Page 101

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IRT8I (continued) Attribute

1756-IRT8I

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire size

0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max

Wire category

2 on signal ports(2)

North American temperature code

T4A

IEC temperature code

T4

Enclosure type

None (open-style)

(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IRT8I Attribute

1756-IRT8I

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on shielded signal ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on shielded signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

101

Page 102

1756 ControlLogix I/O Specifications

Certifications - 1756-IRT8I Certification(1)

1756-IRT8I c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 Gc X

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

102

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 103

1756 ControlLogix I/O Specifications

1756-IR12 ControlLogix RTD analog input module IMPORTANT: Remember the following:

1756-IR12 3-wire RTD

• If separate power sources are used, do not exceed the specific isolation voltage as listed in the specifications. • For 2-wire resistor applications including calibration, make sure IN_x/B and RTN_x/C are shorted together.

Technical Specifications - 1756-IR12 Attribute

1756-IR12

Inputs

12 channels RTD mode

Input range

1…500 2…1000 4…2000 8…4000

Resolution

24 bits 0…510 : 0.06 m/count 0…1020 : 0.12 m/count 0…2040 : 0.25 m/count 0…4080 : 0.50 m/count

RTD sensors supported

100, 200, 500, 1000 Platinum, alpha=385 100, 200, 500, 1000 Platinum, alpha=3916 120 Nickel, alpha=672 100, 120, 200, 500 Nickel, alpha=618 10 Copper, alpha=427

Current draw @ 5.1V

200 mA

Current draw @ 24V

70 mA

Total backplane power

2.7 W

Power dissipation, max

2.7 W

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

103

Page 104

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IR12 (continued) Attribute

1756-IR12

Thermal dissipation

9.2 BTU/hr

RTD excitation current

600 μA

Overvoltage protection, max

±30V DC

Common mode noise rejection

120 dB @ 60 Hz 1000 Ω differential 100 dB @ 50 Hz 1000 Ω differential

Channel bandwidth

Notch Filter configuration dependent See publication 1756-UM540 for possible values.

Settling time

Notch Filter configuration dependent See publication 1756-UM540 for possible values.

Open circuit detection

Positive full-scale reading within 2 s

Calibrated accuracy @ 25 °C

0…510 range: 0.1% Other ranges: 0.25%

Module error over full temperature range

0…510 range: 0.2% Other ranges: 0.5%

Module input scan time, min

50 ms

Data format

IEEE 32-bit floating point

Module conversion method

Sigma-Delta

Isolation Voltage

250V (continuous), reinforced insulation type, inputs to backplane No isolation between individual inputs Type tested at 1800V AC for 60 s

RTD sensor types/temperature range (Each sensor type in a cell supports all temperature ranges in the corresponding column to the right.) 100 PT 385 20 PT 385 500 PT 385 1000 PT 385

-200…+870 °C (-328…+1598 °F) 73…1143 °K 132…2058 °R

100 PT 3916 20 PT 3916 500 PT 3916 1000 PT 3916

-200…+630 °C (-328…+1166 °F) 73…903 °K 132…1626 °R

10 CU 427

-200…+260 °C (-328…+500 °F) 73…533 °K 132…960 °R

120 NI 672

-80…+320 °C (-112…+608 °F) 193…593 °K 348…1068 °R

100 NI 618 120 NI 618 200 NI 618 500 NI 618

-60…+250 °C (-76…+482 °F) 213…523 °K 384…942 °R

Module keying

Electronic, software configurable

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

104

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 105

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IR12 (continued) Attribute

1756-IR12

Wire size

0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max

Wire category

2 on signal ports(1)

North American Temp Code

T4A

ATEX Temp Code

T4

IECEx Temp Code

T4

Enclosure type

None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IR12 Attribute

1756-IR12

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions IEC 61000-6-4

CISPR 11, Class A

ESD Immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF Immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B Immunity IEC 61000-4-4

±2 kV at 5/100kHz on shielded ports

Surge Transient Immunity IEC 61000-4-5

±2 kV line-earth(CM) on shielded ports

Conducted RF Immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

105

Page 106

1756 ControlLogix I/O Specifications

Certifications - 1756-IR12 Certification(1) (when product is marked)

Description c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/EC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: • EN 61010-2-201; Control Equipment Safety Requirements

RCM

Australian Radiocommunications Act, compliant with: • EN 61000-6-4; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" II 3 G Ex nA IIC T4 Gc DEMKO15ATEX1482X

IECEx

IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" II 3 G Ex nA IIC T4 Gc IECEx UL 15.0053X

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3

EAC

Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation

(1) See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.

106

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 107

1756 ControlLogix I/O Specifications

1756-IT6I ControlLogix temperature sensing analog input module 1756-IT6I 2

1

4

3

6

5

8

7

IN-1

IN-0

Not Used Cold Junction Sensor Lug

Not Used

RTN-1

RTN-0

IN-3

ANALOG INPUT

10

9

12

11

14

13

RTN-2

CJC-

Wire

Thermocouple

Not Used

RTN-3

OK

– IN-2

CJC+

CAL

+

Not Used 16

15

18

17

20

19

IN-5

IN-4

Not Used

Not Used

RTN-5

RTN-4

One CJC, part number 94238301, is shipped with the module. A replacement can be ordered as RP-94238301.

Signal and User Counts - 1756-IT6I Range

Low Signal and User Counts

High Signal and User Counts

-12…30 mV

-15.80323 mV -32768 counts

31.396 mV 32767 counts

-12…78 mV

-15.15836 mV -32768 counts

79.241 mV 32767 counts

Technical Specifications - 1756-IT6I Attribute

1756-IT6I

Inputs

Six individually isolated thermocouple 1 CJC

Input range

-12…78 mV -12…30 mV (high-resolution range)

Resolution

16 bits -12…78 mV: 1.4 V/bit (typical) -12…30 mV: 0.7 V/bit (high-resolution range)

Thermocouples

B, E, J, K, R, S, T, N, C, D, L (TXK/XK)

Thermocouple linearization

ITS-90

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

107

Page 108

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IT6I (continued) Attribute

1756-IT6I

Current draw @ 5.1V

250 mA

Current draw @ 24V

125 mA

Total backplane power

4.3 W

Power dissipation, max

4.3 W

Thermal dissipation

14.66 BTU/hr

Input impedance

>10 M

Open circuit detection time

Positive full scale reading within 2 s

Overvoltage protection, max

120V AC/DC

Normal mode noise rejection

60 dB at 60 Hz(1)

Common mode noise rejection

120 dB @ 60 Hz 100 dB @ 50 Hz

Channel bandwidth

15 Hz (-3 dB)(1)

Settling time

<80 ms to 5% of full scale(1)

Calibrated accuracy @ 25 °C

Better than 0.1% of range

Calibration interval

6 months

Local CJC sensor accuracy

±0.3…3.2 °C, depending on channel

Remote CJC sensor accuracy

±0.3 °C

Offset drift

0.5 V/°C

Gain drift with temperature, nom

65 ppm/°C

Gain drift with temperature, max

80 ppm/°C

Module error

0.5% of range

Module scan time

25 ms min floating point (millivolt) 50 ms min floating point (temperature) 10 ms min integer (millivolt)(1)

Data format

Integer mode (left justified, 2 s complement) IEEE 32-bit floating point

Module conversion method

Sigma-Delta

Isolation voltage

250V (continuous), basic insulation type, input channels-to-backplane, and input channel-to-channel Routine tested at 1350V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

Wire category

2(2)

North American temperature code

T4A

IEC temperature code

T4

Enclosure type

None (open-style)

(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

108

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 109

1756 ControlLogix I/O Specifications

Thermocouple Ranges - 1756-IT6I Attribute

1756-IT6I

Thermocouple temperature/millivolt input range

-12…78 mV range

-12…30 mV range

Thermocouple Type B

300…1820 °C (572…3308 °F)

Full range

Thermocouple Type C

0…2315 °C (32…4199 °F)

0…1725 °C (32…3137 °F)

Thermocouple Type E

-270…+1000 °C (-454…+1832 °F)

-270…+415 °C (-454…+779 °F)

Thermocouple Type J

-210…+1200 °C (-346…+2192 °F)

-210…+550 °C (-346…+1022 °F)

Thermocouple Type K

-270…+1372 °C (-454…+2502 °F)

-270…+725 °C (-454…+1337 °F)

Thermocouple Type N

-270…+1300 °C (-454…+2372 °F)

-270…+840 °C (-454…+1544 °F)

Thermocouple Type R

-50…+1768 °C (-58…+3215 °F)

Full range

Thermocouple Type S

-50…+1768 °C (-58…+3215 °F)

Full range

Thermocouple Type T

-270…+400 °C (-454…+752 °F)

Full range

Thermocouple Type D

0…2320 °C (32…4208 °F)

0…1718 °C (32…3124 °F)

Thermocouple Type L (TXK/XK)

-200…+800 °C (-328…+1472 °F)

0…200…399 °C (392…750 °F) °C (32…3124 °F)

Thermocouple resolution over temperature range, nom

-12…78 mV range

-12…30 mV range

Type B, R, S, C

~0.15 °C (~0.28 °F)

~0.08 °C (~0.15 °F)

Type E, J, K, T, N

~0.05 °C (~0.09 °F)

~0.03 °C (~0.05 °F)

Type D

~0.07 °C (~0.13 °F)

~0.03 °C (~0.05 °F)

Type TXK/XK (L)

~0.02 °C (~0.04 °F)

~0.01 °C (~0.02 °F)

Environmental Specifications - 1756-IT6I Attribute

1756-IT6I

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

109

Page 110

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IT6I (continued) Attribute

1756-IT6I

EFT/B immunity IEC 61000-4-4

±2 kV at 5 kHz on shielded signal ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on shielded signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on shielded signal ports

Certifications - 1756-IT6I Certification(1)

1756-IT6I

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

110

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016