The text of a spec sheet · part 24 of 25
1756 ControlLogix I/O Specifications, Technical Data, pages 231 to 240
Pages 231 to 240 of 242
The original document is the PDF (7.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-IB16, Allen-Bradley 1756-OB16E and Allen-Bradley 1756-TBNH
Page 231
1756 ControlLogix I/O Specifications
The following diagram shows how to wire a proximity sensor to the module’s eight counters or eight hardware inputs. Counters use incoming pulses for counts and frequency with two user-configurable On/Off windows per counter. Hardware inputs provide standard input or counter-control functionality.
Allen-Bradley Bulletin 872 3-wire DC Proximity Sensor - Normally Open PNP
12…24V DC
Black
Brown
Module Sink Input Wiring
1756-LSC8XIB8I Blue
12…24V DC Return
GND-0 GND-1
2
1
IN-0
4
3
IN-1
GND-2
6
5
IN-2
GND-3
8
7
IN-3 Counter Control Hardware
GND-4
10
9
IN-4 Inputs 0…7
GND-5
12 11
IN-5
GND-6
14 13
IN-6
GND-7
16 15
IN-7
CTR-GND-0
18 17
CTR-0
Allen-Bradley Bulletin 872 3-wire DC Proximity Sensor - Normally Open NPN
Brown
12…24V DC
Blue
12…24V DC Return
Black
CTR GND-1
20 19
CTR GND-2
22 21
CTR-1 CTR-2
CTR GND- 3
24 23
CTR-3 Counters 0…7
CTR GND-4
26 25
CTR-4
CTR GND- 5
28 27
CTR-5
CTR GND-6
30 29
CTR-6
CTR GND- 7
32 31
CTR-7
CTR GND-7
34 33
Not Used
36 35
Not Used Not Used
Module Source Input Wiring
Counter Specifications - 1756-LSC8XIB8I Attribute
1756-LSC8XIB8I
Number of counters
8 individually isolated
Counting frequency, max
40 kHz
Count range
0…2,147,483,648 (31-bit counter)
Voltage category
12/24V DC sink/source
Operating voltage range
10…30V DC
Off-state voltage, max
5V
Off-state current, max
1.5 mA
On-state current, min
2 mA @ 10V DC
On-state current, max
5 mA @ 30V DC
Change of state
Enter or exit user-configurable windows
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
231
Page 232
1756 ControlLogix I/O Specifications
Hardware Input Specifications - 1756-LSC8XIB8I Attribute
1756-LSC8XIB8I
Inputs
8 individually isolated, standard input or counter-control functionality
Voltage category
12/24V DC sink/source
Operating voltage range
10…30V DC
Input voltage, nom
24V DC
Input delay time (screw to backplane) Off to On On to Off
14 μs nom/23 μs max + user-configurable filter time of 0…30,000 μs 14 μs nom/23 μs max + user-configurable filter time of 0…30,000 μs
Off-state voltage, max
5V
Off-state current, max
1.5 mA
On-state current, min
2 mA @ 10V DC
On-state current, max
5 mA @ 30V DC
Change of state
Any transition
Module Specifications - 1756-LSC8XIB8I Attribute
1756-LSC8XIB8I
Current draw @ 5.1V
275 mA
Current draw @ 24V
3 mA
Total backplane power
1.47 W
Power dissipation
3.8 W @ 60 °C (140 °F)
Thermal dissipation
12.97 BTU/hr
Input impedance, max
Six k @ 30V DC
Cyclic update time
200 μs…750 ms
Isolation voltage
250V (continuous), reinforced insulation type, inputs-to-backplane 250V (continuous), basic insulation type, input-to-input Type tested @ 2300V AC for 60 s inputs-to-backplane Type tested @ 1500V AC for 60 s input-to-input
Module keying
Electronic, software configurable
Removable terminal block housing
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire category
1 on signal ports(1)
North American temperature code
T4A
IEC temperature code
T4
Enclosure type
None (open-style)
Reverse polarity protection
Yes
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
232
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 233
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-LSC8XIB8I Attribute
1756-LSC8XIB8I
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-LSC8XIB8I Certification(1)
1756-LSC8XIB8I c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
233
Page 234
1756 ControlLogix I/O Specifications
1756-PLS ControlLogix programmable limit switch module 1756-PLS Inputs - Left Side 2
1756-PLS Outputs - Right Side
1
OUTPUT 0
INPUT 0 4
3
6
5
8
7
10
9
12
11
14
13
16
15
OUTPUT 1
INPUT 1
OUTPUT 3
INPUT 3
DC PWR 0...3
17
20
19
OUTPUT 7
8
7
10
9
12
11
14
13
16
15
18
17
20
19
INPUT 9 INPUT 10 INPUT 11 DC COM 8...11 INPUT 12
OUTPUT 13
+
INPUT 7
DC PWR 4...7
5
OUTPUT 12
INPUT 6 18
6
INPUT 8
DC PWR 8...11
10...30V DC
INPUT 5
OUTPUT 6
3
OUTPUT 11
_
INPUT 4
OUTPUT 5
4
OUTPUT 10
DC COM 0...3
OUTPUT 4
1
OUTPUT 9
+
INPUT 2
OUTPUT 2
2
OUTPUT 8
INPUT 13 INPUT 14
OUTPUT 14 OUTPUT 15
_
DC PWR 12...15
DC COM 4-...7
INPUT 15 DC COM 12...15
+ _
The 1756-PLS module supports enhanced packaging applications. The module requires three contiguous slots in the chassis. 1756-PLS Resolver 2
1
4
3
6
5
8
7
10
9
12
11
14
13
16
15
18
17
Do Not Use
Do Not Use
Do Not Use
Do Not Use
Do Not Use
Do Not Use
Do Not Use
Do Not Use
Do Not Use
Do Not Use
Do Not Use
Do Not Use
Allen-Bradley Resolver 846-SJDA1CG-R3-C
F (S3)
E (S2) G (S4)
234
Do Not Use
Sine +
D (S1)
Do Not Use
Sine – Cosine +
Reference + 20
Cosine –
19
Reference –
A (R1) B (R2)
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 235
1756 ControlLogix I/O Specifications
Indicator for Left Slot I/O Module
Indicator for Left Resolver Module
Indicator for Right Slot I/O Module
PROG. LIMIT SWITCH
PROG. LIMIT SWITCH
PROG. LIMIT SWITCH
OUT 0 1 2 3 4 5 6 7
O K
O IN 0 1 2 3 4 5 6 7 K
DC I/O
OUT 8 9 10 11 12 13 14 15
O IN 8 9 10 11 12 13 14 15 K
RESOLVER
DC I/O
Technical Specifications - 1756-PLS Attribute
1756-PLS
Module configuration
Left section: Two groups of four outputs and four inputs each Center section: resolver interface and I/O control Right section: Two groups of four outputs and four inputs each
Current draw at 5.1V
1A
Current draw at 24V
125 mA
Total backplane power
8.1 W
Power dissipation, nom
22.62 W @ 30 °C (86 °F) 18.22 W @ 60 °C (140 °F)
Power dissipation, max
25.7 W @ 30 °C (86 °F) 21.3 W @ 60 °C (140 °F)
Thermal dissipation, nom
77.23 BTU/hr @ 30 °C (86 °F) 62.2 BTU/hr @ 60 °C (140 °F)
Thermal dissipation, max
87.74 BTU/hr @ 30 °C (86 °F) 72.72 BTU/hr @ 60 °C (140 °F)
Isolation voltage
250V (continuous), basic insulation type, I/O-to-backplane, I/O group-to-group, resolver-to-backplane, and resolver-to-I/O Routine tested at 1900V DC for 2 s
Removable terminal block
Requires 3 RTBs: 1756-TBNH or 1756-TBSH
RTB keying
User-defined mechanical
Slot width
3
Wire category
2 on signal ports 1 on power ports(1)
North American temperature code
T4
IEC temperature code
T4
Enclosure type
None (open style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
235
Page 236
1756 ControlLogix I/O Specifications
Resolver Specifications - 1756-PLS Attribute
1756-PLS
Resolver location
Center section
Compatible resolver
Allen-Bradley resolver 846-SJxxxx-R3-x (x = customer options)
Resolver interface
2V rms, reference output (differential pair) 2V rms, sine and cosine inputs (two differential pairs)
Reference voltage
2V rms ±20%
Reference frequency
5 kHz ±20%
Digital resolution
12 bits (4096 counts from hardware)
Angular resolution
0.088 °/bit
Digital count range
0…4095 (decimal)
Maximum tracking rate
±1800 RPM
Repeatability
±0.0488% of full scale
Accuracy
±0.0976% of full scale
Input Specifications - 1756-PLS Attribute
1756-PLS
Inputs
16 (2 groups of 4 per I/O section)
Voltage category
12/24V DC
Operating voltage range(1)
10.8…31.2V DC
Input delay time (screw to backplane) Off to On
< 15 μs @ 30 °C (86 °F) < 150 μs @ 60 °C (140 °F)
On to Off
< 30 μs @ 30 °C (86 °F) < 200 μs @ 60 °C (140 °F)
Power dissipation, inputs, nom
1.86 W @ 60 °C (140 °F)
Power dissipation, inputs, max
2.8 W @ 60 °C (140 °F)
Thermal dissipation, inputs, nom
6.35 BTU/hr
Thermal dissipation, inputs, max
9.56 BTU/hr
On-state voltage, min
10V DC
On-state voltage, nom
10.8…26.4V DC
On-state voltage, max
31.2V DC
Off-state voltage, max
5V DC
Off-state current, max
1.5 mA
On-state current, min
3 mA
On-state current, max
10 mA
Input impedance, max
3.3 k @ 24V DC
Reverse polarity protection
Yes
(1) UL certification for 24V DC nominal. Rockwell Automation specified to 10.8…31.2V DC.
236
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 237
1756 ControlLogix I/O Specifications
Output Specifications - 1756-PLS Attribute
1756-PLS
Outputs
16 (2 groups of 4 per I/O section)
Voltage category
12/24V DC
Operating voltage range(1)
10…31.2V DC
Output delay time Off to On On to Off
< 15 μs @ 60 °C (140 °F) < 25 μs @ 60 °C (140 °F)
Power dissipation, outputs, nom
5.4 W @ 30 °C (86 °F) 3.2 W @ 60 °C (140 °F)
Power dissipation, outputs, max
6 W @ 30 °C (86 °F) 3.8 W @ 60 °C (140 °F)
Thermal dissipation, outputs, nom
18.43 BTU/hr @ 30 °C (86 °F) 10.93 BTU/hr @ 60 °C (140 °F)
Thermal dissipation, outputs, max
21.48 BTU/hr @ 30 °C (86 °F) 11.93 BTU/hr @ 60 °C (140 °F)
Output power dissipation/slot thermal dissipation
3.2 W @ 60 °C (140 °F) 10.93 BTU/hr @ 60 °C (140 °F)
Off-state leakage current per point, nom
<10 μA @ 60 °C (140 °F)
Off-state leakage current per point, max
300 mA @ 60 °C (140 °F)
On-state voltage, min
10V DC
On-state voltage, nom
10.8…26.4V DC
On-state voltage, max
31.2V DC
Output voltage drop, max
0.55V DC
Current per point, max
1 A @ 30 °C(2) (86 °F)
Current per group, max
4 A @ 30 °C(3) (86 °F)
Current per module, max
8 A @ 30 °C(4) (86 °F)
Current limit
<4A
Surge current per point
2 A for 10 ms every 1 s @ 60 °C (140 °F)
Load current per point, min
40 mA
Output switching time
Switching 1 A @ 24V DC
Short circuit protection
Electronic (No indication of fault. Remove load and toggle on/off to restore.)
Reverse polarity protection
Yes, current limited. (If wired incorrectly, outputs can be permanently disabled.)
(1) (2) (3) (4)
UL certification for 24V DC nominal. Rockwell Automation specified to 10.8…31.2V DC. Derate 16.7 mA/ °C above 30 °C (86 °F): 0.5 A @ 60 °C (140 °F). Derate 66.8 mA/ °C above 30 °C (86 °F): 2 A @ 60 °C (140 °F). Derate 133.6 mA/ °C above 30 °C (86 °F): 4 A @ 60 °C (140 °F).
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
237
Page 238
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-PLS Attribute
1756-PLS
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on unshielded I/O and power ports ±2 kV at 5 kHz on shielded resolver ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on unshielded I/O and power ports ±2 kV line-earth (CM) on shielded resolver ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on shielded signal ports
Certifications - 1756-PLS Certification(1)
1756-PLS
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
238
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 239
1756 ControlLogix I/O Specifications
ControlLogix I/O Accessories Place 1756 I/O modules in any slot in a 1756 chassis. Each chassis requires a power supply. Product
Cat. No.
Chassis
1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17
Power supply, standard
1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant
1756-PA75R, 1756-PB75R, 1756-PSCA2 1756-CPR2 cable
• For more information on chassis specifications, see ControlLogix Chassis Specifications Technical Data, publication 1756-TD006. • For more information on power supply specifications, see ControlLogix Power Supply Specifications Technical Data, publication 1756-TD005. • For more information on how to choose the right power supply for your application, see the additional product documentation, for example, a user manual, for your 1756 ControlLogix I/O module.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
239
Page 240
1756 ControlLogix I/O Specifications
1756 Removable Terminal Blocks Removable terminal blocks (RTBs) provide a flexible interconnection between your plant wiring and 1756 I/O modules. The RTB plugs into the front of the I/O module. The type of module determines which RTB you need. You can choose screw-clamp or spring-clamp RTBs. RTBs are not shipped with I/O modules. You must order them separately. The standard housing on the front of the wiring arm is not deep enough for 2.5 mm2 (14 AWG) wiring. If you plan to use 2.5 mm2 (14 AWG) wiring, also order the extended housing.
ATTENTION: If separate power sources are used, do not exceed the specified isolation voltage: referring to the specifications for each individual module on the preceding pages.
RTB Specifications - 1756-TBNH, 1756-TBSH, 1756-TBCH, 1756-TBS6H, 1756-TBE Attribute
1756-TBNH
1756-TBSH
1756-TBCH
1756-TBS6H
1756-TBE
Description
20-position NEMA screw-clamp removable block
20-pin spring-clamp removable terminal block with standard housing
36-pin cage-clamp removable terminal block with standard housing
36-pin spring-clamp removable terminal block with standard housing
Extended depth terminal block housing
Screw torque
1.36 N•m (12 lb•in)
–
0.5 N•m (4.4 lb•in)
–
–
Wire size(1)
0.33…2.1 mm2 (22…14 AWG) solid or stranded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max Do not wire more than two conductors on any single terminal.
0.33…2.1 mm2 (22…14 AWG) solid or stranded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max Do not wire multiple conductors on any single terminal.
Single wire connection: 0.33…2.1 mm2 (22…14 AWG) solid or stranded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max Double wire connection: 0.33…1.3 mm2 (22…16 AWG) solid or stranded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max Do not wire more than two conductors on any single terminal.
0.33…2.1 mm2 (22…14 AWG) solid or stranded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max Do not wire multiple conductors on any single terminal.
Screwdriver width
8 mm (5/16 in.) max
–
3.2 mm (1/8 in.)
–
(1) Maximum wire size requires extended housing, catalog number 1756-TBE.
240
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
–