For the Allen-Bradley 1756-IB16, Allen-Bradley 1756-OB16E and Allen-Bradley 1756-TBNH

Page 221

1756 ControlLogix I/O Specifications

1756-CFM ControlLogix configurable flowmeter module 1756-CFM Standard Magnetic Pickup 2 4

3

6

5

8

7

10

9

–

12

11

Shield Ground

13

Not Used 16

15

18 20

17

Customer VCC

19

10

9

12

11

14

13

16

15

18

17

20

19

Z1 RET F1 F1 Return Not Used Not Used

Output 0

Output 1

Customer VCC

7

Not Used

Not Used

Output 0

8

Z1 5V DC

Not Used

Not Used 14

5

F0 Return

F1 Return

Not Used

6

F0

F1

F0 Return

3

Z0 Return

Z1 RET

F0

Z1 12-24V DC 4

Z0 5V DC

Z1 5V DC

Z0 Return

1

Z0 12-24V DC

Z1 12-24V DC

Z0 5V DC

+

2

1

Z0 12-24V DC

Input Device

1756-CFM Standard Output

Output 1

Customer VCC

Customer Common

+ Customer VCC

Customer Common

Load

–

+

Customer Common Customer Common

+ Load

–

–

This wiring diagram can be used in applications with 50 mV (magnetic pickup), 1.3V (TTL), or 4V (preamp level) thresholds. You must use RSLogix 5000® software to choose the appropriate threshold level for your specific application.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

221

Page 222

1756 ControlLogix I/O Specifications

The 1756-CFM module provides Totalizer mode for metering applications, or high-speed frequency measurements for speed or rate control applications, on two channels connected to flowmeters. 1756-CFM Standard Prover/Store Count 12-24V DC

2

+

1

Z1 1224V DC

Z0 12-24V DC

–

4

3

6

5

8

7

Z0 5V DC Shield Ground

Input Device

Z1 5V DC

Z0 Return

Z1 RET

F0

+ –

10

9

12

11

14

13

F0 Return Shield Ground

METERING F1 F1 Return

Not Used

Not Used

Not Used

Not Used 16

15

18

17

20

19

Output 0

Output 1 Customer Common

Customer VCC

Customer Common

Customer VCC

• Detectors 1 and 2 must be wired in parallel. • Customer VCC can be used to power detectors. In this case, though, the maximum current on the wiring arm must be less than 4 A. • This wiring example shows a 12-24V DC standard prover that is connected to the module. If you use a 5V DC standard prover, make sure that the positive wire is connected to the 5V terminal (such as Z0 5V DC).

Technical Specifications - 1756-CFM Attribute

1756-CFM

Inputs

4 (2 per channel)

Inputs per channel

Two flowmeter (F) inputs used for all modes Two gate inputs used in Totalizer mode for prover/store count

Outputs

2 current sourcing

Current draw at 5.1V

300 mA

Current draw at 24V

16 mA

Total backplane power

1.7 W

Power dissipation, max

6 W @ 60 °C (140 °F)

Thermal dissipation

20.4 BTU/hr

Isolation voltage

250V (continuous), reinforced insulation type, I/O-to-backplane 250V (continuous), basic insulation type, I/O group-to-group Routine tested at 1900V DC for 2 s

Module keying

Electronic, software configurable

Removable terminal block

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

222

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

F 0

Z 0

F 1

O O 0 1

DC I/O

Z 1

O K

Page 223

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-CFM (continued) Attribute

1756-CFM

Wire category

2 on signal ports 1 on power ports(1)

North American temperature code

T4

Enclosure type

None (open-style)

Totalizer fill and prover

Yes

High resolution, max

100 kHz

Frequency

0.0005 Hz resolution

Reverse polarity protection

Outputs only

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Input Specifications - 1756-CFM Attributes

1756-CFM

Inputs

4 (2 per channel)

Inputs per channel

Two flowmeter (F) inputs used for all modes Two gate inputs used in Totalizer mode for prover/store count

Count range, max

2, 147, 483, 647

Input frequency, max

100 kHz @ flowmeter inputs (overrange occurs at 100 kHz)

Flowmeter input voltage

±30V, selectable input thresholds of 50 mV, 1.3V, and 4V: • ±30V peak unterminated open circuit voltage, magnetic pickup • TTL compatible, input voltage >1.3V DC is Logic 1 and -0.7…1.3V DC is Logic 0 • 12…24V DC powered preamp output, 4V DC threshold

Flowmeter input impedance

5 k ±30% resistive

Filtering (inputs F0 & F1)

Firmware selectable: High-speed 100 kHz or low-pass filter for frequencies < 70 Hz

Gate input voltage range

5V operation: 4.5…5.5V DC 12/24V operation: 10…26.4V DC

Gate input on-state current, min

4 mA

Gate input on-state current, nom

15 mA

Mechanical filter debouncing (Z0 & Z1 Inputs)

Software selectable

Input sampling period

User selectable

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

223

Page 224

1756 ControlLogix I/O Specifications

Output Specifications - 1756-CFM Attribute

1756-CFM

Outputs

2 current sourcing

Output voltage source

Customer supplied (1)

Output voltage range, nom

5V operation: 4.5…5.5V DC for 3…20 mA load per point 12/24V operation: 10…31.2V DC for 40 mA…1 A load per point

Output type

IEC 1 A 24V DC

Output Current per point

(1)

1 A @ 10…31.2V DC 20 mA @ 4.5…5.5V DC(2)

Surge current

2 A for 50 ms, repeatable every 2 s

Off-state leakage current, max

< 300 A @ 31.2V DC

On-state voltage drop, max

0.6 x current

Output control

Any number of outputs is assignable to any of two flowmeter channels Each output can have 2 “turn-on” and “turn-off” preset values

Output switching time

< 50 s turn on, <300 s turn off Outputs triggered by Total; all other “turn-on” and “turn-off” times <1 ms

Overload current

Electronic (< 4 A)

Output short circuit protection

Electronic (No indication of fault. Remove overload and toggle output on/off to restore.)

Output reverse polarity protection

Yes (If wired incorrectly, module outputs can be permanently disabled.)

(1) UL rating for 24V DC, 24VA. (2) All outputs can be on simultaneously without derating.

Environmental Specifications - 1756-CFM Attribute

1756-CFM

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1k Hz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

224

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 225

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-CFM (continued) Attribute

1756-CFM

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on unshielded output and power ports ±4 kV at 5 kHz on shielded input ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on unshielded output and power ports ±2 kV line-earth (CM) on shielded input ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on shielded signal ports

Certifications - 1756-CFM Certification(1)

1756-CFM

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

225

Page 226

1756 ControlLogix I/O Specifications

1756-HSC ControlLogix high-speed counter module 1756-HSC to Allen-Bradley® 845 Incremental Encoder Z0 (12...24V)

2

1

Z1 (12...24V)

Z0 (5V) Z0 (RET) B0 (12..24V) B0 (5V)

4

3

Z1 (5V) Z1 (RET) B1 (12...24V) B1 (5V)

6

5

8

7

10

9

B0 (RET) A0 (12...24V) A0 (5V)

12 11

A0 (RET) Not Used Not Used

18 17

Not Used Out 0 Out 1

24 23

14 13 16 15

20 19 22 21

26 25 28 27

COMMON 0 COMMON 0 COMMON 0

30 29

DC-0(+)

36 35

32 31 34 33

B1 (RET) A1 (12...24V) A1 (5V) A1 (RET) Not Used Not Used

1756-HSC to Allen-Bradley Series 10,000 Photoelectric Sensor Allen-Bradley® Bulletin 845 Incremental Encoder

Green Black Blue Black White

Differential Line Driver Output

Black

Not Used Out 2 Out 3 COMMON 1 COMMON 1 COMMON 1 DC-1(+)

Z0 (12...24V) Z0 (5V) Z0 (RET) B0 (12...24V) B0 (5V)

2

1

4

3

6

5

8

7

10

9

B0 (RET) A0 (12...24V) A0 (5V)

12 11

A0 (RET) Not Used Not Used

18 17

Not Used Out 0 Out 1

24 23

COMMON 0 COMMON 0 COMMON 0

30 29

DC-0(+)

36 35

Z1 (12...24V)

Whit

Photoswitch Series 10,000

Z1 (5V) Blue Z1 (RET) B1 (12...24V) B1 (5V)

10-30V DC Not Used

B1 (RET) A1 (12...24V) Black A1 (5V)

14 13 16 15

A1 (RET) Not Used Not Used

20 19 22 21

Jumper 12...24V

Not Used Out 2

26 25

Out 3 COMMON 1 COMMON 1 COMMON 1 DC-1(+)

28 27

32 31 34 33

The 1756-HSC module provides four high-speed, output-switching, on-off windows. The module uses pulses for counting and frequency. 1756-HSC to Allen-Bradley 872 3-wire DC Proximity Sensor Allen-Bradley Bulletin 872 3-wire DC Proximity Jumpers Sensor

12...24V DC

Black Blue

12...24V DC Return

226

Z0 (12...24V)

2

1

Z1 (12...24V)

Z0 (5V) Z0 (RET) B0 (12...24V) B0 (5V)

4

3

6

5

8

7

10

9

Z1 (5V) Z1 (RET) B1 (12...24V) B1 (5V)

B0 (RET) A0 (12...24V) A0 (5V)

12 11

A0 (RET) Not Used Not Used

18 17

Not Used Out 0 Out 1

24 23

COMMON 0 COMMON 0 COMMON 0

30 29

DC-0(+)

36 35

14 13 16 15

20 19 22 21

26 25 28 27

32 31 34 33

B1 (RET) A1 (12...24V) A1 (5V) A1 (RET) Not Used Not Used

COUNTER A B Z 0 0 0 O O 0 1

Not Used Out 2 Out 3 COMMON 1 COMMON 1 COMMON 1 DC-1(+)

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

A B Z 1 1 1 O K O O 2 3

DC I/O

Page 227

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-HSC Attribute

1756-HSC

Number of counters

2

Inputs per counter

3 (A, B, Z for gate/reset)

Outputs

4 (2 points/group)

Operating voltage range(1)

5V operation: 4.5…5.5V DC 12/24V operation: 10…26.4V DC

Current draw at 5.1V

300 mA

Current draw at 24V

3 mA

Total backplane power

1.6 W

Power dissipation, max

5.6 W @ 60 °C (140 °F)

Thermal dissipation

19.1 BTU/hr

Isolation voltage

125V (continuous), basic insulation type, input group-to-backplane 30V (continuous), basic insulation type, input group-to-input group Routine tested at 1900V DC for 2 s

Module keying

Electronic, software configurable

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

2 on signal ports 1 on power ports(2)

North American temperature code

T4

IEC temperature code

T4

Enclosure type

None (open-style)

(1) UL rating is 24V DC. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Input Specifications - 1756-HSC Attribute

1756-HSC

Number of counters

2

Inputs per counter

3 (A, B, Z for gate/reset)

Input frequency, max

1 MHz in counter modes (A input) 500 kHz in rate measurement mode (A input) 250 kHz in encoder mode (A/B inputs, X1 or X4) 70 Hz with filter enabled

Count range

0…16, 777, 214

Counting frequency, max

1000 kHz

Input current, min

4 mA

Input current, nom

15 mA

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

227

Page 228

1756 ControlLogix I/O Specifications

Output Specifications - 1756-HSC Attribute

1756-HSC

Outputs

4 (2 per common)

Output delay time Off to On On to Off

20 s nom/50 s max 60 s nom/300 s max

Off-state leakage current per point, max

300 A

On-state voltage drop, max

0.55V

Output current rating, per point(1)

20 mA @ 4.5…5.5V DC 1.0 A @ 10…31.2V DC

Current limit

<4A

Surge current per point

2 A for 10 ms every 1 s @ 60 °C (140 °F)

Load current per point, min

5V operation: 3 mA 12/24V operation: 40 mA

Output control

Up to two outputs are assigned to each counter channel Each output can have two ‘turn-on’ and ’turn-off’ preset values

Short circuit protection

Electronic (Remove overload and toggle On/Off to restore.)

Reverse polarity protection

Yes (If wired incorrectly, module outputs can be permanently disabled.)

Counter, max

1 MHz

Rate measurement, max

500 kHz

Encoder, max

250 kHz

Debounce filter, max

70 Hz

(1) UL rating is 24V DC, 24VA.

Environmental Specifications - 1756-HSC Attribute

1756-HSC

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating -40…+85 °C (-40…+185 °F) IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

228

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 229

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-HSC (continued) Attribute

1756-HSC

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on power ports ±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports ±2 kV line-earth (CM) on shielded ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on shielded signal ports

Certifications - 1756-HSC Certification(1)

1756-HSC

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

229

Page 230

1756 ControlLogix I/O Specifications

1756-LSC8XIB8I ControlLogix 10…30V low-speed counter module Simplified Schematic Current Limiter

Opto-isolator

IN-x or CTR-x

Display ControlLogix Backplane Interface

GND-x or CTR GND-x

1756-LSC8XIB8I

Isolated Wiring GND-0 GND-1

2

1

IN-0

DC-1 (-)

4

3

IN-1

DC-1 (+)

DC-2 (-)

GND-2

6

5

IN-2

DC-2 (+)

GND-3

8

7

IN-3

Source Input Wiring

GND-4

10

9

IN-4

DC-5 (-)

GND-5

12 11

IN-5

DC-6 (-)

GND-6

14 13

IN-6

Jumper Bar Cut to Length

Nonisolated Wiring

DC (-)

GND-7

16 15

IN-7

CTR-GND-0

18 17

CTR-0

CTR GND-1

20 19

CTR GND-2

22 21

CTR-1 CTR-2

CTR GND- 3

24 23

CTR-3

CTR GND-4

26 25

CTR-4

CTR GND- 5

28 27

CTR-5

CTR GND-6

30 29

CTR-6

CTR GND- 7

32 31

CTR-7

CTR GND-7

34 33

Not Used

36 35

Not Used Not Used

Additional jumper bars can be purchased by using catalog number 1756-JMPR.

Daisy Chain to Other RTBs COUNTER

ST

01234567

CTR

01234567

O K

PEER DEVICE

230

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

(+) DC-5 (+) (+) DC-6 (+) Sink Input Wiring

See page 231 for proximity sensor wiring.

DC (+)