For the Allen-Bradley 1756-IB16, Allen-Bradley 1756-OB16E and Allen-Bradley 1756-TBNH

Page 91

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IN16 (continued) Attribute

1756-IN16

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-IN16 Certification(1)

1756-IN16

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T3 X Gc

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

91

Page 92

1756 ControlLogix I/O Specifications

1756-IR6I ControlLogix temperature sensing analog input module 1756-IR6I 3-wire RTD 2

1

4

3

6

5

8

7

IN-1/A

IN-0/A

IN-1/B

IN-0/B

RTN-1/C

RTN-0/C

IN-3/A 10

9

12

11

14

13

16

15

18

17

20

19

IN-3/B

IN-2/B

RTN-3/C

RTN-2/C

Not used

Shield Ground

Not used

IN-5/A

IN-4/A

IN-5/B RTN-5/C

3-wire RTD IN-2/A

IN-4/B RTN-4/C

IMPORTANT: For 2-wire resistor applications including calibration, make sure IN-x/B and RTN-x/C are shorted together as shown.

92

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 93

1756 ControlLogix I/O Specifications

1756-IR6I 4-wire RTD 2

1

4

3

6

5

8

7

IN-1/A

IN-0/A

IN-1/B

IN-0/B

RTN-1/C

RTN-0/C

IN-3/A 10

ANALOG INPUT

9

IN-3/B

IN-2/B 12

11

RTN-3/C

RTN-2/C 14

CAL Shield Ground

OK

13

Not used

Not used 16

15

18

17

20

19

IN-4/A

IN-5/A IN-5/B RTN-5/C

4-wire RTD IN-2/A

IN-4/B RTN-4/C

Signal and User Counts - 1756-IR6I Range

Low Signal and User Counts

High Signal and User Counts

1…487

0.859068653 -32768 counts

507.862 32767 counts

2…1000

2 -32768 counts

1016.502 32767 counts

4…2000

4 -32768 counts

2033.780 32767 counts

8…4020

8 -32768 counts

4068.392 32767 counts

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

93

Page 94

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IR6I Attribute

1756-IR6I

Inputs

6 individually isolated RTD

Input range

1…487 2…1000 4…2000 8…4000

Resolution

16 bits 1…487 : 7.7 m/bit 2…1000 :15 m/bit 4…2000 :30 m/bit 8…4020 :60 m/bit

Sensors supported

100, 200, 500, 1000 Platinum, alpha=385 100, 200, 500, 1000 Platinum, alpha=3916 120 Nickel, alpha=672 100, 120, 200, 500 Nickel, alpha=618 10 Copper

Current draw @ 5.1V

250 mA

Current draw @ 24V

125 mA

Total backplane power

4.25 W

Power dissipation, max

4.3 W

Thermal dissipation

14.66 BTU/hr

Open circuit detection time

Negative full scale reading within 5 s with any combination of lost wires, except input terminal A alone. If input terminal A is lost by itself, the module reads a positive full scale reading within 5 s

Overvoltage protection, max

24V AC/DC

Normal mode noise rejection

60 dB at 60 Hz(1)

Common mode noise rejection

120 dB @ 60 Hz 100 dB @ 50 Hz

Channel bandwidth

15 Hz(1)

Settling time

<80 ms to 5% of full scale(1)

Calibrated accuracy @ 25 °C

Better than 0.1% of range

Calibration interval

6 months

Offset drift

10 M/°C

Gain drift with temperature, nom

50 ppm/°C

Gain drift with temperature, max

90 ppm/°C

Module error

0.54% of range

Module scan time

25 ms min floating point (ohms) 50 ms min floating point (temperature) 10 ms min integer (ohms)(1)

Data format

Integer mode (left justified, 2 s complement) IEEE 32-bit floating point

Module conversion method

Sigma-Delta

Isolation voltage

250V (continuous), basic insulation type, input channels-to-backplane, and input channel-to-channel Routine tested at 1350V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

Wire category

2(2)

94

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 95

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IR6I (continued) Attribute

1756-IR6I

North American temperature code

T4A

IEC temperature code

T4

Enclosure type

None (open-style)

(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IR6I Attribute

1756-IR6I

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±2 kV at 5 kHz on shielded signal ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on shielded signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on shielded signal ports

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

95

Page 96

1756 ControlLogix I/O Specifications

Certifications - 1756-IR6I Certification(1)

1756-IR6I

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

96

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 97

1756 ControlLogix I/O Specifications

1756-IRT8I ControlLogix isolated RTD/Thermocouple analog input module. 1756-IRT8I Module Wiring Diagram - 3-wire RTD Input

3-wire RTD

IMPORTANT: Remember the following:

• If separate power sources are used, do not exceed the specific isolation voltage as listed in the specifications. • Terminals 1, 2, 35, and 36 are not used in RTD applications. • For 2-wire resistor applications including calibration, make sure IN_x(-)/B and IN_x/RTD C are shorted together.

CJC 0

2

1

CJC 0

IN_0(-)/B

4

3

IN_0(+)/A

IN_0/RTD C

6

5

IN_0/RTD D

IN_1(-)/B

8

7

IN_1(+)/A

IN_1/RTD C

10

9

IN_1/RTD D

IN_2(-)/B

12 11

IN_2(+)/A

IN_2/RTD C

14 13

IN_2/RTD D

IN_3(-)/B

16 15

IN_3(+)/A

IN_3/RTD C

18 17

IN_3/RTD D

IN_4(-)/B

20 19

IN_4(+)/A

IN_4/RTD C

22 21

IN_4/RTD D

IN_5(-)/B

24 23

IN_5(+)/A

IN_5/RTD C

26 25

IN_5/RTD D

IN_6(-)/B

28 27

IN_6(+)/A

IN_6/RTD C

30 29

IN_6/RTD D

IN_7(-)/B

32 31

IN_7(+)/A

IN_7/RTD C

34 33

IN_7/RTD D

CJC 1

36 35

CJC1

1756-IRT8I Module Wiring Diagram - 4-wire RTD Input IMPORTANT: Remember the following: • If separate power sources are used, do not exceed the specific isolation voltage as listed in the specifications. • Terminals 1, 2, 35, and 36 are not used in RTD applications.

Shield Ground

4-wire RTD

CJC 0

2

1

CJC 0

IN_0(-)/B

4

3

IN_0(+)/A

IN_0/RTD C

6

5

IN_0/RTD D

IN_1(-)/B

8

7

IN_1(+)/A

IN_1/RTD C

10

9

IN_1/RTD D

IN_2(-)/B

12 11

IN_2(+)/A

IN_2/RTD C

14 13

IN_2/RTD D

IN_3(-)/B

16 15

IN_3(+)/A

IN_3/RTD C

18 17

IN_3/RTD D

IN_4(-)/B

20 19

IN_4(+)/A

IN_4/RTD C

22 21

IN_4/RTD D

IN_5(-)/B

24 23

IN_5(+)/A

IN_5/RTD C

26 25

IN_5/RTD D

IN_6(-)/B

28 27

IN_6(+)/A

IN_6/RTD C

30 29

IN_6/RTD D

IN_7(-)/B

32 31

IN_7(+)/A

IN_7/RTD C

34 33

IN_7/RTD D

CJC 1

36 35

CJC1

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Shield Ground

97

Page 98

1756 ControlLogix I/O Specifications

1756-IRT8I Module Wiring Diagram - Thermocouple Input

CJC Sensor

IMPORTANT: Remember the following:

• Connect the white end of the CJC sensor to the evennumbered terminal. Connect the orange end of the CJC sensor to the odd-numbered terminals. For CJC 0:

– White end - Connected to terminal number 2 – Orange end - Connected to terminal number 1 For CJC 1:

– White end - Connected to terminal number 36 – Orange end - Connected to terminal number 35 • CJC sensors do not come with the module. You must order the sensors, product catalog number 1756-CJC, separately. • If separate power sources are used, do not exceed the specific isolation voltage as listed in the specifications.

RTD/TC/mV INPUT

ST FLT

CJC 0

2

1

CJC 0

IN_0(-)/B

4

3

IN_0(+)/A

IN_0/RTD C

6

5

IN_0/RTD D

IN_1(-)/B

8

7

IN_1(+)/A

IN_1/RTD C

10

9

IN_1/RTD D

IN_2(-)/B

12 11

IN_2(+)/A

IN_2/RTD C

14 13

IN_2/RTD D

IN_3(-)/B

16 15

IN_3(+)/A

IN_3/RTD C

18 17

IN_3/RTD D

IN_4(-)/B

20 19

IN_4(+)/A

IN_4/RTD C

22 21

IN_4/RTD D

IN_5(-)/B

24 23

IN_5(+)/A

IN_5/RTD C

26 25

IN_5/RTD D

IN_6(-)/B

28 27

IN_6(+)/A

IN_6/RTD C

30 29

IN_6/RTD D

IN_7(-)/B

32 31

IN_7(+)/A

IN_7/RTD C

34 33

IN_7/RTD D

CJC 1

36 35

CJC

O K

+

–

+ mV Source

– CJC Sensor

Technical Specifications - 1756-IRT8I Attribute

1756-IRT8I

Inputs

Eight isolated channels - Any combination of RTD or Thermocouple mode Two CJC sensors for Thermocouple use. The CJC sensors, product catalog number 1756-CJC, do not come with the module. You must order the sensors separately.

Input range

1…500 2…1000 4…2000 8…4000 -100…100 mV

Resolution

24 bits 0…510 : 0.06 m/count 0…1020 : 0.12 m/count 0…2040 : 0.25 m/count 0…4080 : 0.50 m/count -101…101 mV: 0.01 μV/count

RTD sensors supported

100, 200, 500, 1000 Platinum, alpha=385 100, 200, 500, 1000 Platinum, alpha=3916 120 Nickel, alpha=672 100, 120, 200, 500 Nickel, alpha=618 10 Copper, alpha=427

Thermocouple types

B, C, D, E, J, K, N, R, S, T, TXK/XK (L)

98

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 99

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IRT8I (continued) Attribute

1756-IRT8I

Thermocouple linearization

ITS-90

Current draw @ 5.1V

200 mA

Current draw @ 24V

150 mA

Total backplane power

4.6 W

Power dissipation, max

4.6 W

Thermal dissipation

15.7 BTU/hr

RTD excitation current

600 μA

Input impedance, approx

1 G

Open circuit detection time

• Thermocouple input and 3-wire RTD input = 2 s • 4-wire RTD input = 5 s IMPORTANT: No Open Circuit Detection when wires are simultaneously disconnected from the IN_x/RTD C and IN_x/RTD D terminals on same channel; where x represents the channel number.

Overvoltage protection, max

±30V DC

Normal mode noise rejection

75 dB at 60 Hz(1)

Common mode noise rejection

125 dB @ 60 Hz 1000 Ω differential 120 dB @ 50 Hz 1000 Ω differential 160 dB @ 600V 100 Ω differential

Channel bandwidth

Notch Filter configuration dependent See publication 1756-UM540 for possible values.

Settling time

Notch Filter configuration dependent See publication 1756-UM540 for possible values.

Calibrated accuracy @ 25 °C

0.05%

Module error over full temperature range

0.1%

Local CJC sensor accuracy

± 0.3 °C

Remote CJC sensor, accuracy

± 0.3 °C

Module input scan time, min

1 ms

Data format

IEEE 32-bit floating point

Module conversion method

Sigma-Delta

Isolation voltage

250V (continuous), reinforced Type tested at 2300V AC for 60 s, inputs to backplane insulation type, inputs to backplane 250V (continuous), basic insulation type, input to input Type tested at 1500V AC for 60 s, input to input

RTD sensor types/temperature range (Each sensor type in a cell supports all temperature ranges in the corresponding column to the right.) 100 PT 385 20 PT 385 500 PT 385 1000 PT 385

-200…+870 °C (-328…+1598 °F) 73…1143 °K 132…2058 °R

100 PT 3916 20 PT 3916 500 PT 3916 1000 PT 3916

-200…+630 °C (-328…+1166 °F) 73…903 °K 132…1626 °R

10 CU 427

-200…+260 °C (-328…+500 °F) 73…533 °K 132…960 °R

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

99

Page 100

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IRT8I (continued) Attribute

1756-IRT8I

120 NI 672

-80…+320 °C (-112…+608 °F) 193…593 °K 348…1068 °R

100 NI 618 120 NI 618 200 NI 618 500 NI 618

-60…+250 °C (-76…+482 °F) 213…523 °K 384…942 °R

Thermocouple type/temperature range Thermocouple Type B

21…1820 °C (68…3308 °F) 293…2093 °K 528…3768 °R

Thermocouple Type C

0…2320 °C (32…4208 °F) 273…2593 °K 492…4668 °R

Thermocouple Type D

0…2320 °C (32…4208 °F) 273…2593 °K 492…4668 °R

Thermocouple Type E

-270…+1000 °C (-454…+1832 °F) 3…1273 °K 6…2292 °R

Thermocouple Type J

-210…+1200 °C (-346…+2192 °F) 63…1473 °K 114…2652 °R

Thermocouple Type K

-270…+1372 °C (-454…+2502 °F) 3…1645 °K 6…2961 °R

Thermocouple Type N

-270…+1300 °C (-454…+2372 °F) 3…1573 °K 6…2832 °R

Thermocouple Type R

-50…+1768 °C (-58…+3215 °F) 223…2041 °K 402…3674 °R

Thermocouple Type S

-50…+1768 °C (-58…+3215 °F) 223…2041 °K 402…3674 °R

Thermocouple Type T

-270…+400 °C (-454…+752 °F) 3…673 °K 6…1212 °R

Thermocouple Type TXK/XK (L)

-200…+800 °C (-328…+1472 °F) 73…1073 °K 132…1932 °R

Thermocouple type/resolution, nom Type C, R

~0.03 °C (~0.05 °F)

Type B, S

~0.04 °C (~0.07 °F)

Type E, J, K, N, T, TXK/XK (L)

~0.01 °C (~0.02 °F)

Type D

~0.02 °C (~0.04 °F)

Module keying

100

Electronic, software configurable

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016