Page 191

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-OF8H Attribute

1756-OF8H

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

IEC 61000-6-4

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±2 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on shielded ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

191

Page 192

1756 ControlLogix I/O Specifications

Certifications - 1756-OF8H Certification(1)

1756-OF8H c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2014/30/EU EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

RCM

Australian Radiocommunications Act, compliant with: EN 61000-6-4: Industrial Emissions

Ex

European Union 2014/34/EU ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • DEMKO12ATEX1219040X

IECEx

IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • IECEx UL 16.0109X

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

EAC

Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

192

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 193

1756 ControlLogix I/O Specifications

1756-OF8I ControlLogix isolated voltage/current output analog module. 1756-OF8I Module Wiring Diagram - Current Mode

IMPORTANT: Remember the following:

• If separate power sources are used, do not exceed the specific isolation voltage as listed in the specifications. • Place additional devices anywhere in the loop.

OUT_0/V

2

1

OUT_1/V

OUT_0/I

4

3

OUT_1/I

RTN_0

6

5

RTN_1

Not used

8

7

Not used

OUT_2/V

10

9

OUT_3/V

OUT_2/I

12 11

OUT_3/I

RTN_2

14 13

RTN_3

Not used

16 15

Not used

OUT_4/V

18 17

OUT_5/V

OUT_4/I

20 19

OUT_5/I

RTN_4

22 21

RTN_5

Not used

24 23

Not used

OUT_6/V

26 25

OUT_7/V

OUT_6/I

28 27

OUT_7/I

RTN_6

30 29

RTN_7

Not used

32 31

Not used

Not used

34 33

Not used

Not used

36 35

Not used i < 1000 User Analog Output Device

ANALOG OUPUT

ST FLT

1756-OF8I Module Wiring Diagram - Voltage Mode

IMPORTANT: Remember the following:

• If separate power sources are used, do not exceed the specific isolation voltage as listed in the specifications. • Place additional devices anywhere in the loop.

OUT_0/V

2

1

OUT_1/V

OUT_0/I

4

3

OUT_1/I

RTN_0

6

5

RTN_1

Not used

8

7

Not used

OUT_2/V

10

9

OUT_3/V

OUT_2/I

12 11

OUT_3/I

RTN_2

14 13

RTN_3

Not used

16 15

Not used

OUT_4/V

18 17

OUT_5/V

OUT_4/I

20 19

OUT_5/I

RTN_4

22 21

RTN_5

Not used

24 23

Not used

OUT_6/V

26 25

OUT_7/V

OUT_6/I

28 27

OUT_7/I

RTN_6

30 29

RTN_7

Not used

32 31

Not used

Not used

34 33

Not used

Not used

36 35

Not used

O K

+

> 1000 User Analog Output Device –

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

193

Page 194

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OF8I Attribute

1756-OF8I

Outputs

Eight isolated channels - Any combination of voltage or current mode

Output range

-10…10V 0…10V 0…5V 0…20 mA

Resolution

16-bit ±10.5V (0.32 mV/count) 0…10.5V (0.16 mV/count) 0…5.25V (0.08 mV/count) 0…21 mA (0.32 μA/count)

Current draw @ 5.1V

200 mA

Current draw @ 24V

Voltage or Current mode with 250 loads = 220 mA Current mode with 500 loads = 275 mA Current mode with 750 loads = 340 mA Current mode with 1000 loads = 385 mA

Total backplane power

Voltage mode = 6.3 W Current mode with 250 loads = 6.3 W Current mode with 500 loads = 7.6 W Current mode with 750 loads = 9.2 W Current mode with 1000 loads = 10.2 W

Power dissipation, max

Voltage mode = 5.4 W Current mode with 250 loads = 5.4 W Current mode with 500 loads = 5.8 W Current mode with 750 loads = 6.5 W Current mode with 1000 loads = 6.7 W

Thermal dissipation

Voltage mode = 18.4 BTU/hr Current mode with 250 loads = 18.4 BTU/hr Current mode with 500 loads = 19.8 BTU/hr Current mode with 750 loads = 22.2 BTU/hr Current mode with 1000 loads = 22.9 BTU/hr

Output impedance

46 (Current output)

Open circuit detection

Current output = Yes

Short circuit detection

Voltage output = Yes

Overvoltage protection

±30V DC (voltage/current)

Drive capability

Current output = 0…1000 Voltage output = >1000

Settling time

< 2 ms to 95% of final value with Resistive loads

Calibrated accuracy @ 25 °C (77 °F)

0.05%

Module error over full temperature range

0.1%

Module scan time, min

1 ms

Data format

IEEE 32-bit floating point

Module conversion method

R-Ladder DAC, monotonicity with no missing codes

Isolation voltage

250V (continuous), reinforced insulation type, outputs to backplane 250V (continuous), basic insulation type, output to output Type tested at 2300V AC for 60 s, outputs to backplane Type tested at 1500V AC for 60 s, output to output

Module keying

Electronic, software configurable

194

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 195

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OF8I (continued) Attribute

1756-OF8I

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire size

0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max

Wire category

2 on signal ports(1)

North American temperature code

T4

IEC temperature code

T4

Enclosure type

None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-OF8I Attribute

1756-OF8I

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on shielded signal ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on shielded signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

195

Page 196

1756 ControlLogix I/O Specifications

Certifications - 1756-OF8I Certification(1)

1756-OF8I c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 Gc X

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

196

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 197

1756 ControlLogix I/O Specifications

1756-OF8IH ControlLogix isolated HART current analog output module Not used IOUT0 RTN0 Not used Not used IOUT2 RTN2 Not used Not used IOUT4 RTN4 Not used Not used IOUT6 RTN6 Not used Not used Not used

2

1

4

3

6

5

8

7

10

9

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

XMTR2

Not used IOUT1 RTN1 Reserved Reserved IOUT3 RTN3 Not used Not used IOUT5 RTN5 Not used Not used IOUT7 RTN7 Not used Not used Not used

ANALOG OUTPUT CAL OK HART

Signal and User Counts - 1756-OF8IH Range

Low Signal

High Signal

0…21 mA

0 mA

21.2916 mA

Technical Specifications - 1756-OF8IH Attribute

1756-OF8IH

Outputs

8 current

Output range

0…20 mA 4…20 mA

Resolution

15 bits across 24 mA, 732 nA per bit

Voltage and current ratings

Backplane: 220 mA @ 5.1V DC, 360 mA @ 24V DC Output voltage range: 5…30V DC Output current range: 0…20 mA, 4…20 mA

Current draw @ 24V

400 mA (estimated)

Power dissipation, max

6.5 W nominal (< 6.4 W with 50 load on all channels) (<6.5 W with 250 load on all channels) (<6.7 W with 750 load on all channels)

Open circuit detection

Current output only (output must be set >= 0.1 mA)

Overvoltage protection, max

±24V DC

Output short circuit protection

Current electronically limited to <= 21 mA with no damage

Drive capability

50…750 with short circuit survival

Load reactance, max

10 H

Settling time

HART not enabled: < 23 ms to 95% with resistive loads HART enabled: < 100 ms to 95% with resistive loads

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

197

Page 198

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OF8IH (continued) Attribute

1756-OF8IH

Calibrated accuracy @ 25 °C (77 °F)

0.15% @ 4…20 mA

Calibration interval

12 months typical

Offset drift

±3 ppm of full scale range/°C (72 nA/°C typical)

Gain drift with temperature

±4 ppm of full scale range/°C

Module error

0.3% @ 4…20 mA

Module scan time

Estimate 1 s if all channels are HART enabled Pass through messages, handheld communications, secondary masters, communication errors, or configuration changes can significantly increase the update time.

Data format

IEEE 32-bit floating point

Output conversion method

R-Ladder DAC

Isolation voltage

250V (continuous) Reinforced Insulation Type, outputs to backplane. Basic Insulation Type, output to output, and outputs to ground. Type tested at 3535V DC for 60 s, outputs to backplane. Type tested at 2120V DC for 60 s, output to output, and outputs to ground.

Module keying

Electronic, software configurable

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire size

1756-TBCH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max 1756-TBS6H Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max

Terminal block torque specs

1756-TBCH 0.5 N•m (4.4 lb•in)

Wiring category(1)

2 - on signal ports

Wire type

Copper

North American temp code

T4A

ATEX temp code

T4

IECEx temp code

T4

Enclosure type rating

None (open-style)

(1)

Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-OF8IH Attribute

1756-OF8IH

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock

-40…+85 °C (-40…+185 °F)

198

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 199

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-OF8IH (continued) Attribute

1756-OF8IH

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration (operating) IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Emissions

IEC 61000-6-4

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz square wave 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz square wave 50% Pulse 100% AM @ 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±2 kV @ 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on shielded ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-OF8IH Certification(1)

1756-OF8IH c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2014/30/EU EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A and B) European Union 2014/35/EU LVD, compliant with: • EN 61131-2; Programmable Controllers (Clause 11)

RCM

Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions

Ex

European Union 2014/34/EU ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • DEMKO14ATEX1238X

IECEx

IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • IECEx UL 16.0110X

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

EAC

Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

199

Page 200

1756 ControlLogix I/O Specifications

1756-OG16 ControlLogix TTL output module 1756-OG16 CE Compliant Wiring

1756-OG16 Standard Wiring – DC

+ 2

1

OUT-1 +5 V DC

OUT-0 4

3

6

5

8

7

OUT-3

10

9

+

OUT-8 14

13

OUT-11

OUT-10 16 18

15 17

TTL Output Device

–

5

8

7

10

9

12

11

14

13

16

15

18

17

20

19

OUT-4 OUT-6 DC COM 0 OUT-8

OUT-11

OUT-10

OUT-13

OUT-12

OUT-15

19

DC-1(+)

OUT-0 OUT-2

OUT-9

Capacitor 0.01 µF Typical (See notes below.)

OUT-14 20

6

DC-0(+)

OUT-12

OUT-15

3

OUT-7

I/O Wire

11

OUT-9

4

OUT-5

DC COM 0 12

1

OUT-3

OUT-6

DC-0(+)

2

OUT-1

OUT-4

OUT-7

OUT-13

–

OUT-2

OUT-5

+ DC

5V DC Power

DC Power Wire

OUT-14

DC COM 1

DC-1(+)

DC COM 1

Simplified Schematic +5 DC

IMPORTANT: I/O cables must be shielded type and cable length must be <10 m (32.8 ft) for maximum EMI noise immunity.

74AC14

OUT

DC OUTPUT ST 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15

74AC14

OUT

DC COM

Low to True Format - 1756-OG16 • 0…0.4V DC = Output guaranteed to be in on-state • 0.4…4.5V DC = Output state not guaranteed • 4.5…5.5V DC = Output guaranteed to be in off-state

200

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

O K