For the Allen-Bradley 1756-IB16, Allen-Bradley 1756-OB16E and Allen-Bradley 1756-TBNH
Page 211
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OV16E Attribute
1756-OV16E
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-OV16E Certification(1)
1756-OV16E
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
211
Page 212
1756 ControlLogix I/O Specifications
1756-OV32E ControlLogix DC (10…30V) electronically fused, sinking output module 1756-OV32E
Simplified Schematic Display
Optoisolation
DC-0(+)
Daisy Chain to Other RTBs
OUT-0
Group 0
RTN OUT-0 ControlLogix Backplane Interface
Electronic Fuse Circuitry
Surge Current Chart Group 1
Surge
Current
2A
Continuous @ 60 °C (140 °F) 1A
Daisy Chain to Other RTBs OUT-1 OUT-3 OUT-5
2
1
4
3
6
5
OUT-7 OUT-9 OUT-11
8
7
10
9
OUT-13 OUT-15 DC-0(+)
14 13
OUT-17 OUT-19 OUT-21 OUT-23 OUT-25 OUT-27
20 19
OUT-29 OUT-31 DC-1(+)
32 31
18 17
OUT-16 OUT-18 OUT-20
22 21 24 23
OUT-22 OUT-24 OUT-26
26 25 28 27 30 29
OUT-28 OUT-30 RTN OUT-1
34 33 36 35
_
10 ms DC COM
DC OUTPUT ST 0 1 2 3 4 5 6 7 1 11 11 1 ST 8 9 0 1 2 3 4 5 1 1 1 12 22 2 ST 6 7 8 9 0 1 2 3 2 2 2 22 23 3 ST 4 5 6 7 8 9 0 1
F 0 O K F 1
ELECTRONIC FUSING
Diagnostic Specifications - 1756-OV32E Attribute
1756-OV32E
Short trip
5 A for 20 ms @ 24V DC (output on then short) 5 A for 20 ms @ 24V DC (output into short)
Time stamp of diagnostics
±1 ms
Technical Specifications - 1756-OV32E Attribute
1756-OV32E
Outputs
32 electronically fused (16 points/group)
Voltage category
12/24V DC sink
Operating voltage range
10…30V DC
Output delay time (24V to 0V DC transition) Off to On On to Off
75 μs nom/300 μs max 230 μs nom/1 ms max
Current draw @ 5.1V
390 mA
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Group 0
OUT-12 OUT-14 RTN OUT-0
16 15
Time
212
OUT-6 OUT-8 OUT-10
12 11
+ 0
OUT-0 OUT-2 OUT-4
Group 1
Page 213
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OV32E (continued) Attribute
1756-OV32E
Current draw @ 24V
2 mA
Total backplane power
2.04 W
Power dissipation, max
5.88 W @ 60 °C (140 °F)
Thermal dissipation
20.1 BTU/hr
Off-state leakage current per point, max
1 mA per point
On-state voltage drop, max
350 mV DC @ 0.5 A
Current per point, max
0.5 A @ 50 °C (122 °F) linear derating 0.35 A @ 60 °C (140 °F)
Current per group, max
8 A @ 50 °C (122 °F) linear derating 5 A @ 60 °C (140 °F)
Current per module, max
16 A @ 50 °C (122 °F) linear derating 10 A @ 60 °C (140 °F)
Surge current per point
2 A for 10 ms per point, repeatable every 2 s @ 60 °C (140 °F)
Load current, min
2 mA per output
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Fusing
Electronically fused per group
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
North American temperature code
T4
IEC temperature code
T4
Enclosure type
None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-OV32E Attribute
1756-OV32E
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
213
Page 214
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OV32E (continued) Attribute
1756-OV32E
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-OV32E Certification(1)
1756-OV32E
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
214
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 215
1756 ControlLogix I/O Specifications
1756-OW16I ControlLogix AC (10…240V) DC (5…125V) isolated contact module Simplified Schematic
1756-OW161 Isolated Wiring
+24V L1
Display ControlLogix Backplane Interface
OUT
Additional jumper bars are available as catalog number 1756-JMPR.
RELAY OUTPUT
L1-0
L1-0 L1-1 L1-2 L1-2 L1-3 DC-4 (+) L1-4 L1-5 L1-6 L1-7 Jumper Bar (Cut to Length) L1-8 L1-9 L1-10 L1-11 Nonisolated L1-12 Wiring L1-13 L1-14 L1-15 L1-15 L1 Not Used
2
1
4
3
6
5
8
7
10
9
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
L2-0
OUT-0 OUT-1 N.O. OUT-2 N.O. OUT-3 N.O. OUT-4 N.O. OUT-5 N.O. OUT-6 N.O. OUT-7 N.O. OUT-8 N.O. OUT-9 N.O. OUT-10 N.O. OUT-11 N.O. OUT-12 N.O. OUT-13 N.O. OUT-14 N.O. OUT-15 N.O Not Used Not Used
L2-2 DC-4 (-)
L2 Daisy Chain to Other RTBs
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K
Technical Specifications - 1756-OW16I Attribute
1756-OW16I
Outputs
16 N.O. individually isolated
Pilot duty
C300/R150
Operating voltage range
5…125V DC 10…240V AC
Output voltage range (load dependent)
1 A @ 5…30V DC 0.5 A @ 48V DC 0.22 A @ 125V DC 1.5 A @ 120V AC 50/60 Hz 0.75 A @ 240V AC 50/60 Hz
Output delay time Off to On On to Off
10 ms max 10 ms max
Current draw @ 5.1V
150 mA
Current draw @ 24V
150 mA
Total backplane power
4.4 W
Power dissipation, max
4.5 W @ 60 °C (140 °F)
Thermal dissipation
15.35 BTU/hr
Off-state leakage current per point, max
1.5 mA per point
Minimum load current
10 mA per point
Initial contact resistance, max
100 m @ 6V 1 A
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
215
Page 216
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OW16I (continued) Attribute
1756-OW16I
Switching frequency, max
1 operation/3 s (0.3 Hz at rated load)
Bounce time, mean
1.2 ms
Expected contact life
300 kHz resistive 100 kHz inductive
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Fusing
Not protected. A fused IFM can be used to help protect outputs. See publication 1492-TD008. However, the ControlLogix system has been agency certified using only the ControlLogix RTBs, that is, 1756-TBCH, 1756-TBNH, 1756-TBSH, and 1756-TBS6H. Any application that requires agency certification of the ControlLogix system using other wiring termination methods can require application-specific approval by the certifying agency.
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
North American temperature code
T4A
Enclosure type
None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-OW16I Attribute
1756-OW16I
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
216
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 217
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OW16I (continued) Attribute
1756-OW16I
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Oscillatory surge withstand IEEE C37.90.1
3 kV
Certifications - 1756-OW16I Certification(1)
1756-OW16I
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
217
Page 218
1756 ControlLogix I/O Specifications
1756-OX8I ControlLogix AC (10…240V) DC (5…125V) isolated contact module Simplified Schematic
1756-OX81
+24V
ControlLogix Backplane Interface Display
RELAY OUTPUT
Isolated Wiring
2
1
L1-0
4
3
L1-0 L1-0 L1-1 L1-1 OUT-0 N.C. DC-2 (+) L1-2 L1-2 L1-3 Jumper Bar OUT-0 N.O. L1-3 (Cut to Length) L1-4 L1-4 L1-5 L1-5 L1-6 Nonisolated Wiring L1-6 L1-7 L1-7 Additional jumper bars are available L1-7 L1 as catalog number 1756-JMPR. Not Used
L1-0
6
5
8
7
10
9
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
L2-0
DC-2 (-)
L2 Daisy Chain to Other RTBs
ST 0 1 2 3 4 5 6 7 O K
Technical Specifications - 1756-OX8I Attribute
1756-OX8I
Outputs
8 N.O. 8 N.C. individually isolated (two points per group)
Pilot duty
C300/R150
Operating voltage range
5…125V DC 10…240V AC
Contact current rating
1 A @ 5…30V DC 0.5 A @ 48V DC 0.22 A @ 125V DC 1.5 A @ 120V AC 50/60 Hz 0.75 A @ 240VAC 50/60 Hz
Output delay time Off to On On to Off
13 ms max 13 ms max
Current draw @ 5.1V
100 mA
Current draw @ 24V
100 mA
Total backplane power
2.9 W
Power dissipation, max
3.1 W @ 60 °C (140 °F)
Thermal dissipation
10.57 BTU/hr
Off-state leakage current per point, max
0 mA
Minimum load current
10 mA per point
Initial contact resistance, max
100 m @ 6V 1 A
218
OUT-0 N.C. OUT-0 N.O. OUT-1 N.C. OUT-1 N.O. OUT-2 N.C. OUT-2 N.O. OUT-3 N.C. OUT-3 N.O. OUT-4 N.C. OUT-4 N.O. OUT-5 N.C. OUT-5 N.O. OUT-6 N.C. OUT-6 N.O. OUT-7 N.C. OUT-7 N.O Not Used Not Used
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 219
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-OX8I (continued) Attribute
1756-OX8I
Switching frequency, max
1 operation/3 s (0.3 Hz at rated load)
Bounce time, mean
1.2 ms
Expected contact life
300 kHz resistive 100 kHz inductive
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Fusing
Not protected. A fused IFM is recommended to help protect outputs.
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
North American temperature code
T4A
Enclosure type
None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-OX8I Attribute
1756-OX8I
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
219
Page 220
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-OX8I (continued) Attribute
1756-OX8I
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Oscillatory surge withstand IEEE C37.90.1
3 kV
Certifications - 1756-OX8I Certification(1)
1756-OX8I
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
220
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016