The text of a spec sheet · part 7 of 25
1756 ControlLogix I/O Specifications, Technical Data, pages 61 to 70
Pages 61 to 70 of 242
The original document is the PDF (7.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-IB16, Allen-Bradley 1756-OB16E and Allen-Bradley 1756-TBNH
Page 61
1756 ControlLogix I/O Specifications
1756-IF8IH ControlLogix isolated current analog input module with HART protocol i
ANALOG INPUT
+
+
2
1
Not Used
IN0
4
3
IN1
CAL
RTN0
6
5
RTN1
OK
Reserved
8
7
Reserved
Reserved
10
9
Reserved
IN2
12 11
IN3
RTN2
14 13
RTN3
Reserved
16 15
Reserved
Reserved
18 17
Reserved
IN4
20 19
IN5
RTN4
22 21
RTN5
Reserved
24 23
Reserved
Reserved
Reserved
A
26 25
IN6
28 27
IN7
A
RTN6
30 29
RTN7
Reserved
32 31
Reserved
Reserved
34 33
Reserved
Not Used
36 35
Not Used
A A
–
–
Not Used i
HART
Technical Specifications - 1756-IF8IH Attribute
1756-IF8IH
Inputs
Eight current inputs
Input range
0…20 mA (0…20.58 mA) 4…20 mA (3.42…20.58 mA)
Resolution
16…21 bits
Voltage and current ratings
Backplane: 210 mA @ 5.1V DC, 110 mA @ 24V DC Input voltage range: 5…30V DC Input current range: 0…20 mA, 4…20 mA
Power dissipation within module
4W
Inrush current
400 mA @ 5V 450 mA @ 24V
Isolation voltage
250V (continuous) Reinforced Insulation Type, inputs to backplane. Basic Insulation Type, input to input, and inputs to ground. Type tested at 3535V DC for 60 s, inputs to backplane. Type tested at 2120V DC for 60 s, input to input, and inputs to ground.
Input impedance
250 ±5
Open circuit detection time
5 s (4...20 mA range only)
Input overvoltage protection
+28.8V DC
Normal mode noise rejection
> 90 dB @ 50 Hz and 60 Hz with 10 Hz filter > 74 dB @ 50 Hz and 60 Hz with 15 Hz filter > 33 dB @ 50 Hz and > 90 dB @ 60 Hz with 20 Hz filter
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
61
Page 62
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-IF8IH (continued) Attribute
1756-IF8IH
Common mode noise rejection
> 90 dB @ 50 Hz and 60 Hz (10 Hz, 15 Hz, or 20 Hz filters only)
Calibrated accuracy at 25 °C with HART disabled
0.15…1.5% of full scale, filter dependent
Calibrated accuracy at 25 °C with HART enabled
1.5% of full scale with 250 Hz filter 0.5% of full scale with 100 Hz filter 0.2% of full scale with 50 Hz or 60 Hz filter 0.15% of full scale with 15 Hz or 20 Hz filter Monotonicity not guaranteed
Calibrated accuracy over full temperature range with HART enabled
1.8% of full scale with 250 Hz filter 0.8% of full scale with 100 Hz filter 0.5% of full scale with 50 Hz or 60 Hz filter 0.4% of full scale with 15 Hz or 20 Hz filter Monotonicity not guaranteed
Calibration interval
12 months typical
Input offset drift with temperature
<=300 A/°C
Gain drift with temperature
20 ppm/°C
Module error over full temperature range with HART disabled
0.3% of range (all filters)
Module scan time for all channels - analog, min
18…488 ms (filter dependent)
Typical module HART dynamic variables update time for all channels
1 s typical if all channels are HART enabled Pass through messages, handheld communications, secondary masters, communication errors, or configuration changes can significantly increase the update time.
Data format
32-bit floating point
Input conversion method
Sigma-Delta ADC (24-bit converter)
Module keying
Electronic, software configurable
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire Size
1756-TBCH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max 1756-TBS6H Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max
Terminal block torque specs
1756-TBCH 0.4 N•m (4. 4 lb•in)
Wire category
2 - on signal ports(1)
Wire type
Copper
North American temp code
T5
ATEX temp code
T4
IECEx temp code
T4
Enclosure type
None (open-style)
(1) Use this conductor category information for planning conductor routing. See Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
62
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 63
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-IF8IH Attribute
1756-IF8IH
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
IEC 61000-6-4
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±2 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on shielded ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
63
Page 64
1756 ControlLogix I/O Specifications
Certifications - 1756-IF8IH Certification(1)
1756-IF8IH c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584 UL Listed for Class I, Division 2 Group A, B, C, D Hazardous Locations, certified for US and Canada. See UL File E194810.
CE
European Union 2014/30/EU EMC Directive, compliant with: • EN 61326-1: Meas./Control/Lab., Industrial Requirements • EN 61000-6-2: Industrial Immunity • EN 61000-6-4: Industrial Emissions • EN 61131-2: Programmable Controllers (Clause 8, Zone A and B) European Union 2014/35/EU LVD, compliant with: • EN 61131-2: Programmable Controllers (Clause 11)
RCM
Australian Radiocommunications Act, compliant with: • EN 61000-6-4: Industrial Emissions
Ex
European Union 2014/34/EU ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • DEMKO14ATEX1238X
IECEx
IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • IECEx UL 16.0110X
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3
EAC
Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
64
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 65
1756 ControlLogix I/O Specifications
1756-IF16 ControlLogix voltage/current analog input module 1756-IF16 Differential Current Channel 0
Channel 0 i A
Shield Ground Channel 3 2-wire Transmitter
1756-IF16 Differential Voltage i A
1 i RTN-0 i RTN-1
IN-0 IN-1
2 4
3
IN-2
6
5
IN-3
8
7
RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9
10
IN-10 IN-11 RTN IN-12 IN-13 IN-14
24 23
34 33 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14
IN-15
36 35 i RTN-15
9
12 11 14 13 16 15 18 17 20 19 22 21
26 25 28 27 30 29 32 31 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9
Use this table when wiring your module in Differential mode.
+ –
Jumper Shield Ground Wires
Channel 3
+ –
Shield Ground
IN-0 IN-1 IN-2 IN-3
1
4
3 i RTN-0 i RTN-1
6
5 i RTN-2
8
7 i RTN-3
RTN IN-4 IN-5 IN-6 IN-7
10
9
IN-8 IN-9
20 19
RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9
IN-10 IN-11 RTN IN-12 IN-13 IN-14
24 23
IN-15
12 11 14 13 16 15 18 17
22 21
32 31 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13
34 33 i RTN-14
36 35 i RTN-15
26 25 28 27 30 29
Use this table when wiring your module in Differential mode.
This channel
Uses these terminals
This channel
Uses these terminals
Channel 0
IN-0 (+), IN-1 (-), i RTN-0
Channel 0
IN-0 (+), IN-1 (-)
Channel 1
IN-2 (+), IN-3 (-), i RTN-2
Channel 1
IN-2 (+), IN-3 (-)
Channel 2
IN-4 (+), IN-5 (-), i RTN-4
Channel 2
IN-4 (+), IN-5 (-)
Channel 3
IN-6 (+), IN-7 (-), i RTN-6
Channel 3
IN-6 (+), IN-7 (-)
Channel 4
IN-8 (+), IN-9 (-), i RTN-8
Channel 4
IN-8 (+), IN-9 (-)
Channel 5
IN-10 (+), IN-11 (-), i RTN-10
Channel 5
IN-10 (+), IN-11 (-)
Channel 6
IN-12 (+), IN-13 (-), i RTN-12
Channel 6
IN-12 (+), IN-13 (-)
Channel 7
IN-14 (+), IN-15 (-), i RTN-14
Channel 7
IN-14 (+), IN-15 (-)
• All terminals marked RTN are connected internally. • A 249 current loop resistor is located between IN-x and i RTN-x terminals. • If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the accuracy of the module. • Place additional loop devices (such as strip chart recorders) at the A location in the current loop.
2
• All terminals marked RTN are connected internally. • If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the accuracy of the module. • Terminals marked RTN or i RTN are not used for differential voltage wiring. IMPORTANT: When operating in 4-channel, High-Speed mode, only use channels 0, 2, 4, and 6.
IMPORTANT: When operating in 4-channel, High-Speed mode, only use channels 0, 2, 4, and 6.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
65
Page 66
1756 ControlLogix I/O Specifications
1756-IF16 Single-ended Voltage
1756-IF16 Single-ended Current i
+ IN-0 IN-1 IN-2 IN-3
Shield Ground 2-wire Transmitter i A
2
1
4
3
6
5
8
7 9 i RTN-0 i RTN-1 i RTN-2 i RTN-3
RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9
10
IN-10 IN-11 RTN IN-12 IN-13 IN-14
24 23
34 33 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14
IN-15
36 35 i RTN-15
12 11 14 13 16 15 18 17 20 19 22 21
26 25 28 27 30 29 32 31
RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9
• All terminals marked RTN are connected internally. • For current applications, all terminals marked i RTN must be wired to terminals marked RTN. • A 249 current loop resistor is located between IN-x and iRTN-x terminals. • Place additional loop devices (such as strip chart recorders) at the A location in the current loop.
–
Jumper Wires Shield Ground
+ –
Shield Ground
1
4
3 i RTN-0 i RTN-1
IN-2
6
5 i RTN-2
IN-3
8
7 i RTN-3
RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9
10
9
RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9
IN-10 IN-11 RTN IN-12 IN-13
24 23
32 31 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13
IN-14
34 33 i RTN-14
IN-15
36 35 i RTN-15
12 11 14 13 16 15 18 17 20 19 22 21
26 25 28 27 30 29
• All terminals marked RTN are connected internally. • Terminals marked i RTN are not used for single-ended voltage wiring.
ANALOG INPUT CAL OK
66
2
IN-0 IN-1
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 67
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-IF16 Attribute
1756-IF16
Inputs
16 single ended, 8 differential or 4 differential (high speed)
Input range
±10V 0…10V 0…5V 0…20 mA
Resolution
320 μV/count (15 bits + sign bipolar) @ ±10.25V 160 μV/count (16 bits) @ 0…10.25V 80 μV/count (16 bits) @ 0…5.125V 0.32 μA/count (16 bits) @ 0…20.5 mA
Current draw @ 5.1V
150 mA
Current draw @ 24V
65 mA
Total backplane power
2.33 W
Voltage and current ratings
Backplane: 5.1V DC, 150mA max 24V DC, 65mA max Input Voltage Range: -10…+10V Input Current Range: 4…20mA Limited to 100VA
Power consumption
2.3 W
Power dissipation
Voltage: 2.3 W Current: 3.9 W
Thermal dissipation
Voltage: 7.84 BTU/hr Current: 13.3 BTU/hr
Input impedance
Voltage: >10 M Current: 249
Open circuit detection time
Differential voltage - Positive full scale reading within 5 s Single-ended/differential current - Negative full scale reading within 5 s Single-ended voltage - Even-numbered channels go to positive full scale reading within 5 s, odd-numbered channels go to negative full scale reading within 5 s
Overvoltage protection, max
Voltage: 30V DC Current: 8V DC
Normal mode noise rejection
>80 dB @ 50/60 Hz(2)
Common mode noise rejection
>100 dB @ 50/60 Hz
Channel bandwidth
15 Hz (-3 dB)(1)
Settling time
<80 ms to 5% of full scale(1)
Calibrated accuracy 25 °C (77 °F)
Voltage: Better than 0.05% of range Current: Better than 0.15% of range
Offset drift
45 V/°C
Gain drift with temperature
Voltage: 15 ppm/°C Current: 20 ppm/°C
Module error
Voltage: 0.1% of range Current: 0.3% of range
Module input scan time, min
16 pt single-ended: 16…488 ms 8 pt differential: 8…244 ms 4 pt differential: 5…122 ms(1)
Onboard data alarming
Yes
Scaling to engineering units
Yes
Real-time channel sampling
Yes
Data format
Integer mode (left justified, 2 s complement) IEEE 32-bit floating point
Module conversion method
Sigma-Delta
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
67
Page 68
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-IF16 (continued) Attribute
1756-IF16
Isolation voltage
250V (continuous), Reinforced insulation type, Inputs-to-Backplane. No isolation between individual Inputs. Routine tested at 1350V AC for 2 s
Module keying
Electronic, software configurable
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire size
1756-TBCH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max 1756-TBS6H Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max
Terminal block torque specs
1756-TBCH: 0.5 N•m (4.4 lb•in)
Wire category(1)
2 - on signal ports
North American temp code
T4A
ATEX temp code
T4
IECEx temp code
T4
Enclosure type
None (open-style)
(1) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. (2) Notch filter dependent.
Environmental Specifications - 1756-IF16 Attribute
1756-IF16
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
IEC 61000-6-4
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
68
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 69
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-IF16 (continued) Attribute
1756-IF16
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±2 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on shielded ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-IF16 Certification(1)
1756-IF16
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
CE
European Union 2014/30/EU EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2014/35/EU LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
RCM
Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions
Ex
European Union 2014/34/EU ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • DEMKO15ATEX1482X
IECEx
IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • IECEx UL 15.0053X
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
EAC
Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
69
Page 70
1756 ControlLogix I/O Specifications
1756-IF16H ControlLogix current analog input module with HART protocol
+-
+ -
2
1
IN0
4
3
IN1
RTN0
6
5
RTN1
IN2
8
7
IN3
RTN2
10
9
RTN3
+ + +
IN4
12 11
IN5
-
RTN4
14 13
RTN5
IN6
16 15
IN7
RTN6
18 17
RTN7
-
-
ANALOG INPUT CAL OK
IN8
20 19
IN9
RTN8
22 21
RTN9
IN10
24 23
IN11
RTN10
26 25
RTN11
IN12
28 27
IN13
RTN12
30 29
RTN13
IN14
32 31
IN15
RTN14
34 33
RTN15
HART
36 35
Technical Specifications - 1756-IF16H Attribute
1756-IF16H
Inputs
16 differential, current Dedicated HART modem per channel
Input range
0…20 mA 4…20 mA
Resolution
16…21 bits
Voltage and current ratings
Backplane: 5.1V DC @ 200 mA, 24V DC @ 125 mA Input current range: 0…20 mA, 4…20 mA
Total backplane power
4.02 W
Power dissipation, max
6W
Isolation voltage
50V (continuous), Basic insulation type, Input Channels to Backplane No isolation between individual Input Channels Type tested at 1500V DC for 60 s
Thermal dissipation
12 BTU/hr
Input impedance
249
Open circuit detection time
Positive full scale reading within 5 s
Overvoltage protection, max
8V DC
Normal mode noise rejection
74 dB @ 50/60 Hz (15 Hz filter) 90 dB @ 60 Hz (20 Hz filter)
Common mode noise rejection
> 90 dB @ 50/60 Hz (15 Hz and 20 Hz filters only)
70
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
When a common supply is used, tie the IN- to RTN.