Page 181
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OF6CI Attribute
1756-OF6CI
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±2 kV at 5 kHz on shielded signal ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on shielded signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on shielded signal ports
Certifications - 1756-OF6CI Certification(1)
1756-OF6CI
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
181
Page 182
1756 ControlLogix I/O Specifications
1756-OF6VI ControlLogix voltage loop output analog module 1756-OF6VI 2
+
1
OUT-1
OUT-0 4
3
Not Used
User Analog Output Device
Not Used 6
5
8
7
RTN-1
RTN-0
OUT-3
– ANALOG OUTPUT
OUT-2 10
9
12
11
Not Used
CAL
Not Used
RTN-3
OK
RTN-2 14
13
Not Used
Shield Ground Not Used
16
15
18
17
20
19
OUT-5
OUT-4
Not Used
Not Used
RTN-5
RTN-4
Place additional devices anywhere in the loop.
Signal and User Counts - 1756-OF6VI Range
Low Signal and User Counts
High Signal and User Counts
±10V
-10.517V -32768 counts
10.517V 32767 counts
Technical Specifications - 1756-OF6VI Attribute
1756-OF6VI
Outputs
6 individually isolated
Output range
± 10.5V
Resolution
14 bits across 21V (1.3 mV) (13 bits across 10.5V +sign bit)
Current draw @ 5.1V
250 mA
Current draw @ 24V
175 mA
Total backplane power
5.5 W
Power dissipation, max
4.85 W
Thermal dissipation
16.54 BTU/hr
Output impedance
<1
Open circuit detection
None
Overvoltage protection
24V DC
Short circuit protection
Electronically current limited
Drive capability
> 1000 loads, 10 mA
182
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 183
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OF6VI (continued) Attribute
1756-OF6VI
Settling time
< 2 ms to 95% of final value with resistive loads
Calibrated accuracy @ 25 °C (77 °F)
Better than 0.1% of range
Calibration interval
6 months typical
Offset drift
60 V/ °C typical
Gain drift with temperature, nom
50 ppm/°C
Gain drift with temperature, max
80 ppm/°C
Module error
0.5% of range
Module scan time, max
25 ms floating point 10 ms integer
Data format
Integer mode (left justified, 2 s complement) IEEE 32-bit floating point
Module conversion method
R-Ladder DAC, monotonicity with no missing codes
Isolation voltage
250V (continuous), basic insulation type, output channels-to-backplane, and output channel-to-channel Routine tested at 1350V AC for 2 s
Module keying
Electronic, software configurable
Removable terminal block
1756-TBNH 1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
Wire category
2(1)
North American temperature code
T4A
IEC temperature code
T4
Enclosure
None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-OF6VI Attribute
1756-OF6VI
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
183
Page 184
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OF6VI (continued) Attribute
1756-OF6VI
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±2 kV at 5 kHz on shielded signal ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on shielded signal ports
Conducted RF Immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on shielded signal ports
Certifications - 1756-OF6VI Certification(1)
1756-OF6VI
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
184
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 185
1756 ControlLogix I/O Specifications
1756-OF8 ControlLogix voltage/current output analog module 1756-OF8 Voltage
1756-OF8 Current 2
1
VOUT-4 4 i
Current IOUT-4 Output RTN Load
IOUT-0 6
5
8
7
10
9
RTN
A RTN
VOUT-5
11
VOUT-6
Shield Ground VOUT-2
14
13
16
15
IOUT-6
18
17
5
8
7
10
9
IOUT-0
19
• Place additional loop devices (such as strip chart recorders) at the A location noted in the drawing. • All terminals marked RTN are connected internally.
–
VOUT-1 Shield Ground IOUT-1 12
11
14
13
16
15
18
17
20
19
VOUT-2
VOUT-6
IOUT-2 RTN VOUT-3 IOUT-3
IOUT-7
IOUT-3
+
RTN
VOUT-7
VOUT-3 20
6
RTN
RTN
VOUT-7
3
IOUT-6
IOUT-2
RTN
4
IOUT-5
IOUT-1 12
VOUT-0
VOUT-5
VOUT-1
IOUT-5
1
VOUT-4
3
IOUT-4
IOUT-7
2
VOUT-0
All terminals marked RTN are connected internally.
ANALOG OUTPUT CAL OK
Signal and User Counts - 1756-OF8 Range
Low Signal and User Counts
High Signal and User Counts
0…20 mA
0 mA -32768 counts
21.2916 mA 32767 counts
±10V
-10.4336V -32768 counts
10.4336V 32767 counts
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
185
Page 186
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OF8 Attribute
1756-OF8
Outputs
Eight voltage or current
Output range
± 10V 0…20 mA
Resolution
15 bits across 21 mA - 650 nA/bit 15 bits across 10.4V - 320 V/bit
Current draw @ 5.1V
150 mA
Current draw @ 24V
210 mA
Total backplane power
5.8 W
Voltage and current ratings
Backplane: 5.1V DC, 150mA max, 24V DC, 210mA max Output Voltage: -10…+10V Output Current: 4…20mA
Power consumption
5.8 W backplane power
Power dissipation
5.8 W to 3.15 W; 0 to 750 ohm loads
Thermal dissipation
16.78 BTU/hr
Open circuit detection
Current output only (Output must be set to >0.1 mA)
Overvoltage protection
24V DC
Short circuit protection
Electronically current limited to 21 mA or less
Drive capability
Voltage: > 2000 Current: 0…750
Settling time
< 2 ms to 95% of final value with resistive loads
Calibrated accuracy @ 25 °C (77 °F)
Better than 0.05% of range from 4…21 mA, -10.4…10.4V
Calibration interval
12 months typical
Offset drift
50 V/°C typical (Voltage mode) 0.1 A/°C typical (Current mode)
Gain drift with temperature, max
Voltage: 25 ppm/°C max Current: 50 ppm/°C max
Module error
Voltage: 0.15% of range Current: 0.3% of range
Module scan time, min
12 ms floating point 8 ms integer
Data format
Integer mode (left justified, 2 s complement) IEEE 32-bit floating point
Module conversion method
R-Ladder DAC, monotonicity with no missing codes
Isolation voltage
250V (continuous), Reinforced insulation type, Output Channels to Backplane No isolation between individual Output Channels Routine tested at 1350V AC for 2 s
Module keying
Electronic, software configurable
Removable terminal block
1756-TBNH 1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
186
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 187
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OF8 (continued) Attribute
1756-OF8
Wire size
1756-TBNH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max. Double wire connection: 0.33…1.3 mm²(22…16 AWG) solid or stranded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max. Do not wire more than two conductors on any terminal. 1756-TBSH Single wire connection, 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.) insulation max. Do not wire multiple conductors on any terminal.
Terminal block torque specs Wiring category
(1)
1756-TBNH: 1.36 N•m (12 lb•in) 1 - on signal ports
North American temp code
T4A
ATEX temp code
T4
IECEx temp code
T4
Enclosure type
None (open-style)
(1) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-OF8 Attribute
1756-OF8
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
IEC 61000-6-4
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
187
Page 188
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OF8 (continued) Attribute
1756-OF8
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-OF8 Certification(1)
1756-OF8
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
CE
European Union 2014/30/EU EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2014/35/EU LVD, compliant with: • EN 61010-2-201; Control Equipment Safety Requirements
RCM
Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions
Ex
European Union 2014/34/EU ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • DEMKO15ATEX1482X
IECEx
IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • IECEx UL 15.0053X
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
EAC
Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
188
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 189
1756 ControlLogix I/O Specifications
1756-OF8H ControlLogix voltage/current output analog module with HART protocol 1756-OF8H
ANALOG OUTPUT CAL OK HART
Signal and User Counts - 1756-OF8H Range
Low Signal and User Counts
High Signal and User Counts
0…20 mA
0 mA -32768 counts
21.2916 mA 32767 counts
±10V
-10.4336V -32768 counts
10.4336V 32767 counts
Technical Specifications - 1756-OF8H Attribute
1756-OF8H
Outputs
Eight voltage or current, one HART modem per module
Output range
±10V 0…20 mA 4…20 mA
Resolution
15…16 bits for all ranges
Voltage and current ratings
Backplane: 5.1V DC, 230 mA, 24V DC, 230 mA Output voltage range: -10…10.4V Output current range: 0…20 mA, 4…20 mA
Total backplane power
6.54 W
Power dissipation
4.92 W
Thermal dissipation
16.78 BTU/hr
Isolation voltage
50V (continuous), Basic insulation type, Output Channels to Backplane No isolation between individual output Channels Type tested at 1500V AC for 60 s
Output impedance
–
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
189
Page 190
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OF8H (continued) Attribute
1756-OF8H
Open circuit detection time
Current output only (output must be set to < 0.1 mA)
Overvoltage protection, max
±24V DC
Drive capability
–
Load reactance, max
Voltage: 1 F Current: 10 H
Settling time
Current (no HART): < 23 ms to 95% with resistive loads Current (with HART): < 37 ms to 95% with resistive loads Voltage: < 8.5 ms to 95% with resistive loads
Calibrated accuracy @ 25 °C (77 °F) with HART disabled
Voltage: Better than 0.1% of range Current: Better than 0.15% of range
Calibration interval
12 months typical
Offset drift
100 V/°C typical 200 nA/°C typical
Gain drift with temperature
Voltage: 20 ppm/°C Current: 35 ppm/°C
Module error
Voltage: 0.15% of range Current: 0.3% of range
Module HART scan time
Analog: 12 ms, min, floating point. HART: typically 1 s per HART channel enabled. Estimate 10 s if all 8 channels have HART enabled. Pass through messages, handheld communicators, secondary masters, communication errors, or configuration changes can significantly increase the update time
Data format
Integer mode (left justified, 2 s complement) IEEE 32-bit floating point
Input conversion method
Successive approximation
Output conversion method
R-Ladder DAC, monotonicity with no missing codes
Module keying
Electronic, software configurable
Removable terminal block
1756-TBNH 1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
Wire size
1756-TBNH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max Double wire connection: 0.33…1.3 mm² (22…16 AWG) solid or stranded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max 1756-TBSH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max
Terminal block torque specs
1756-TBNH 1.36 N•m (12 lb·in)
Wire category(1)
2 - on signal ports
Wire type
Copper
North American temp code
T4
ATEX temp code
T4
IECEx temp code
T4
Enclosure type rating
None (open-style)
(1) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
190
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016