Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 9 of 25

1756 ControlLogix I/O Specifications, Technical Data, pages 81 to 90

Pages 81 to 90 of 242

The original document is the PDF (7.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1756-IB16, Allen-Bradley 1756-OB16E and Allen-Bradley 1756-TBNH

Page 81

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IH16I (continued) Attribute

1756-IH16I

On-state current, min

1 mA @ 90V DC

On-state current, max

3 mA @ 146V DC

On-state voltage Derated as follows

90…146V DC 90…146V DC @ 50 °C (122 °F), 12 Channels ON 90…132V DC @ 55 °C (131 °F), 14 Channels ON 90…125V DC @ 60 °C (140 °F), 16 Channels ON 90…146V DC @ 30 °C (86 °F), 16 Channels ON

Inrush current, max

250 mA

Input impedance, max

48.67 k @ 146V DC

Cyclic update time

200 s…750 ms

Change of state

Software configurable

Time stamp of inputs

±200 μs

Isolation voltage

250V (continuous), basic insulation type, inputs-to-backplane, and input-to-input Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block housing

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(2)

North American temperature code

T4

Enclosure type

None (open-style)

Reverse polarity protection

Yes

(1) UL certification for 125V nominal. Rockwell Automation specified to the following: 90…146V DC @ 50 °C (122 °F),12 channels on 90…132V DC @ 55 °C (131 °F), 14 channels on 90…125V DC @ 60 °C (140 °F), 16 channels on 90…146V DC @ 30 °C (86 °F), 16 channels on. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IH16I Attribute

1756-IH16I

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

81

Page 82

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IH16I (continued) Attribute

1756-IH16I

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Oscillatory surge withstand IEEE C37.90.1

3 kV

Certifications - 1756-IH16I Certification(1)

1756-IH16I

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

82

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 83

1756 ControlLogix I/O Specifications

1756-IH16ISOE ControlLogix DC (90…140V) sequence of events input module Simplified Schematic

1756-IH16ISOE

+5V Isolated Wiring

IN-0

GND-0 GND-1 GND-2 GND-3 Source Input Wiring GND-4 DC-5 (-) GND-5 GND-6 DC-6 (-) GND-7 GND-8 Jumper Bar GND-9 (Cut to Length) GND-10 GND-11 Nonisolated GND-12 Wiring GND-13 GND-14 GND-15 GND-15 DC (-) Not Used DC-0 (-)

GND-0

ControlLogix Backplane Interface

Display

Additional jumper bars are available as catalog number 1756-JMPR.

2

1

4

3

6

5

8

7

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Sink Input Wiring IN-0 DC-0 (+) IN-1 DC-1 (+) IN-2 IN-3 Source Input Wiring IN-4 DC-5 (+) IN-5 IN-6 DC-6 (+) IN-7 IN-8 Sink Input Wiring IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used DC (+)

Daisy Chain to Other RTBs

SOE INPUT ST 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15

O K

Technical Specifications - 1756-IH16ISOE Attribute

1756-IH16ISOE

Inputs

16 individually isolated, sequence of events

Voltage category

125V DC sink/source

Operating voltage range

90…140V DC

Input voltage, nom

125V DC

Input delay time (screw to backplane) Off to On

On to Off

Hardware delay: 10 s nom/20 s max + firmware scan: up to 25 μs + filter time: 0…50 ms + ASIC delay: 175 s (FIFO) or 625 s (Coordinated System Time per point) Hardware delay: 50 μs nom/75 μs max + firmware scan: up to 25 μs + filter time: 0…50 ms + ASIC delay: 175 s (FIFO) or 625 s (Coordinated System Time per point)

Current draw @ 5.1V

275 mA§

Current draw @ 24V

2 mA

Total backplane power

1.3 W

Power dissipation, max

5.5 W @ 60 °C (140 °F)

Thermal dissipation

17.22 BTU/hr

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

83

Page 84

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IH16ISOE (continued) Attribute

1756-IH16ISOE

Off-state voltage, max

20V

Off-state current, max

0.3 mA

On-state current, min

1.15 mA @ 90V DC

On-state current, max

1.85 mA @ 140V DC

Input impedance, max

74.8 k

Cyclic update time

200 s…750 ms

Change of state

Software configurable

Time stamp of inputs

±100 μs

Isolation voltage

250V (continuous), basic insulation type, inputs-to-backplane, and input-to-input Routine tested @ 1350V AC for 2 s, inputs-to-backplane

Module keying

Electronic, software configurable

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(1)

North American temperature code

T3C

Enclosure type

None (open-style)

Reverse polarity protection

Yes

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IH16ISOE Attribute

1756-IH16ISOE

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

84

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 85

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IH16ISOE (continued) Attribute

1756-IH16ISOE

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Oscillatory surge withstand IEEE C37.90.1

3 kV

Certifications - 1756-IH16ISOE Certification(1)

1756-IH16ISOE

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

85

Page 86

1756 ControlLogix I/O Specifications

1756-IM16I ControlLogix 240V AC input module 1756-IM161

Simplified Schematic Isolated Wiring

+5V

IN-O

L2-0 L2-2

L2-0

L2-4

GND ControlLogix Backplane Interface

Display

Jumper Bar (Cut to Length)

Nonisolated Wiring

Additional jumper bars are available as catalog number 1756-JMPR.

L2

2

1 3

IN-0 IN-1

L1-0

4

L2-2

6

5

IN-2

L1-2

L2-3

8

7

IN-3

L2-4

10

9

IN-4

L2-5

12 11

IN-5

L2-6

14 13

IN-6

L2-7

16 15

IN-7

L2-8

18 17

IN-8

L2-9

20 19

IN-9

L2-10

22 21

IN-10

L2-11

24 23

IN-11

L2-12

26 25

IN-12

L2-13 L2-14

28 27 30 29

IN-13 IN-14

L2-15

32 31

IN-15

L2-15 Not Used

34 33

Not Used Not Used

L2-0 L2-1

36 35

L1-4

L1 Daisy Chain to Other RTBs

AC INPUT ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K

Technical Specifications - 1756-IM16I Attribute

1756-IM16I

Inputs

16 individually isolated

Voltage category

240V AC 50/60 Hz

Operating voltage range

159…265V AC, 47…63 Hz(1)

Input voltage, nom

240V AC 50/60 Hz

Input delay time (screw to backplane) Off to On Onto Off

Hardware delay: 10 ms max + filter time User-selectable filter time: 1 ms or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 ms or 18 ms

Current draw @ 5.1V

100 mA

Current draw @ 24V

3 mA

Total backplane power

0.58 W

Power dissipation, max

5.8 W @ 60 °C (140 °F)

Thermal dissipation

19.78 BTU/hr

Off-state voltage, max

40V

Off-state current, max

2.5 mA

86

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 87

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IM16I (continued) Attribute

1756-IM16I

On-state current, min

5 mA @ 159V AC, 60 Hz

On-state current, max

13 mA @ 265V AC, 60 Hz

On-state voltage

159…265V AC, 47…63Hz @ 30 °C (86 °F) all channels ON 159…265V AC, 47…63Hz @ 40 °C (104 °F) 8 points ON 159…253V AC, 47…63Hz @ 45 °C (113 °F) all channels ON 159…242V AC, 47…63Hz @ 60 °C (140 °F) all channels ON

Inrush current, max

250 mA

Input impedance, max

20.38 k @ 265V AC, 60 Hz

Cyclic update time

200 s…750 ms

Change of state

Software configurable

Time stamp of inputs

±200 μs

Isolation voltage

250V (continuous), basic insulation type, inputs-to-backplane, and input-to-input Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block housing

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(2)

North American temperature code

T4

Enclosure type

None (open-style)

(1) UL certification for 240V 50/60 Hz nominal. Rockwell Automation specified to the following: 159…265V AC, 47…63Hz @ 30 °C (86 °F) all channels on 159…265V AC, 47…63Hz @ 40 °C (104 °F) 8 points on 159…253V AC, 47…63Hz @ 45 °C (113 °F) all channels on 159…242V AC, 47…63Hz @ 60 °C (140 °F) all channels on. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IM16I Attribute

1756-IM16I

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

87

Page 88

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IM16I (continued) Attribute

1756-IM16I

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-IM16I Certification(1)

1756-IM16I

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

88

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 89

1756 ControlLogix I/O Specifications

1756-IN16 ControlLogix AC (10…30V) input module 1756-IN16

Simplified Schematic +5V

IN-O

2

1

4

3

6

5

8

7

IN-0

IN-1 L1

L2-0

IN-2

IN-3

GND

IN-4

IN-5 L2

Group 0

ControlLogix Backplane Interface

Display

10

9

12

11

14

13

16

15

L2-0

L2-0

IN-8

IN-9

IN-10

IN-11 Group 1

IN-12

IN-13

AC INPUT

18

17

20

19

L2-1

Group 1

IN-14

IN-15 ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K

Group 0 IN-6

IN-7

L2-1

Daisy Chain to Other RTBs

Technical Specifications - 1756-IN16 Attribute

1756-IN16

Inputs

16 (8 points/group)

Voltage category

24V AC 50/60 Hz

Operating voltage range

10…30V AC, 47…63 Hz

Input voltage, nom

24V AC 50/60 Hz

Input delay time (screw to backplane) Off to On On to Off

Hardware delay: 10 ms max + filter time User-selectable filter time: 0 ms, 1 ms, or 2 ms Hardware delay: 10 ms max + filter time User-selectable filter time: 9 ms or 18 ms

Current draw @ 5.1V

100 mA

Current draw @ 24V

2 mA

Total backplane power

0.56 W

Power dissipation, max

5.1 W @ 60 °C (140 °F)

Thermal dissipation

17.39 BTU/hr

Off-state voltage, max

5V

Off-state current, max

2.75 mA

On-state current, min

5 mA @ 10V AC, 60 Hz

On-state current, max

1.2 mA @ 30V AC, 60 Hz

Inrush current, max

250 mA

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

89

Page 90

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IN16 (continued) Attribute

1756-IN16

Input impedance, max

2.5 k @ 30V AC, 60 Hz

Cyclic update time

200 s…750 ms

Change of state

Software configurable

Time stamp of inputs

±200 μs

Isolation voltage

250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block housing

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

Wire category

1(1)

North American temperature code

T3C

IEC temperature code

T3

Enclosure type

None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IN16 Attribute

1756-IN16

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

90

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016