Page 231

1756 ControlLogix I/O Specifications

The following diagram shows how to wire a proximity sensor to the module’s eight counters or eight hardware inputs. Counters use incoming pulses for counts and frequency with two user-configurable On/Off windows per counter. Hardware inputs provide standard input or counter-control functionality.

Allen-Bradley Bulletin 872 3-wire DC Proximity Sensor - Normally Open PNP

12…24V DC

Black

Brown

Module Sink Input Wiring

1756-LSC8XIB8I Blue

12…24V DC Return

GND-0 GND-1

2

1

IN-0

4

3

IN-1

GND-2

6

5

IN-2

GND-3

8

7

IN-3 Counter Control Hardware

GND-4

10

9

IN-4 Inputs 0…7

GND-5

12 11

IN-5

GND-6

14 13

IN-6

GND-7

16 15

IN-7

CTR-GND-0

18 17

CTR-0

Allen-Bradley Bulletin 872 3-wire DC Proximity Sensor - Normally Open NPN

Brown

12…24V DC

Blue

12…24V DC Return

Black

CTR GND-1

20 19

CTR GND-2

22 21

CTR-1 CTR-2

CTR GND- 3

24 23

CTR-3 Counters 0…7

CTR GND-4

26 25

CTR-4

CTR GND- 5

28 27

CTR-5

CTR GND-6

30 29

CTR-6

CTR GND- 7

32 31

CTR-7

CTR GND-7

34 33

Not Used

36 35

Not Used Not Used

Module Source Input Wiring

Counter Specifications - 1756-LSC8XIB8I Attribute

1756-LSC8XIB8I

Number of counters

8 individually isolated

Counting frequency, max

40 kHz

Count range

0…2,147,483,648 (31-bit counter)

Voltage category

12/24V DC sink/source

Operating voltage range

10…30V DC

Off-state voltage, max

5V

Off-state current, max

1.5 mA

On-state current, min

2 mA @ 10V DC

On-state current, max

5 mA @ 30V DC

Change of state

Enter or exit user-configurable windows

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

231

Page 232

1756 ControlLogix I/O Specifications

Hardware Input Specifications - 1756-LSC8XIB8I Attribute

1756-LSC8XIB8I

Inputs

8 individually isolated, standard input or counter-control functionality

Voltage category

12/24V DC sink/source

Operating voltage range

10…30V DC

Input voltage, nom

24V DC

Input delay time (screw to backplane) Off to On On to Off

14 μs nom/23 μs max + user-configurable filter time of 0…30,000 μs 14 μs nom/23 μs max + user-configurable filter time of 0…30,000 μs

Off-state voltage, max

5V

Off-state current, max

1.5 mA

On-state current, min

2 mA @ 10V DC

On-state current, max

5 mA @ 30V DC

Change of state

Any transition

Module Specifications - 1756-LSC8XIB8I Attribute

1756-LSC8XIB8I

Current draw @ 5.1V

275 mA

Current draw @ 24V

3 mA

Total backplane power

1.47 W

Power dissipation

3.8 W @ 60 °C (140 °F)

Thermal dissipation

12.97 BTU/hr

Input impedance, max

Six k @ 30V DC

Cyclic update time

200 μs…750 ms

Isolation voltage

250V (continuous), reinforced insulation type, inputs-to-backplane 250V (continuous), basic insulation type, input-to-input Type tested @ 2300V AC for 60 s inputs-to-backplane Type tested @ 1500V AC for 60 s input-to-input

Module keying

Electronic, software configurable

Removable terminal block housing

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1 on signal ports(1)

North American temperature code

T4A

IEC temperature code

T4

Enclosure type

None (open-style)

Reverse polarity protection

Yes

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

232

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 233

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-LSC8XIB8I Attribute

1756-LSC8XIB8I

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-LSC8XIB8I Certification(1)

1756-LSC8XIB8I c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

233

Page 234

1756 ControlLogix I/O Specifications

1756-PLS ControlLogix programmable limit switch module 1756-PLS Inputs - Left Side 2

1756-PLS Outputs - Right Side

1

OUTPUT 0

INPUT 0 4

3

6

5

8

7

10

9

12

11

14

13

16

15

OUTPUT 1

INPUT 1

OUTPUT 3

INPUT 3

DC PWR 0...3

17

20

19

OUTPUT 7

8

7

10

9

12

11

14

13

16

15

18

17

20

19

INPUT 9 INPUT 10 INPUT 11 DC COM 8...11 INPUT 12

OUTPUT 13

+

INPUT 7

DC PWR 4...7

5

OUTPUT 12

INPUT 6 18

6

INPUT 8

DC PWR 8...11

10...30V DC

INPUT 5

OUTPUT 6

3

OUTPUT 11

_

INPUT 4

OUTPUT 5

4

OUTPUT 10

DC COM 0...3

OUTPUT 4

1

OUTPUT 9

+

INPUT 2

OUTPUT 2

2

OUTPUT 8

INPUT 13 INPUT 14

OUTPUT 14 OUTPUT 15

_

DC PWR 12...15

DC COM 4-...7

INPUT 15 DC COM 12...15

+ _

The 1756-PLS module supports enhanced packaging applications. The module requires three contiguous slots in the chassis. 1756-PLS Resolver 2

1

4

3

6

5

8

7

10

9

12

11

14

13

16

15

18

17

Do Not Use

Do Not Use

Do Not Use

Do Not Use

Do Not Use

Do Not Use

Do Not Use

Do Not Use

Do Not Use

Do Not Use

Do Not Use

Do Not Use

Allen-Bradley Resolver 846-SJDA1CG-R3-C

F (S3)

E (S2) G (S4)

234

Do Not Use

Sine +

D (S1)

Do Not Use

Sine – Cosine +

Reference + 20

Cosine –

19

Reference –

A (R1) B (R2)

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 235

1756 ControlLogix I/O Specifications

Indicator for Left Slot I/O Module

Indicator for Left Resolver Module

Indicator for Right Slot I/O Module

PROG. LIMIT SWITCH

PROG. LIMIT SWITCH

PROG. LIMIT SWITCH

OUT 0 1 2 3 4 5 6 7

O K

O IN 0 1 2 3 4 5 6 7 K

DC I/O

OUT 8 9 10 11 12 13 14 15

O IN 8 9 10 11 12 13 14 15 K

RESOLVER

DC I/O

Technical Specifications - 1756-PLS Attribute

1756-PLS

Module configuration

Left section: Two groups of four outputs and four inputs each Center section: resolver interface and I/O control Right section: Two groups of four outputs and four inputs each

Current draw at 5.1V

1A

Current draw at 24V

125 mA

Total backplane power

8.1 W

Power dissipation, nom

22.62 W @ 30 °C (86 °F) 18.22 W @ 60 °C (140 °F)

Power dissipation, max

25.7 W @ 30 °C (86 °F) 21.3 W @ 60 °C (140 °F)

Thermal dissipation, nom

77.23 BTU/hr @ 30 °C (86 °F) 62.2 BTU/hr @ 60 °C (140 °F)

Thermal dissipation, max

87.74 BTU/hr @ 30 °C (86 °F) 72.72 BTU/hr @ 60 °C (140 °F)

Isolation voltage

250V (continuous), basic insulation type, I/O-to-backplane, I/O group-to-group, resolver-to-backplane, and resolver-to-I/O Routine tested at 1900V DC for 2 s

Removable terminal block

Requires 3 RTBs: 1756-TBNH or 1756-TBSH

RTB keying

User-defined mechanical

Slot width

3

Wire category

2 on signal ports 1 on power ports(1)

North American temperature code

T4

IEC temperature code

T4

Enclosure type

None (open style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

235

Page 236

1756 ControlLogix I/O Specifications

Resolver Specifications - 1756-PLS Attribute

1756-PLS

Resolver location

Center section

Compatible resolver

Allen-Bradley resolver 846-SJxxxx-R3-x (x = customer options)

Resolver interface

2V rms, reference output (differential pair) 2V rms, sine and cosine inputs (two differential pairs)

Reference voltage

2V rms ±20%

Reference frequency

5 kHz ±20%

Digital resolution

12 bits (4096 counts from hardware)

Angular resolution

0.088 °/bit

Digital count range

0…4095 (decimal)

Maximum tracking rate

±1800 RPM

Repeatability

±0.0488% of full scale

Accuracy

±0.0976% of full scale

Input Specifications - 1756-PLS Attribute

1756-PLS

Inputs

16 (2 groups of 4 per I/O section)

Voltage category

12/24V DC

Operating voltage range(1)

10.8…31.2V DC

Input delay time (screw to backplane) Off to On

< 15 μs @ 30 °C (86 °F) < 150 μs @ 60 °C (140 °F)

On to Off

< 30 μs @ 30 °C (86 °F) < 200 μs @ 60 °C (140 °F)

Power dissipation, inputs, nom

1.86 W @ 60 °C (140 °F)

Power dissipation, inputs, max

2.8 W @ 60 °C (140 °F)

Thermal dissipation, inputs, nom

6.35 BTU/hr

Thermal dissipation, inputs, max

9.56 BTU/hr

On-state voltage, min

10V DC

On-state voltage, nom

10.8…26.4V DC

On-state voltage, max

31.2V DC

Off-state voltage, max

5V DC

Off-state current, max

1.5 mA

On-state current, min

3 mA

On-state current, max

10 mA

Input impedance, max

3.3 k @ 24V DC

Reverse polarity protection

Yes

(1) UL certification for 24V DC nominal. Rockwell Automation specified to 10.8…31.2V DC.

236

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 237

1756 ControlLogix I/O Specifications

Output Specifications - 1756-PLS Attribute

1756-PLS

Outputs

16 (2 groups of 4 per I/O section)

Voltage category

12/24V DC

Operating voltage range(1)

10…31.2V DC

Output delay time Off to On On to Off

< 15 μs @ 60 °C (140 °F) < 25 μs @ 60 °C (140 °F)

Power dissipation, outputs, nom

5.4 W @ 30 °C (86 °F) 3.2 W @ 60 °C (140 °F)

Power dissipation, outputs, max

6 W @ 30 °C (86 °F) 3.8 W @ 60 °C (140 °F)

Thermal dissipation, outputs, nom

18.43 BTU/hr @ 30 °C (86 °F) 10.93 BTU/hr @ 60 °C (140 °F)

Thermal dissipation, outputs, max

21.48 BTU/hr @ 30 °C (86 °F) 11.93 BTU/hr @ 60 °C (140 °F)

Output power dissipation/slot thermal dissipation

3.2 W @ 60 °C (140 °F) 10.93 BTU/hr @ 60 °C (140 °F)

Off-state leakage current per point, nom

<10 μA @ 60 °C (140 °F)

Off-state leakage current per point, max

300 mA @ 60 °C (140 °F)

On-state voltage, min

10V DC

On-state voltage, nom

10.8…26.4V DC

On-state voltage, max

31.2V DC

Output voltage drop, max

0.55V DC

Current per point, max

1 A @ 30 °C(2) (86 °F)

Current per group, max

4 A @ 30 °C(3) (86 °F)

Current per module, max

8 A @ 30 °C(4) (86 °F)

Current limit

<4A

Surge current per point

2 A for 10 ms every 1 s @ 60 °C (140 °F)

Load current per point, min

40 mA

Output switching time

Switching 1 A @ 24V DC

Short circuit protection

Electronic (No indication of fault. Remove load and toggle on/off to restore.)

Reverse polarity protection

Yes, current limited. (If wired incorrectly, outputs can be permanently disabled.)

(1) (2) (3) (4)

UL certification for 24V DC nominal. Rockwell Automation specified to 10.8…31.2V DC. Derate 16.7 mA/ °C above 30 °C (86 °F): 0.5 A @ 60 °C (140 °F). Derate 66.8 mA/ °C above 30 °C (86 °F): 2 A @ 60 °C (140 °F). Derate 133.6 mA/ °C above 30 °C (86 °F): 4 A @ 60 °C (140 °F).

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

237

Page 238

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-PLS Attribute

1756-PLS

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on unshielded I/O and power ports ±2 kV at 5 kHz on shielded resolver ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on unshielded I/O and power ports ±2 kV line-earth (CM) on shielded resolver ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on shielded signal ports

Certifications - 1756-PLS Certification(1)

1756-PLS

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

238

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 239

1756 ControlLogix I/O Specifications

ControlLogix I/O Accessories Place 1756 I/O modules in any slot in a 1756 chassis. Each chassis requires a power supply. Product

Cat. No.

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2 1756-CPR2 cable

• For more information on chassis specifications, see ControlLogix Chassis Specifications Technical Data, publication 1756-TD006. • For more information on power supply specifications, see ControlLogix Power Supply Specifications Technical Data, publication 1756-TD005. • For more information on how to choose the right power supply for your application, see the additional product documentation, for example, a user manual, for your 1756 ControlLogix I/O module.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

239

Page 240

1756 ControlLogix I/O Specifications

1756 Removable Terminal Blocks Removable terminal blocks (RTBs) provide a flexible interconnection between your plant wiring and 1756 I/O modules. The RTB plugs into the front of the I/O module. The type of module determines which RTB you need. You can choose screw-clamp or spring-clamp RTBs. RTBs are not shipped with I/O modules. You must order them separately. The standard housing on the front of the wiring arm is not deep enough for 2.5 mm2 (14 AWG) wiring. If you plan to use 2.5 mm2 (14 AWG) wiring, also order the extended housing.

ATTENTION: If separate power sources are used, do not exceed the specified isolation voltage: referring to the specifications for each individual module on the preceding pages.

RTB Specifications - 1756-TBNH, 1756-TBSH, 1756-TBCH, 1756-TBS6H, 1756-TBE Attribute

1756-TBNH

1756-TBSH

1756-TBCH

1756-TBS6H

1756-TBE

Description

20-position NEMA screw-clamp removable block

20-pin spring-clamp removable terminal block with standard housing

36-pin cage-clamp removable terminal block with standard housing

36-pin spring-clamp removable terminal block with standard housing

Extended depth terminal block housing

Screw torque

1.36 N•m (12 lb•in)

–

0.5 N•m (4.4 lb•in)

–

–

Wire size(1)

0.33…2.1 mm2 (22…14 AWG) solid or stranded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max Do not wire more than two conductors on any single terminal.

0.33…2.1 mm2 (22…14 AWG) solid or stranded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max Do not wire multiple conductors on any single terminal.

Single wire connection: 0.33…2.1 mm2 (22…14 AWG) solid or stranded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max Double wire connection: 0.33…1.3 mm2 (22…16 AWG) solid or stranded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max Do not wire more than two conductors on any single terminal.

0.33…2.1 mm2 (22…14 AWG) solid or stranded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max Do not wire multiple conductors on any single terminal.

Screwdriver width

8 mm (5/16 in.) max

–

3.2 mm (1/8 in.)

–

(1) Maximum wire size requires extended housing, catalog number 1756-TBE.

240