Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 8 of 25

1756 ControlLogix I/O Specifications, Technical Data, pages 71 to 80

Pages 71 to 80 of 242

The original document is the PDF (7.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1756-IB16, Allen-Bradley 1756-OB16E and Allen-Bradley 1756-TBNH

Page 71

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IF16H (continued) Attribute

1756-IF16H

Repeatability

Better than 0.01% of range (15 Hz and 20 Hz filters only)

Calibrated accuracy

Better than 0.13% of range (all filters)

Calibration interval

12 months typical

Offset drift

27 V/°C

Gain drift with temperature

11ppm/°C

Module error

0.3% of range

Module input scan time, min

11…328 ms (filter dependent)

Module HART scan time

Estimate 1 s if all channels are HART enabled

Data format

Integer mode (left justified, 2 s complement) IEEE 32-bit floating point

Input conversion method

Successive approximation

Output conversion method

R-Ladder DAC, monotonicity with no missing codes

Module keying

Electronic, software configurable

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire size

1756-TBCH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max 1756-TBS6H Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max

Terminal block torque spec

1756-TBCH 0.5 N•m (4.4 lb•in)

Wire category(1)

2 - on signal ports

Wire type

Copper

North American temp code

T5

ATEX temp code

T4

IECEx temp code

T4

Enclosure type rating

None (open-style)

(1) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IF16H Attribute

1756-IF16H

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

71

Page 72

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IF16H (continued) Attribute

1756-IF16H

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

IEC 61000-6-4

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±2 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on shielded ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-IF16H Certification(1)

1756-IF16H c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2014/30/EU EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

RCM

Australian Radiocommunications Act, compliant with: • EN 61000-6-4; Industrial Emissions

Ex

European Union 2014/34/EU ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • DEMKO12ATEX1219040X

IECEx

IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • IECEx UL 16.0109X

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3

EAC

Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

72

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 73

1756 ControlLogix I/O Specifications

1756-IF16IH ControlLogix current analog input module with HART protocol 2-wire HART Device 2-wire XMTR

Not Used

2

1

Not Used

+-

24V DC +

IN0

4

3

IN1

-

RTN0

6

5

RTN1

4-wire HART Device

IN2

8

7

IN3

RTN2

10

9

RTN3

IN4

12 11

IN5

RTN4

14 13

RTN5

IN6

16 15

IN7

RTN6

18 17

RTN7

Power Supply

24V DC Power Supply

+ +4-wire+ -

-

XMTR

-

ANALOG INPUT CAL OK HART

IN8

20 19

IN9

RTN8

22 21

RTN9

IN10

24 23

IN11

RTN10

26 25

RTN11

IN12

28 27

IN13

RTN12

30 29

RTN13 IN15

IN14

32 31

RTN14

34 33

RTN15

Not Used

36 35

Not Used

When a common supply is used, tie the IN- to RTN.

Technical Specifications - 1756-IF16IH Attribute

1756-IF16IH

Voltage and current ratings

Backplane: 225 mA @ 5.1V DC, 200 mA @ 24V DC 16 Inputs Input current range: 0…20 mA, 4…20 mA

Resolution

16…21 bits

Power dissipation

5.30 W

Inrush current

400 mA @ 5.1V DC 450 mA @ 24V DC

Isolation voltage

250V (continuous) Reinforced Insulation Type, inputs to backplane. Basic Insulation Type, input to input, and inputs to ground

Input impedance

250 (±5 )

Open circuit detection time

5 s, 4…20 mA range only

Input overvoltage protection

28.8V DC

Normal mode noise rejection

90 dB @ 50/60 Hz (10 Hz filter) 74 dB @ 50/60 Hz (15 Hz filter) 33 dB @ 60 Hz, 90 dB @60 Hz (20 Hz filter)

Common mode noise rejection

> 90 dB @ 50/60 Hz (10 Hz, 15 Hz, and 20 Hz filters only)

Calibrated accuracy at 25 °C with HART disabled

0.15…1.5% of full scale, dependent on selected filter

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

73

Page 74

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IF16IH (continued) Attribute

1756-IF16IH

Calibrated accuracy at 25 °C with HART enabled

1.5% of full scale with 250 Hz filter 0.5% of full scale with 100 Hz filter 0.2% of full scale with 50 Hz or 60 Hz filter 0.15% of full scale with 15 Hz or 20 Hz filter Monotonicity not guaranteed

Calibrated accuracy over full temperature range with HART enabled

1.8% of full scale with 250 Hz filter 0.8% of full scale with 100 Hz filter 0.5% of full scale with 50 Hz or 60 Hz filter 0.4% of full scale with 15 Hz or 20 Hz filter Monotonicity not guaranteed

Calibration interval

12 months typical

Input offset drift with temperature

300 A/°C

Gain drift with temperature

20 ppm/°C

Module error over full temperature range with HART disabled

0.3% of range (all filters)

Module scan time for all channels - analog, min

14…428 ms (filter dependent)

Typical module HART dynamic variables update time for all channels

1 s typical with no pass through or device information messaging active

Data format

Integer mode (left justified, 2 s complement) IEEE 32-bit floating point

Input conversion method

Sigma-Delta ADC (24-bit converter)

Output conversion method

Sigma-Delta ADC (24-bit converter)

Module keying

ASIC does not support module keying

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire size

1756-TBCH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max 1756-TBS6H Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max

Terminal block torque specs

1756-TBCH 0.5 N•m (4.4 lb·in)

Wiring category(1)

2 - on signal ports

Wire type

Copper

North American temp code

T5

ATEX temp code

T4

IECEx temp code

T4

Enclosure type rating

None (open-style)

(1) Use this conductor category information for planning conductor routing. See Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

74

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 75

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IF16IH Attribute

1756-IF16IH

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

IEC 61000-6-4

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…6000 MHz

EFT/B immunity IEC 61000-4-4

±2 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on shielded ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

75

Page 76

1756 ControlLogix I/O Specifications

Certifications - 1756-IF16IH Certification(1)

1756-IF16IH c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2014/30/EU EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2014/35/EU LVD, compliant with: • EN 61131-2; Programmable Controllers (Clause 11)

RCM

Australian Radiocommunications Act, compliant with: • EN 61000-6-4; Industrial Emissions

Ex

European Union 2014/34/EU ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • DEMKO14ATEX1238X

IECEx

IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • IECEx UL 16.0110X

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3

EAC

Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation

(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

76

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 77

1756 ControlLogix I/O Specifications

1756-IG16 ControlLogix TTL input module Standard Wiring

CE Compliant Wiring 1756-IG16

1756-IG16 – DC 2

IN-1

IN-0 4

IN-2 6

5

8

7

10

9

IN-4

IN-7

+

IN-6

DC Power Wire

6

5

8

7

IN-2

12

11

14

13

16

15

18

17

5V DC Power

12

11

14

13

DC COM 0

IN-8 IN-10 16

15

IN-12 18

17

20

19

DC-1(+)

19

+ – TTL Input Device

Capacitor 0.01 µF Typical (See notes below.)

IN-14

IN-15

IN-14

IN-15

9

IN-13

IN-12

IN-13

10

IN-11

IN-10

IN-11

I/O Wire

IN-6

IN-9

IN-8

IN-9

IN-4

IN-7

DC COM 0

I/O Wire

IN-0

DC-0(+)

–

DC-0(+)

20

3

IN-5

IN-5

+ DC

1

4

IN-3

3

IN-3

5V DC

2

IN-1

1

DC COM 1

DC COM 1

DC-1(+)

IMPORTANT: I/O cables must be shielded type and cable length must be <10 m (32.8 ft) for maximum EMI noise immunity.

Simplified Schematic +5 DC 1.5 K 1K

74HCT14

IN

560

DC INPUT ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

1.5 K 1K

74HCT14

IN

560

DC COM

Low to True Format - 1756-IG16 • -0.2…0.8V = Input guaranteed to be in on-state • 0.8…2.0V = Input state not guaranteed • 2.0…5.5V = Input guaranteed to be in off-state

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

77

Page 78

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IG16 Attribute

1756-IG16

Inputs

16 (8 points/group)

Voltage category

5V DC TTL source (Low=True)(1)

Operating voltage range

4.5…5.5V DC 50 mV P-P ripple max

Input delay time (screw to backplane) Off to On (5-to-0V DC transition) On to Off (0-to-5V DC transition)

Hardware delay: 270 s nom/450 s max + filter time User-selectable filter time: 0 ms, 1 ms, or 2 ms Hardware delay: 390 s nom/ 700 s max + filter time User-selectable filter time: 0 ms, 1 ms, 2 ms, 9 ms, or 18 ms

Current draw @ 5.1V

110 mA

Current draw @ 24V

2 mA

Total backplane power

0.61 W

Power dissipation, max

1.4 W @ 60 °C (140 °F)

Thermal dissipation

4.8 BTU/hr @ 60 °C (140 °F)

Off-state voltage, max

2V

Off-state current, max

4.1 mA

Input impedance, max

1.4 k min 1.5 k typical

Input current, nom

3.7 mA @ 5V DC

Input current, max

4.1 mA @ 5V DC

Cyclic update time

200 s…750 ms

Change of state

Software configurable

Time stamp of inputs

±200 μs

Isolation voltage

250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block housing

1756-TBNH 1756-TBSH

RTB keying

User-defined mechanical

Slot width

1

Wire category

2(2)

North American temperature code

T5

IEC temperature code

T5

Enclosure type

None (open-style)

Reverse polarity protection

No

(1) TTL inputs are inverted (-0.2 to +0.8 = low voltage = True = On.) Use a NOT instruction in your program to convert to traditional True - High logic. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

78

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 79

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IG16 Attribute

1756-IG16

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±1 kV at 5 kHz on signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-IG16 Certification(1)

1756-IG16

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T5 X Gc

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

79

Page 80

1756 ControlLogix I/O Specifications

1756-IH16I ControlLogix 125V DC isolated input module Simplified Schematic

1756-IH161 +5V

IN-0

DC-0 (-) Isolated Wiring

GND-0

DC-3 (-)

GND ControlLogix Backplane Interface

Display

DC-7 (-) Jumper Bar (Cut to Length)

Nonisolated Wiring

Additional jumper bars are available as catalog number 1756-JMPR.

DC (-)

GND-0

2

1

IN-0

GND-1 GND-2

4

3

6

5

IN-1 IN-2

GND-3 GND-4 GND-5 GND-6

8

7

Voltage category

125V DC sink/source

Operating voltage range

90…146V DC(1)

Input voltage, nom

125V DC

Input delay time (screw to backplane) Off to On On to Off

32 31

IN-12 IN-13 IN-14 IN-15

GND-15

34 33

Not Used

Not Used

36 35

Not Ysed

Hardware delay: 2 ms max + filter time User-selectable filter time: 0 ms, 1 ms, or 2 ms Hardware delay: 6 max + filter time User-selectable filter time: 0 ms, 1 ms, 2 ms, 9 ms, or 18 ms

Current draw @ 5.1V

125 mA

Current draw @ 24V

3 mA

Total backplane power

0.71 W

Power dissipation, max

5 W @ 60 °C (140 °F)

Thermal dissipation

17.05 BTU/hr

Off-state voltage, max

20V DC

Off-state current, max

0.8 mA

80

D C-7 (+)

20 19

Technical Specifications - 1756-IH16I

16 individually isolated

IN-7 IN-8

GND-9 GND-10 GND-11 GND-12 GND-13 GND-14 GND-15

ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

Inputs

14 13

DC-3 (+)

16 15

DC INPUT

1756-IH16I

12 11

IN-3 IN-4 IN-5 IN-6

GND-7 GND-8

Daisy Chain to Other RTBs

Attribute

10 9

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

18 17 22 21 24 23 26 25 28 27 30 29

DC-0 (+)

IN-9 IN-10 IN-11

DC (+)