1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OG16 Attribute
1756-OG16
Outputs
16 (8 points/group)
Voltage category
5V DC TTL (Low=True(1)
Operating voltage range
4.5…5.5V DC source, 50 mV P-P ripple max
Output delay time (resistive load) Off to On (5V-to-0V DC transition) On to Off (0V-to-5V DC transition)
45 μs nom/450 μs max 145 μs nom/700 μs max
Current draw @ 5.1V
210 mA
Current draw @ 24V
2 mA
Total backplane power
1.12 W
Power dissipation, max
1.5 W @ 60 °C (140 °F)
Thermal dissipation
5.2 BTU/hr @ 60 °C (140 °F)
Off-state leakage current per point, max
0.1 mA per point
On-state voltage drop, max
0.4V DC
Continuous current, max
24 mA
Load current per point, max
24 mA
Load current per module, max
384 mA
Load current
0.15 mA
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Fusing
Not protected. A fused IFM is recommended to help protect outputs.
Removable terminal block
1756-TBNH 1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
Wire category
2(2)
North American temperature code
T5
IEC temperature code
T5
Enclosure type
None (open-style)
(1) TTL outputs are inverted (0 to +0.4V DC = low voltage = True = On.) Use a NOT instruction in your program to convert to traditional True - High logic. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
201
Page 202
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OG16 Attribute
1756-OG16
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-OG16 Certification(1)
1756-OG16
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T5 X Gc
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
202
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 203
1756 ControlLogix I/O Specifications
1756-OH8I ControlLogix DC (90…146V) isolated output module Simplified Schematic
1756-OH81
DC-0 Isolated Wiring
+5V OUT-0
+
-
RTN OUT-0 +
ControlLogix Backplane Interface
-
Display Surge Current Chart Surge
4A
Current
Non-Isolated Wiring
Continuous @ 60 °C (140 °F) 2A
0
Daisy chain to other RTBs
Daisy chain to other RTBs
10 ms Time
DC-0 (+)
2
1
OUT-0
RTN OUT-0
4
3
OUT-0
DC-1 (+)
6
5
OUT-1
RTN OUT-1 DC-2 (+)
8
7
10
9
OUT-1 OUT-2
RTN OUT-2
12 11
OUT-2
DC-3 (+)
14 13
OUT-3
RTN OUT-3
16 15
OUT-3
DC-4 (+)
18 17
OUT-4
RTN OUT-4
20 19
OUT-4
DC-5 (+)
22 21
OUT-5
RTN OUT-5
24 23
OUT-5
DC-6 (+)
26 25
OUT-6
RTN OUT-6
28 27
OUT-6
DC-7 (+)
30 29
OUT-7
RTN OUT-7
32 31
OUT-7
Not used
34 33
Not used
Not used
36 35
Not used
+
– DC COM
DC OUTPUT ST 0 1 2 3 4 5 6 7 O K
Technical Specifications - 1756-OH8I Attribute
1756-OH8I
Outputs
8 individually isolated
Voltage category
120V DC sink/source
Operating voltage range
90…146V DC
Output delay time Off to On On to Off
2 ms max 2 ms max
Current draw @ 5.1V
210 mA
Current draw @ 24V
2 mA
Total backplane power
1.11 W
Power dissipation, max
3.3 W @ 60 °C (140 °F)
Thermal dissipation
11.25 BTU/hr
Off-state leakage current, max
1 mA per point
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
203
Page 204
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OH8I (continued) Attribute
1756-OH8I
On-state voltage drop, max
2V DC @ 2 A
Current per point, max
2 A @ 60 °C (140 °F)
Current per module, max
8 A @ 60 °C (140 °F)
Surge current per point
4 A for 10 ms per point, repeatable every 1 s @ 60 °C (140 °F)
Load current, min
2 mA per point
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Fusing
Not protected. A fused IFM is recommended to help protect outputs.
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
North American temperature code
T4A
Enclosure type
None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-OH8I Attribute
1756-OH8I
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
204
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 205
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OH8I (continued) Attribute
1756-OH8I
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-OH8I Certification(1)
1756-OH8I
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
205
Page 206
1756 ControlLogix I/O Specifications
1756-ON8 ControlLogix 24V AC output module 1756-ON8
Simplified Schematic +5V
L1-0
Daisy Chain to Other RTBs 2
1
4
3
6
5
8
7
10
9
12
11
14
13
16
15
L1-0
OUT-0
L1-0
OUT-0 Group 0
ControlLogix Backplane Interface Display
L1-0
OUT-2
L1-0
Surge Current Chart
Not Used
L1-1
OUT-4
Current
L1-1 Group 1
OUT-5
L1-1
2A
43 ms
Group 1 OUT-6
18
17
20
19
L1-1
0
Group 0
OUT-3
L1-0
Surge
20 A
OUT-1
OUT-7
L1-1
Not Used
L2
Time L1
AC OUTPUT ST 0 1 2 3 4 5 6 7 O K
Technical Specifications - 1756-ON8 Attribute
1756-ON8
Outputs
8 (4 points/group)
Voltage category Operating voltage range Output delay time Off to On
24V AC 50/60 Hz (1)
10…30V AC, current >50 mA, 47…63Hz 16…30V AC, current <50 mA, 47…63Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz
On to Off
9.3 ms @ 60 Hz 11 ms @ 50 Hz
Current draw @ 5.1V
200 mA
Current draw @ 24V
2 mA
Total backplane power
1.07 W
206
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 207
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-ON8 (continued) Attribute
1756-ON8
Power dissipation, max
5.1 W @ 60 °C (140 °F)
Thermal dissipation
17.39 BTU/hr
Off-state leakage current, max
3 mA per point
On-state voltage drop, max
1.5V peak @ 2 A 6V peak @ load current < 50 mA
Current per point, max
2 A @ 60 °C (140 °F)
Current per module, max
5 A @ 30 °C (86 °F) linear derating 4 A @ 60 °C (140 °F) linear derating
Surge current per point
20 A for 43 ms per point, repeatable every 2 s @ 60 °C (140 °F)
Load current, min
10 mA per point
Commutating voltage
4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(2)
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Fusing
Not protected. A fused IFM is recommended to help protect outputs.
Removable terminal block
1756-TBNH 1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(3)
North American temperature code
T4A
IEC temperature code
T4
Enclosure type
None (open style)
(1) UL certification for 24V 50/60 Hz nominal. Rockwell Automation specified to 10…30V, 47…63 Hz. (2) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/s for loads under 50 mA. The commutating dv/dt rating of the module for loads 50…500 mA (OUTPUT to L2) is 4V/s maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 10…50 mA range, a resistor can be added AC across the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it dissipates (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50…500 mA range, the L1 AC waveform could be at fault. Be sure that the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-ON8 Attribute
1756-ON8
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
207
Page 208
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-ON8 (continued) Attribute
1756-ON8
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-ON8 Certification(1)
1756-ON8
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
208
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 209
1756 ControlLogix I/O Specifications
1756-OV16E ControlLogix DC (10…30V) electronically fused, sinking output module 1756-OV16E
Simplified Schematic Display
Optoisolation
DC-0(+)
1
4
3
6
5
8
7
10
9
12
11
14
13
16
15
18
17
20
19
OUT-0
OUT-3
OUT-0 Group 0
OUT-2
OUT-5
OUT-4
OUT-7
RTN OUT-0 ControlLogix Backplane Interface
2
OUT-1
Electronic Fuse Circuitry
OUT-6
DC-0(+)
RTN OUT-0
OUT-9
OUT-8
OUT-11
Surge Current Chart Group 1
Current
OUT-10
OUT-13
OUT-12
OUT-15
Surge
2A
Group 1
OUT-14
DC-1(+)
Continuous @ 60 °C (140 °F)
Group 0
RTN OUT-1
1A
0
+
10 ms Time
– DC COM
Daisy Chain to Other RTBs
Daisy Chain to Other RTBs
DC OUTPUT ST 0 1 2 3 4 5 6 7 O K ST 8 9 10111213 1415
FUSE
FUSE ELECTRONICALLYFUSED
Diagnostic Specifications - 1756-OV16E Attribute
1756-OV16E
Short trip
5 A for 20 ms @ 24V DC (output on, then short) 5 A for 20 ms @ 24V DC (output on into short)
Time stamp of diagnostics
±1 ms
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
209
Page 210
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OV16E Attribute
1756-OV16E
Outputs
16 electronically fused (8 points/group)
Pilot duty
1 A (DC-13/SR)
Voltage category
12/24V DC sink
Output delay time Off to On On to Off
75 μs nom/1 ms max 360 μs nom/1 ms max
Operating voltage range
10…30V DC
Current draw @ 5.1V
210 mA
Current draw @ 24V
2 mA
Total backplane power
1.12 W
Power dissipation, max
6.72 W @ 60 °C (140 °F)
Thermal dissipation
22.94 BTU/hr
Off-state leakage current per point, max
1 mA per point
On-state voltage drop, max
700 mV DC @ 1 A
Current per point, max
1 A @ 60 °C (140 °F)
Current per module, max
8 A @ 60 °C (140 °F)
Surge current per point
2 A for 10 ms per Point, repeatable every 2 s @ 60 °C (140 °F)
Load current, min
2 mA per point
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Fusing
Electronically fused per group
Removable terminal block
1756-TBNH 1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
North American temperature code
T4
IEC temperature code
T4
Enclosure type
None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
210
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016