Page 201

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OG16 Attribute

1756-OG16

Outputs

16 (8 points/group)

Voltage category

5V DC TTL (Low=True(1)

Operating voltage range

4.5…5.5V DC source, 50 mV P-P ripple max

Output delay time (resistive load) Off to On (5V-to-0V DC transition) On to Off (0V-to-5V DC transition)

45 μs nom/450 μs max 145 μs nom/700 μs max

Current draw @ 5.1V

210 mA

Current draw @ 24V

2 mA

Total backplane power

1.12 W

Power dissipation, max

1.5 W @ 60 °C (140 °F)

Thermal dissipation

5.2 BTU/hr @ 60 °C (140 °F)

Off-state leakage current per point, max

0.1 mA per point

On-state voltage drop, max

0.4V DC

Continuous current, max

24 mA

Load current per point, max

24 mA

Load current per module, max

384 mA

Load current

0.15 mA

Scheduled outputs

Synchronization within 16.7 s max, reference to the Coordinated System Time

States in Fault mode per point

Hold last state, On or Off (Off is default)

States in Program mode per point

Hold last state, On or Off (Off is default)

Isolation voltage

250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Fusing

Not protected. A fused IFM is recommended to help protect outputs.

Removable terminal block

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

Wire category

2(2)

North American temperature code

T5

IEC temperature code

T5

Enclosure type

None (open-style)

(1) TTL outputs are inverted (0 to +0.4V DC = low voltage = True = On.) Use a NOT instruction in your program to convert to traditional True - High logic. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

201

Page 202

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-OG16 Attribute

1756-OG16

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-OG16 Certification(1)

1756-OG16

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T5 X Gc

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

202

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 203

1756 ControlLogix I/O Specifications

1756-OH8I ControlLogix DC (90…146V) isolated output module Simplified Schematic

1756-OH81

DC-0 Isolated Wiring

+5V OUT-0

+

-

RTN OUT-0 +

ControlLogix Backplane Interface

-

Display Surge Current Chart Surge

4A

Current

Non-Isolated Wiring

Continuous @ 60 °C (140 °F) 2A

0

Daisy chain to other RTBs

Daisy chain to other RTBs

10 ms Time

DC-0 (+)

2

1

OUT-0

RTN OUT-0

4

3

OUT-0

DC-1 (+)

6

5

OUT-1

RTN OUT-1 DC-2 (+)

8

7

10

9

OUT-1 OUT-2

RTN OUT-2

12 11

OUT-2

DC-3 (+)

14 13

OUT-3

RTN OUT-3

16 15

OUT-3

DC-4 (+)

18 17

OUT-4

RTN OUT-4

20 19

OUT-4

DC-5 (+)

22 21

OUT-5

RTN OUT-5

24 23

OUT-5

DC-6 (+)

26 25

OUT-6

RTN OUT-6

28 27

OUT-6

DC-7 (+)

30 29

OUT-7

RTN OUT-7

32 31

OUT-7

Not used

34 33

Not used

Not used

36 35

Not used

+

– DC COM

DC OUTPUT ST 0 1 2 3 4 5 6 7 O K

Technical Specifications - 1756-OH8I Attribute

1756-OH8I

Outputs

8 individually isolated

Voltage category

120V DC sink/source

Operating voltage range

90…146V DC

Output delay time Off to On On to Off

2 ms max 2 ms max

Current draw @ 5.1V

210 mA

Current draw @ 24V

2 mA

Total backplane power

1.11 W

Power dissipation, max

3.3 W @ 60 °C (140 °F)

Thermal dissipation

11.25 BTU/hr

Off-state leakage current, max

1 mA per point

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

203

Page 204

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OH8I (continued) Attribute

1756-OH8I

On-state voltage drop, max

2V DC @ 2 A

Current per point, max

2 A @ 60 °C (140 °F)

Current per module, max

8 A @ 60 °C (140 °F)

Surge current per point

4 A for 10 ms per point, repeatable every 1 s @ 60 °C (140 °F)

Load current, min

2 mA per point

Scheduled outputs

Synchronization within 16.7 s max, reference to the Coordinated System Time

States in Fault mode per point

Hold last state, On or Off (Off is default)

States in Program mode per point

Hold last state, On or Off (Off is default)

Isolation voltage

250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Fusing

Not protected. A fused IFM is recommended to help protect outputs.

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(1)

North American temperature code

T4A

Enclosure type

None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-OH8I Attribute

1756-OH8I

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

204

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 205

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-OH8I (continued) Attribute

1756-OH8I

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-OH8I Certification(1)

1756-OH8I

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

205

Page 206

1756 ControlLogix I/O Specifications

1756-ON8 ControlLogix 24V AC output module 1756-ON8

Simplified Schematic +5V

L1-0

Daisy Chain to Other RTBs 2

1

4

3

6

5

8

7

10

9

12

11

14

13

16

15

L1-0

OUT-0

L1-0

OUT-0 Group 0

ControlLogix Backplane Interface Display

L1-0

OUT-2

L1-0

Surge Current Chart

Not Used

L1-1

OUT-4

Current

L1-1 Group 1

OUT-5

L1-1

2A

43 ms

Group 1 OUT-6

18

17

20

19

L1-1

0

Group 0

OUT-3

L1-0

Surge

20 A

OUT-1

OUT-7

L1-1

Not Used

L2

Time L1

AC OUTPUT ST 0 1 2 3 4 5 6 7 O K

Technical Specifications - 1756-ON8 Attribute

1756-ON8

Outputs

8 (4 points/group)

Voltage category Operating voltage range Output delay time Off to On

24V AC 50/60 Hz (1)

10…30V AC, current >50 mA, 47…63Hz 16…30V AC, current <50 mA, 47…63Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz

On to Off

9.3 ms @ 60 Hz 11 ms @ 50 Hz

Current draw @ 5.1V

200 mA

Current draw @ 24V

2 mA

Total backplane power

1.07 W

206

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 207

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-ON8 (continued) Attribute

1756-ON8

Power dissipation, max

5.1 W @ 60 °C (140 °F)

Thermal dissipation

17.39 BTU/hr

Off-state leakage current, max

3 mA per point

On-state voltage drop, max

1.5V peak @ 2 A 6V peak @ load current < 50 mA

Current per point, max

2 A @ 60 °C (140 °F)

Current per module, max

5 A @ 30 °C (86 °F) linear derating 4 A @ 60 °C (140 °F) linear derating

Surge current per point

20 A for 43 ms per point, repeatable every 2 s @ 60 °C (140 °F)

Load current, min

10 mA per point

Commutating voltage

4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(2)

Scheduled outputs

Synchronization within 16.7 s max, reference to the Coordinated System Time

States in Fault mode per point

Hold last state, On or Off (Off is default)

States in Program mode per point

Hold last state, On or Off (Off is default)

Isolation voltage

250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Fusing

Not protected. A fused IFM is recommended to help protect outputs.

Removable terminal block

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(3)

North American temperature code

T4A

IEC temperature code

T4

Enclosure type

None (open style)

(1) UL certification for 24V 50/60 Hz nominal. Rockwell Automation specified to 10…30V, 47…63 Hz. (2) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/s for loads under 50 mA. The commutating dv/dt rating of the module for loads 50…500 mA (OUTPUT to L2) is 4V/s maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 10…50 mA range, a resistor can be added AC across the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it dissipates (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50…500 mA range, the L1 AC waveform could be at fault. Be sure that the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-ON8 Attribute

1756-ON8

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

207

Page 208

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-ON8 (continued) Attribute

1756-ON8

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-ON8 Certification(1)

1756-ON8

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

208

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 209

1756 ControlLogix I/O Specifications

1756-OV16E ControlLogix DC (10…30V) electronically fused, sinking output module 1756-OV16E

Simplified Schematic Display

Optoisolation

DC-0(+)

1

4

3

6

5

8

7

10

9

12

11

14

13

16

15

18

17

20

19

OUT-0

OUT-3

OUT-0 Group 0

OUT-2

OUT-5

OUT-4

OUT-7

RTN OUT-0 ControlLogix Backplane Interface

2

OUT-1

Electronic Fuse Circuitry

OUT-6

DC-0(+)

RTN OUT-0

OUT-9

OUT-8

OUT-11

Surge Current Chart Group 1

Current

OUT-10

OUT-13

OUT-12

OUT-15

Surge

2A

Group 1

OUT-14

DC-1(+)

Continuous @ 60 °C (140 °F)

Group 0

RTN OUT-1

1A

0

+

10 ms Time

– DC COM

Daisy Chain to Other RTBs

Daisy Chain to Other RTBs

DC OUTPUT ST 0 1 2 3 4 5 6 7 O K ST 8 9 10111213 1415

FUSE

FUSE ELECTRONICALLYFUSED

Diagnostic Specifications - 1756-OV16E Attribute

1756-OV16E

Short trip

5 A for 20 ms @ 24V DC (output on, then short) 5 A for 20 ms @ 24V DC (output on into short)

Time stamp of diagnostics

±1 ms

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

209

Page 210

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-OV16E Attribute

1756-OV16E

Outputs

16 electronically fused (8 points/group)

Pilot duty

1 A (DC-13/SR)

Voltage category

12/24V DC sink

Output delay time Off to On On to Off

75 μs nom/1 ms max 360 μs nom/1 ms max

Operating voltage range

10…30V DC

Current draw @ 5.1V

210 mA

Current draw @ 24V

2 mA

Total backplane power

1.12 W

Power dissipation, max

6.72 W @ 60 °C (140 °F)

Thermal dissipation

22.94 BTU/hr

Off-state leakage current per point, max

1 mA per point

On-state voltage drop, max

700 mV DC @ 1 A

Current per point, max

1 A @ 60 °C (140 °F)

Current per module, max

8 A @ 60 °C (140 °F)

Surge current per point

2 A for 10 ms per Point, repeatable every 2 s @ 60 °C (140 °F)

Load current, min

2 mA per point

Scheduled outputs

Synchronization within 16.7 s max, reference to the Coordinated System Time

States in Fault mode per point

Hold last state, On or Off (Off is default)

States in Program mode per point

Hold last state, On or Off (Off is default)

Isolation voltage

250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Fusing

Electronically fused per group

Removable terminal block

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(1)

North American temperature code

T4

IEC temperature code

T4

Enclosure type

None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

210