The text of a spec sheet · part 20 of 25
1756 ControlLogix I/O Specifications, Technical Data, pages 191 to 200
Pages 191 to 200 of 242
The original document is the PDF (7.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-IB16, Allen-Bradley 1756-OB16E and Allen-Bradley 1756-TBNH
Page 191
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OF8H Attribute
1756-OF8H
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
IEC 61000-6-4
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±2 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on shielded ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
191
Page 192
1756 ControlLogix I/O Specifications
Certifications - 1756-OF8H Certification(1)
1756-OF8H c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2014/30/EU EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
RCM
Australian Radiocommunications Act, compliant with: EN 61000-6-4: Industrial Emissions
Ex
European Union 2014/34/EU ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • DEMKO12ATEX1219040X
IECEx
IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • IECEx UL 16.0109X
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
EAC
Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
192
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 193
1756 ControlLogix I/O Specifications
1756-OF8I ControlLogix isolated voltage/current output analog module. 1756-OF8I Module Wiring Diagram - Current Mode
IMPORTANT: Remember the following:
• If separate power sources are used, do not exceed the specific isolation voltage as listed in the specifications. • Place additional devices anywhere in the loop.
OUT_0/V
2
1
OUT_1/V
OUT_0/I
4
3
OUT_1/I
RTN_0
6
5
RTN_1
Not used
8
7
Not used
OUT_2/V
10
9
OUT_3/V
OUT_2/I
12 11
OUT_3/I
RTN_2
14 13
RTN_3
Not used
16 15
Not used
OUT_4/V
18 17
OUT_5/V
OUT_4/I
20 19
OUT_5/I
RTN_4
22 21
RTN_5
Not used
24 23
Not used
OUT_6/V
26 25
OUT_7/V
OUT_6/I
28 27
OUT_7/I
RTN_6
30 29
RTN_7
Not used
32 31
Not used
Not used
34 33
Not used
Not used
36 35
Not used i < 1000 User Analog Output Device
ANALOG OUPUT
ST FLT
1756-OF8I Module Wiring Diagram - Voltage Mode
IMPORTANT: Remember the following:
• If separate power sources are used, do not exceed the specific isolation voltage as listed in the specifications. • Place additional devices anywhere in the loop.
OUT_0/V
2
1
OUT_1/V
OUT_0/I
4
3
OUT_1/I
RTN_0
6
5
RTN_1
Not used
8
7
Not used
OUT_2/V
10
9
OUT_3/V
OUT_2/I
12 11
OUT_3/I
RTN_2
14 13
RTN_3
Not used
16 15
Not used
OUT_4/V
18 17
OUT_5/V
OUT_4/I
20 19
OUT_5/I
RTN_4
22 21
RTN_5
Not used
24 23
Not used
OUT_6/V
26 25
OUT_7/V
OUT_6/I
28 27
OUT_7/I
RTN_6
30 29
RTN_7
Not used
32 31
Not used
Not used
34 33
Not used
Not used
36 35
Not used
O K
+
> 1000 User Analog Output Device –
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
193
Page 194
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OF8I Attribute
1756-OF8I
Outputs
Eight isolated channels - Any combination of voltage or current mode
Output range
-10…10V 0…10V 0…5V 0…20 mA
Resolution
16-bit ±10.5V (0.32 mV/count) 0…10.5V (0.16 mV/count) 0…5.25V (0.08 mV/count) 0…21 mA (0.32 μA/count)
Current draw @ 5.1V
200 mA
Current draw @ 24V
Voltage or Current mode with 250 loads = 220 mA Current mode with 500 loads = 275 mA Current mode with 750 loads = 340 mA Current mode with 1000 loads = 385 mA
Total backplane power
Voltage mode = 6.3 W Current mode with 250 loads = 6.3 W Current mode with 500 loads = 7.6 W Current mode with 750 loads = 9.2 W Current mode with 1000 loads = 10.2 W
Power dissipation, max
Voltage mode = 5.4 W Current mode with 250 loads = 5.4 W Current mode with 500 loads = 5.8 W Current mode with 750 loads = 6.5 W Current mode with 1000 loads = 6.7 W
Thermal dissipation
Voltage mode = 18.4 BTU/hr Current mode with 250 loads = 18.4 BTU/hr Current mode with 500 loads = 19.8 BTU/hr Current mode with 750 loads = 22.2 BTU/hr Current mode with 1000 loads = 22.9 BTU/hr
Output impedance
46 (Current output)
Open circuit detection
Current output = Yes
Short circuit detection
Voltage output = Yes
Overvoltage protection
±30V DC (voltage/current)
Drive capability
Current output = 0…1000 Voltage output = >1000
Settling time
< 2 ms to 95% of final value with Resistive loads
Calibrated accuracy @ 25 °C (77 °F)
0.05%
Module error over full temperature range
0.1%
Module scan time, min
1 ms
Data format
IEEE 32-bit floating point
Module conversion method
R-Ladder DAC, monotonicity with no missing codes
Isolation voltage
250V (continuous), reinforced insulation type, outputs to backplane 250V (continuous), basic insulation type, output to output Type tested at 2300V AC for 60 s, outputs to backplane Type tested at 1500V AC for 60 s, output to output
Module keying
Electronic, software configurable
194
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 195
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OF8I (continued) Attribute
1756-OF8I
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire size
0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max
Wire category
2 on signal ports(1)
North American temperature code
T4
IEC temperature code
T4
Enclosure type
None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-OF8I Attribute
1756-OF8I
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on shielded signal ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on shielded signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
195
Page 196
1756 ControlLogix I/O Specifications
Certifications - 1756-OF8I Certification(1)
1756-OF8I c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 Gc X
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
196
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 197
1756 ControlLogix I/O Specifications
1756-OF8IH ControlLogix isolated HART current analog output module Not used IOUT0 RTN0 Not used Not used IOUT2 RTN2 Not used Not used IOUT4 RTN4 Not used Not used IOUT6 RTN6 Not used Not used Not used
2
1
4
3
6
5
8
7
10
9
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
XMTR2
Not used IOUT1 RTN1 Reserved Reserved IOUT3 RTN3 Not used Not used IOUT5 RTN5 Not used Not used IOUT7 RTN7 Not used Not used Not used
ANALOG OUTPUT CAL OK HART
Signal and User Counts - 1756-OF8IH Range
Low Signal
High Signal
0…21 mA
0 mA
21.2916 mA
Technical Specifications - 1756-OF8IH Attribute
1756-OF8IH
Outputs
8 current
Output range
0…20 mA 4…20 mA
Resolution
15 bits across 24 mA, 732 nA per bit
Voltage and current ratings
Backplane: 220 mA @ 5.1V DC, 360 mA @ 24V DC Output voltage range: 5…30V DC Output current range: 0…20 mA, 4…20 mA
Current draw @ 24V
400 mA (estimated)
Power dissipation, max
6.5 W nominal (< 6.4 W with 50 load on all channels) (<6.5 W with 250 load on all channels) (<6.7 W with 750 load on all channels)
Open circuit detection
Current output only (output must be set >= 0.1 mA)
Overvoltage protection, max
±24V DC
Output short circuit protection
Current electronically limited to <= 21 mA with no damage
Drive capability
50…750 with short circuit survival
Load reactance, max
10 H
Settling time
HART not enabled: < 23 ms to 95% with resistive loads HART enabled: < 100 ms to 95% with resistive loads
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
197
Page 198
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OF8IH (continued) Attribute
1756-OF8IH
Calibrated accuracy @ 25 °C (77 °F)
0.15% @ 4…20 mA
Calibration interval
12 months typical
Offset drift
±3 ppm of full scale range/°C (72 nA/°C typical)
Gain drift with temperature
±4 ppm of full scale range/°C
Module error
0.3% @ 4…20 mA
Module scan time
Estimate 1 s if all channels are HART enabled Pass through messages, handheld communications, secondary masters, communication errors, or configuration changes can significantly increase the update time.
Data format
IEEE 32-bit floating point
Output conversion method
R-Ladder DAC
Isolation voltage
250V (continuous) Reinforced Insulation Type, outputs to backplane. Basic Insulation Type, output to output, and outputs to ground. Type tested at 3535V DC for 60 s, outputs to backplane. Type tested at 2120V DC for 60 s, output to output, and outputs to ground.
Module keying
Electronic, software configurable
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire size
1756-TBCH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max 1756-TBS6H Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max
Terminal block torque specs
1756-TBCH 0.5 N•m (4.4 lb•in)
Wiring category(1)
2 - on signal ports
Wire type
Copper
North American temp code
T4A
ATEX temp code
T4
IECEx temp code
T4
Enclosure type rating
None (open-style)
(1)
Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-OF8IH Attribute
1756-OF8IH
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock
-40…+85 °C (-40…+185 °F)
198
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 199
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OF8IH (continued) Attribute
1756-OF8IH
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration (operating) IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Emissions
IEC 61000-6-4
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz square wave 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz square wave 50% Pulse 100% AM @ 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±2 kV @ 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on shielded ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-OF8IH Certification(1)
1756-OF8IH c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2014/30/EU EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A and B) European Union 2014/35/EU LVD, compliant with: • EN 61131-2; Programmable Controllers (Clause 11)
RCM
Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions
Ex
European Union 2014/34/EU ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • DEMKO14ATEX1238X
IECEx
IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • IECEx UL 16.0110X
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
EAC
Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
199
Page 200
1756 ControlLogix I/O Specifications
1756-OG16 ControlLogix TTL output module 1756-OG16 CE Compliant Wiring
1756-OG16 Standard Wiring – DC
+ 2
1
OUT-1 +5 V DC
OUT-0 4
3
6
5
8
7
OUT-3
10
9
+
OUT-8 14
13
OUT-11
OUT-10 16 18
15 17
TTL Output Device
–
5
8
7
10
9
12
11
14
13
16
15
18
17
20
19
OUT-4 OUT-6 DC COM 0 OUT-8
OUT-11
OUT-10
OUT-13
OUT-12
OUT-15
19
DC-1(+)
OUT-0 OUT-2
OUT-9
Capacitor 0.01 µF Typical (See notes below.)
OUT-14 20
6
DC-0(+)
OUT-12
OUT-15
3
OUT-7
I/O Wire
11
OUT-9
4
OUT-5
DC COM 0 12
1
OUT-3
OUT-6
DC-0(+)
2
OUT-1
OUT-4
OUT-7
OUT-13
–
OUT-2
OUT-5
+ DC
5V DC Power
DC Power Wire
OUT-14
DC COM 1
DC-1(+)
DC COM 1
Simplified Schematic +5 DC
IMPORTANT: I/O cables must be shielded type and cable length must be <10 m (32.8 ft) for maximum EMI noise immunity.
74AC14
OUT
DC OUTPUT ST 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15
74AC14
OUT
DC COM
Low to True Format - 1756-OG16 • 0…0.4V DC = Output guaranteed to be in on-state • 0.4…4.5V DC = Output state not guaranteed • 4.5…5.5V DC = Output guaranteed to be in off-state
200
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
O K