1756 ControlLogix I/O Specifications, Technical Data, pages 171 to 180

Pages 171 to 180 of 242

The original document is the PDF (7.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1756-IB16, Allen-Bradley 1756-OB16E and Allen-Bradley 1756-TBNH

Page 171

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-OB32 (continued) Attribute

1756-OB32

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-OB32 Certification(1)

1756-OB32

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T3 X Gc

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

171

Page 172

1756 ControlLogix I/O Specifications

1756-OC8 ControlLogix DC (30…60V) output module Simplified Schematic

DC-0(+)

1756-OC8 Daisy Chain to Other RTBs

+5V OUT-0

2

1

4

3

6

5

DC-0 (+)

OUT-0

DC-0 (+)

RTN OUT-0

Group 0

OUT-1 Group 0

DC-0 (+)

ControlLogix Backplane Interface

OUT-2 8

7

10

9

12

11

14

13

16

15

DC-0 (+)

Display

OUT-3

RTN OUT-0

RTN OUT-0

DC-1(+)

Surge Current Chart

OUT-4

DC-1(+)

Surge

4A

Group 1

OUT-5 Group 1

Current

DC-1(+)

Continuous @ 60 °C (140 °F)

2A

OUT-6 18

17

20

19

DC-1(+)

OUT-7

RTN OUT-1

0

10 ms

RTN OUT-1

+

Time

DC COM

DC OUTPUT ST 0 1 2 3 4 5 6 7 O K

Technical Specifications - 1756-OC8 Attribute

1756-OC8

Outputs

8 (4 points/group)

Pilot duty

2A

Voltage category

48V DC source

Operating voltage range

30…60V DC

Output delay time Off to On On to Off

1 ms, max 2 ms, max

Current draw @ 5.1V

165 mA

Current draw @ 24V

2 mA

Total backplane power

0.89 W

Power dissipation, max

4.9 W @ 60 °C (140 °F)

172

–

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Daisy Chain to Other RTBs

Page 173

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OC8 (continued) Attribute

1756-OC8

Thermal dissipation

16.71 BTU/hr

Off-state leakage current, max

1 mA per point

On-state voltage drop, max

2V DC @ 2 A

Current per point, max

2 A @ 60 °C (140 °F)

Current per module, max

8 A @ 60 °C (140 °F)

Surge current per point

4 A for 10 ms per point, repeatable every 1 s @ 60 °C (140 °F)

Load current, min

2 mA per point

Scheduled outputs

Synchronization within 16.7 s max, reference to the Coordinated System Time

States in Fault mode per point

Hold last state, On or Off (Off is default)

States in Program mode per point

Hold last state, On or Off (Off is default)

Isolation voltage

250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested at 1350V AC for 2 s

Module keying

Electronic, software configurable

Fusing

Not protected. A fused IFM is recommended to help protect outputs

Removable terminal block

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(1)

North American temperature code

T4

IEC temperature code

T4

Enclosure type

None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-OC8 Attribute

1756-OC8

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

173

Page 174

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-OC8 (continued) Attribute

1756-OC8

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-OC8 Certification(1)

1756-OC8

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

174

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 175

1756 ControlLogix I/O Specifications

1756-OF4 ControlLogix voltage/current output analog module 1756-OF4 Current 2

2

1

Not Used

VOUT-0 4

IOUT-0 6

RTN

Current Output Load

A

5

RTN 8

7

Not Used 10

11

Not Used

Shield Ground

VOUT-2 14

13

Not Used

18

8

7

10

9

VOUT-1 IOUT-1 12

11

14

13

16

15

18

17

20

19

IOUT-2 RTN VOUT-3

Not Used

19

Shield Ground

VOUT-2

Not Used

17

–

RTN

RTN

VOUT-3 20

IOUT-0

Not Used

RTN

Not Used

5

Not Used

15

RTN

6

RTN

IOUT-2 16

3

Not Used

IOUT-1 12

4

Not Used

9

Not Used

VOUT-0

Not Used

VOUT-1

+

1

Not Used i

3

Not Used

Not Used

1756-OF4 Voltage

IOUT-3

IOUT-3

• Place additional loop devices (such as strip chart recorders) at the A location noted in the drawing. • All terminals marked RTN are connected internally.

All terminals marked RTN are connected internally.

ANALOG OUTPUT CAL OK

Signal and User Counts - 1756-OF4 Range

Low Signal and User Counts

High Signal and User Counts

0…20 mA

0 mA -32768 counts

21.2916 mA 32767 counts

±10V

-10.4336V -32768 counts

10.4336V 32767 counts

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

175

Page 176

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OF4 Attribute

1756-OF4

Outputs

Four voltage or current outputs

Output range

±10V 4…20 mA

Resolution

Voltage: 15 bits across 10.5V, 320 V/bit Current: 15 bits across 21 mA, 650 nA/bit

Voltage and current ratings

Backplane: 5.1V DC, 150 mA max 24V DC, 210 mA max Output voltage: -10…+10V Output current: 4…20 mA

Current draw @ 5.1V

150 mA

Current draw @ 24V

120 mA

Total backplane power

5.8 W

Power consumption

3.7 W backplane power

Power dissipation, max

3.7 W to 2.4 W; 0 to 750 ohm load

Thermal dissipation

10.91 BTU/hr

Open circuit detection

Current output only (Output must be set to >0.1 mA)

Overvoltage protection

24V DC

Short circuit protection

Electronically current limited to 21 mA or less

Drive capability

Voltage: >2000 Current: 0…750

Settling time

<2 ms to 95% of final value with resistive loads

Calibrated accuracy

Better than 0.05% of range from 4…21 mA, -10.4…10.4V

Calibration interval

12 months typical

Offset drift

50 V/ °C 100 nA/°C

Gain drift with temperature

Voltage: 25 ppm/°C, 520 V/°C Current: 50 ppm/°C, 1050 A/°C

Module error

Voltage: 0.15% of range Current: 0.3% of range

Module scan time

12 ms floating point 8 ms integer

Data format

Integer mode (left justified, 2 s complement) IEEE 32-bit floating point

Module conversion method

R-Ladder DAC, monotonicity with no missing codes

Isolation voltage

250V (continuous), Reinforced insulation type, Output Channels to Backplane No isolation between individual Output Channels Routine tested at 1350V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

176

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 177

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OF4 (continued) Attribute

1756-OF4

Wire size

1756-TBNH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max. Double wire connection: 0.33…1.3 mm² (22…16 AWG) solid or stranded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max. Do not wire more than two conductors on any terminal. 1756-TBSH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max. Do not wire multiple conductors on any terminal.

Terminal block torque specs Wiring category

(1)

1756-TBNH: 1.36 N•m (12 lb•in) 1 - on signal ports

North American temp code

T4A

ATEX temp code

T4

IECEx temp code

T4

Enclosure type

None (open-style)

(1) Use this conductor category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-OF4 Attribute

1756-OF4

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0 °C < Ta < 60 °C (+32 °F < Ta < +140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

IEC 61000-6-4

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

177

Page 178

1756 ControlLogix I/O Specifications

Certifications - 1756-OF4 Certification(1)

1756-OF4

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

178

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 179

1756 ControlLogix I/O Specifications

1756-OF6CI ControlLogix current loop output analog module 1756-OF6CI 0…550 Ω 2

2

1

OUT-1

OUT-0 4

3

6 i User Analog Output Device

8

9

12

11

14

13

16

15

Not Used

Shield Ground

Not Used

OUT-5 18

7

10

9

12

11

14

13

17

OUT-2

ALT-2 RTN-2 Shield Ground Not Used 16

15

18

17

20

19

OUT-4 ALT-4

ALT-5

19

User Analog Output Device

RTN-0

OUT-5

ALT-4 20

8

Not Used

OUT-4

ALT-5

5

RTN-3

RTN-2

RTN-3

6

ALT-3

ALT-2 i

ALT-0

OUT-3

OUT-2 10

ALT-1

7

ALT-3

3

RTN-1

RTN-0

OUT-3

OUT-0 4

5

RTN-1

1

OUT-1

ALT-0

ALT-1

RTN-5

1756-OF6CI 551…1000 Ω

RTN-4

RTN-5

RTN-4

Place additional devices anywhere in the loop. Place additional devices anywhere in the loop.

ANALOG OUTPUT CAL OK

Signal and User Counts - 1756-OF6CI Range

Low Signal and User Counts

High Signal and User Counts

0…21 mA

0 mA -32768 counts

21.074 mA 32767 counts

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

179

Page 180

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OF6CI Attribute

1756-OF6CI

Outputs

6 individually isolated

Output range

0…21 mA

Resolution

13 bits across 21 mA (2.7 A)

Current draw @ 5.1V

250 mA for 0…550 loads terminated on OUTs and RTNs 250 mA for 551…1000 loads terminated on OUTs and ALTs

Current draw @ 24V

225 mA for 0…550 loads terminated on OUTs and RTNs 300 mA for 551…1000 loads terminated on OUTs and ALTs

Total backplane power

6.7 W for 0…550 range 8.5 W for 551…1000 range

Power dissipation, max

5.5 W (0…550 loads) 6.1 W (551…1000 loads)

Thermal dissipation

18.76 BTU/hr (0…550 loads) 20.80 BTU/hr (551…1000 loads)

Open circuit detection

None

Overvoltage protection

24V DC

Short circuit protection

Electronically current limited to 21 mA or less

Drive capability

0…1000 Separate field terminations for 0…550 and 551…1000

Settling time

< 2 ms to 95% of final value with resistive loads

Calibrated accuracy @ 25 °C (77 °F)

Better than 0.1% of range from 4…21 mA

Calibration interval

6 months typical

Offset drift

1 A/°C typical

Gain drift with temperature, nom

60 ppm/°C

Gain drift with temperature, max

100 ppm/°C

Module error

0.6% of range

Module scan time, max

25 ms floating point 10 ms integer

Data format

Integer mode (left justified, 2 s complement) IEEE 32-bit floating point

Module conversion method

R-Ladder DAC, monotonicity with no missing codes

Isolation voltage

250V (continuous), basic insulation type, output channels-to-backplane, and output channel-to-channel Routine tested at 1350V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

Wire category

2(1)

North American temperature code

T4A

IEC temperature code

T4

Enclosure type

None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

180

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016