The text of a spec sheet · part 8 of 25
1756 ControlLogix I/O Specifications, Technical Data, pages 71 to 80
Pages 71 to 80 of 242
The original document is the PDF (7.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-IB16, Allen-Bradley 1756-OB16E and Allen-Bradley 1756-TBNH
Page 71
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-IF16H (continued) Attribute
1756-IF16H
Repeatability
Better than 0.01% of range (15 Hz and 20 Hz filters only)
Calibrated accuracy
Better than 0.13% of range (all filters)
Calibration interval
12 months typical
Offset drift
27 V/°C
Gain drift with temperature
11ppm/°C
Module error
0.3% of range
Module input scan time, min
11…328 ms (filter dependent)
Module HART scan time
Estimate 1 s if all channels are HART enabled
Data format
Integer mode (left justified, 2 s complement) IEEE 32-bit floating point
Input conversion method
Successive approximation
Output conversion method
R-Ladder DAC, monotonicity with no missing codes
Module keying
Electronic, software configurable
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire size
1756-TBCH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max 1756-TBS6H Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max
Terminal block torque spec
1756-TBCH 0.5 N•m (4.4 lb•in)
Wire category(1)
2 - on signal ports
Wire type
Copper
North American temp code
T5
ATEX temp code
T4
IECEx temp code
T4
Enclosure type rating
None (open-style)
(1) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-IF16H Attribute
1756-IF16H
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
71
Page 72
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-IF16H (continued) Attribute
1756-IF16H
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions
IEC 61000-6-4
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±2 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on shielded ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-IF16H Certification(1)
1756-IF16H c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2014/30/EU EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
RCM
Australian Radiocommunications Act, compliant with: • EN 61000-6-4; Industrial Emissions
Ex
European Union 2014/34/EU ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • DEMKO12ATEX1219040X
IECEx
IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • IECEx UL 16.0109X
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3
EAC
Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
72
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 73
1756 ControlLogix I/O Specifications
1756-IF16IH ControlLogix current analog input module with HART protocol 2-wire HART Device 2-wire XMTR
Not Used
2
1
Not Used
+-
24V DC +
IN0
4
3
IN1
-
RTN0
6
5
RTN1
4-wire HART Device
IN2
8
7
IN3
RTN2
10
9
RTN3
IN4
12 11
IN5
RTN4
14 13
RTN5
IN6
16 15
IN7
RTN6
18 17
RTN7
Power Supply
24V DC Power Supply
+ +4-wire+ -
-
XMTR
-
ANALOG INPUT CAL OK HART
IN8
20 19
IN9
RTN8
22 21
RTN9
IN10
24 23
IN11
RTN10
26 25
RTN11
IN12
28 27
IN13
RTN12
30 29
RTN13 IN15
IN14
32 31
RTN14
34 33
RTN15
Not Used
36 35
Not Used
When a common supply is used, tie the IN- to RTN.
Technical Specifications - 1756-IF16IH Attribute
1756-IF16IH
Voltage and current ratings
Backplane: 225 mA @ 5.1V DC, 200 mA @ 24V DC 16 Inputs Input current range: 0…20 mA, 4…20 mA
Resolution
16…21 bits
Power dissipation
5.30 W
Inrush current
400 mA @ 5.1V DC 450 mA @ 24V DC
Isolation voltage
250V (continuous) Reinforced Insulation Type, inputs to backplane. Basic Insulation Type, input to input, and inputs to ground
Input impedance
250 (±5 )
Open circuit detection time
5 s, 4…20 mA range only
Input overvoltage protection
28.8V DC
Normal mode noise rejection
90 dB @ 50/60 Hz (10 Hz filter) 74 dB @ 50/60 Hz (15 Hz filter) 33 dB @ 60 Hz, 90 dB @60 Hz (20 Hz filter)
Common mode noise rejection
> 90 dB @ 50/60 Hz (10 Hz, 15 Hz, and 20 Hz filters only)
Calibrated accuracy at 25 °C with HART disabled
0.15…1.5% of full scale, dependent on selected filter
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
73
Page 74
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-IF16IH (continued) Attribute
1756-IF16IH
Calibrated accuracy at 25 °C with HART enabled
1.5% of full scale with 250 Hz filter 0.5% of full scale with 100 Hz filter 0.2% of full scale with 50 Hz or 60 Hz filter 0.15% of full scale with 15 Hz or 20 Hz filter Monotonicity not guaranteed
Calibrated accuracy over full temperature range with HART enabled
1.8% of full scale with 250 Hz filter 0.8% of full scale with 100 Hz filter 0.5% of full scale with 50 Hz or 60 Hz filter 0.4% of full scale with 15 Hz or 20 Hz filter Monotonicity not guaranteed
Calibration interval
12 months typical
Input offset drift with temperature
300 A/°C
Gain drift with temperature
20 ppm/°C
Module error over full temperature range with HART disabled
0.3% of range (all filters)
Module scan time for all channels - analog, min
14…428 ms (filter dependent)
Typical module HART dynamic variables update time for all channels
1 s typical with no pass through or device information messaging active
Data format
Integer mode (left justified, 2 s complement) IEEE 32-bit floating point
Input conversion method
Sigma-Delta ADC (24-bit converter)
Output conversion method
Sigma-Delta ADC (24-bit converter)
Module keying
ASIC does not support module keying
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire size
1756-TBCH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max 1756-TBS6H Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max
Terminal block torque specs
1756-TBCH 0.5 N•m (4.4 lb·in)
Wiring category(1)
2 - on signal ports
Wire type
Copper
North American temp code
T5
ATEX temp code
T4
IECEx temp code
T4
Enclosure type rating
None (open-style)
(1) Use this conductor category information for planning conductor routing. See Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
74
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 75
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-IF16IH Attribute
1756-IF16IH
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
IEC 61000-6-4
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…6000 MHz
EFT/B immunity IEC 61000-4-4
±2 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on shielded ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
75
Page 76
1756 ControlLogix I/O Specifications
Certifications - 1756-IF16IH Certification(1)
1756-IF16IH c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2014/30/EU EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2014/35/EU LVD, compliant with: • EN 61131-2; Programmable Controllers (Clause 11)
RCM
Australian Radiocommunications Act, compliant with: • EN 61000-6-4; Industrial Emissions
Ex
European Union 2014/34/EU ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • DEMKO14ATEX1238X
IECEx
IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • IECEx UL 16.0110X
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3
EAC
Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
76
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 77
1756 ControlLogix I/O Specifications
1756-IG16 ControlLogix TTL input module Standard Wiring
CE Compliant Wiring 1756-IG16
1756-IG16 – DC 2
IN-1
IN-0 4
IN-2 6
5
8
7
10
9
IN-4
IN-7
+
IN-6
DC Power Wire
6
5
8
7
IN-2
12
11
14
13
16
15
18
17
5V DC Power
12
11
14
13
DC COM 0
IN-8 IN-10 16
15
IN-12 18
17
20
19
DC-1(+)
19
+ – TTL Input Device
Capacitor 0.01 µF Typical (See notes below.)
IN-14
IN-15
IN-14
IN-15
9
IN-13
IN-12
IN-13
10
IN-11
IN-10
IN-11
I/O Wire
IN-6
IN-9
IN-8
IN-9
IN-4
IN-7
DC COM 0
I/O Wire
IN-0
DC-0(+)
–
DC-0(+)
20
3
IN-5
IN-5
+ DC
1
4
IN-3
3
IN-3
5V DC
2
IN-1
1
DC COM 1
DC COM 1
DC-1(+)
IMPORTANT: I/O cables must be shielded type and cable length must be <10 m (32.8 ft) for maximum EMI noise immunity.
Simplified Schematic +5 DC 1.5 K 1K
74HCT14
IN
560
DC INPUT ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K
1.5 K 1K
74HCT14
IN
560
DC COM
Low to True Format - 1756-IG16 • -0.2…0.8V = Input guaranteed to be in on-state • 0.8…2.0V = Input state not guaranteed • 2.0…5.5V = Input guaranteed to be in off-state
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
77
Page 78
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-IG16 Attribute
1756-IG16
Inputs
16 (8 points/group)
Voltage category
5V DC TTL source (Low=True)(1)
Operating voltage range
4.5…5.5V DC 50 mV P-P ripple max
Input delay time (screw to backplane) Off to On (5-to-0V DC transition) On to Off (0-to-5V DC transition)
Hardware delay: 270 s nom/450 s max + filter time User-selectable filter time: 0 ms, 1 ms, or 2 ms Hardware delay: 390 s nom/ 700 s max + filter time User-selectable filter time: 0 ms, 1 ms, 2 ms, 9 ms, or 18 ms
Current draw @ 5.1V
110 mA
Current draw @ 24V
2 mA
Total backplane power
0.61 W
Power dissipation, max
1.4 W @ 60 °C (140 °F)
Thermal dissipation
4.8 BTU/hr @ 60 °C (140 °F)
Off-state voltage, max
2V
Off-state current, max
4.1 mA
Input impedance, max
1.4 k min 1.5 k typical
Input current, nom
3.7 mA @ 5V DC
Input current, max
4.1 mA @ 5V DC
Cyclic update time
200 s…750 ms
Change of state
Software configurable
Time stamp of inputs
±200 μs
Isolation voltage
250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s
Module keying
Electronic, software configurable
Removable terminal block housing
1756-TBNH 1756-TBSH
RTB keying
User-defined mechanical
Slot width
1
Wire category
2(2)
North American temperature code
T5
IEC temperature code
T5
Enclosure type
None (open-style)
Reverse polarity protection
No
(1) TTL inputs are inverted (-0.2 to +0.8 = low voltage = True = On.) Use a NOT instruction in your program to convert to traditional True - High logic. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
78
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 79
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-IG16 Attribute
1756-IG16
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±1 kV at 5 kHz on signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-IG16 Certification(1)
1756-IG16
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T5 X Gc
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
79
Page 80
1756 ControlLogix I/O Specifications
1756-IH16I ControlLogix 125V DC isolated input module Simplified Schematic
1756-IH161 +5V
IN-0
DC-0 (-) Isolated Wiring
GND-0
DC-3 (-)
GND ControlLogix Backplane Interface
Display
DC-7 (-) Jumper Bar (Cut to Length)
Nonisolated Wiring
Additional jumper bars are available as catalog number 1756-JMPR.
DC (-)
GND-0
2
1
IN-0
GND-1 GND-2
4
3
6
5
IN-1 IN-2
GND-3 GND-4 GND-5 GND-6
8
7
Voltage category
125V DC sink/source
Operating voltage range
90…146V DC(1)
Input voltage, nom
125V DC
Input delay time (screw to backplane) Off to On On to Off
32 31
IN-12 IN-13 IN-14 IN-15
GND-15
34 33
Not Used
Not Used
36 35
Not Ysed
Hardware delay: 2 ms max + filter time User-selectable filter time: 0 ms, 1 ms, or 2 ms Hardware delay: 6 max + filter time User-selectable filter time: 0 ms, 1 ms, 2 ms, 9 ms, or 18 ms
Current draw @ 5.1V
125 mA
Current draw @ 24V
3 mA
Total backplane power
0.71 W
Power dissipation, max
5 W @ 60 °C (140 °F)
Thermal dissipation
17.05 BTU/hr
Off-state voltage, max
20V DC
Off-state current, max
0.8 mA
80
D C-7 (+)
20 19
Technical Specifications - 1756-IH16I
16 individually isolated
IN-7 IN-8
GND-9 GND-10 GND-11 GND-12 GND-13 GND-14 GND-15
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K
Inputs
14 13
DC-3 (+)
16 15
DC INPUT
1756-IH16I
12 11
IN-3 IN-4 IN-5 IN-6
GND-7 GND-8
Daisy Chain to Other RTBs
Attribute
10 9
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
18 17 22 21 24 23 26 25 28 27 30 29
DC-0 (+)
IN-9 IN-10 IN-11
DC (+)