4 20
8
Not Used
OUT-4
ALT-5
5
RTN-3
RTN-2
RTN-3
6
ALT-3
ALT-2 i
ALT-0
OUT-3
OUT-2 10
ALT-1
7
ALT-3
3
RTN-1
RTN-0
OUT-3
OUT-0 4
5
RTN-1
1
OUT-1
ALT-0
ALT-1
RTN-5
1756-OF6CI 551…1000 Ω
RTN-4
RTN-5
RTN-4
Place additional devices anywhere in the loop. Place additional devices anywhere in the loop.
ANALOG OUTPUT CAL OK
Signal and User Counts - 1756-OF6CI Range
Low Signal and User Counts
High Signal and User Counts
0…21 mA
0 mA -32768 counts
21.074 mA 32767 counts
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
179
Page 180
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OF6CI Attribute
1756-OF6CI
Outputs
6 individually isolated
Output range
0…21 mA
Resolution
13 bits across 21 mA (2.7 A)
Current draw @ 5.1V
250 mA for 0…550 loads terminated on OUTs and RTNs 250 mA for 551…1000 loads terminated on OUTs and ALTs
Current draw @ 24V
225 mA for 0…550 loads terminated on OUTs and RTNs 300 mA for 551…1000 loads terminated on OUTs and ALTs
Total backplane power
6.7 W for 0…550 range 8.5 W for 551…1000 range
Power dissipation, max
5.5 W (0…550 loads) 6.1 W (551…1000 loads)
Thermal dissipation
18.76 BTU/hr (0…550 loads) 20.80 BTU/hr (551…1000 loads)
Open circuit detection
None
Overvoltage protection
24V DC
Short circuit protection
Electronically current limited to 21 mA or less
Drive capability
0…1000 Separate field terminations for 0…550 and 551…1000
Settling time
< 2 ms to 95% of final value with resistive loads
Calibrated accuracy @ 25 °C (77 °F)
Better than 0.1% of range from 4…21 mA
Calibration interval
6 months typical
Offset drift
1 A/°C typical
Gain drift with temperature, nom
60 ppm/°C
Gain drift with temperature, max
100 ppm/°C
Module error
0.6% of range
Module scan time, max
25 ms floating point 10 ms integer
Data format
Integer mode (left justified, 2 s complement) IEEE 32-bit floating point
Module conversion method
R-Ladder DAC, monotonicity with no missing codes
Isolation voltage
250V (continuous), basic insulation type, output channels-to-backplane, and output channel-to-channel Routine tested at 1350V AC for 2 s
Module keying
Electronic, software configurable
Removable terminal block
1756-TBNH 1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
Wire category
2(1)
North American temperature code
T4A
IEC temperature code
T4
Enclosure type
None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
180
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016