Page 61

1756 ControlLogix I/O Specifications

1756-IF8IH ControlLogix isolated current analog input module with HART protocol i

ANALOG INPUT

+

+

2

1

Not Used

IN0

4

3

IN1

CAL

RTN0

6

5

RTN1

OK

Reserved

8

7

Reserved

Reserved

10

9

Reserved

IN2

12 11

IN3

RTN2

14 13

RTN3

Reserved

16 15

Reserved

Reserved

18 17

Reserved

IN4

20 19

IN5

RTN4

22 21

RTN5

Reserved

24 23

Reserved

Reserved

Reserved

A

26 25

IN6

28 27

IN7

A

RTN6

30 29

RTN7

Reserved

32 31

Reserved

Reserved

34 33

Reserved

Not Used

36 35

Not Used

A A

–

–

Not Used i

HART

Technical Specifications - 1756-IF8IH Attribute

1756-IF8IH

Inputs

Eight current inputs

Input range

0…20 mA (0…20.58 mA) 4…20 mA (3.42…20.58 mA)

Resolution

16…21 bits

Voltage and current ratings

Backplane: 210 mA @ 5.1V DC, 110 mA @ 24V DC Input voltage range: 5…30V DC Input current range: 0…20 mA, 4…20 mA

Power dissipation within module

4W

Inrush current

400 mA @ 5V 450 mA @ 24V

Isolation voltage

250V (continuous) Reinforced Insulation Type, inputs to backplane. Basic Insulation Type, input to input, and inputs to ground. Type tested at 3535V DC for 60 s, inputs to backplane. Type tested at 2120V DC for 60 s, input to input, and inputs to ground.

Input impedance

250 ±5

Open circuit detection time

5 s (4...20 mA range only)

Input overvoltage protection

+28.8V DC

Normal mode noise rejection

> 90 dB @ 50 Hz and 60 Hz with 10 Hz filter > 74 dB @ 50 Hz and 60 Hz with 15 Hz filter > 33 dB @ 50 Hz and > 90 dB @ 60 Hz with 20 Hz filter

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

61

Page 62

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IF8IH (continued) Attribute

1756-IF8IH

Common mode noise rejection

> 90 dB @ 50 Hz and 60 Hz (10 Hz, 15 Hz, or 20 Hz filters only)

Calibrated accuracy at 25 °C with HART disabled

0.15…1.5% of full scale, filter dependent

Calibrated accuracy at 25 °C with HART enabled

1.5% of full scale with 250 Hz filter 0.5% of full scale with 100 Hz filter 0.2% of full scale with 50 Hz or 60 Hz filter 0.15% of full scale with 15 Hz or 20 Hz filter Monotonicity not guaranteed

Calibrated accuracy over full temperature range with HART enabled

1.8% of full scale with 250 Hz filter 0.8% of full scale with 100 Hz filter 0.5% of full scale with 50 Hz or 60 Hz filter 0.4% of full scale with 15 Hz or 20 Hz filter Monotonicity not guaranteed

Calibration interval

12 months typical

Input offset drift with temperature

<=300 A/°C

Gain drift with temperature

20 ppm/°C

Module error over full temperature range with HART disabled

0.3% of range (all filters)

Module scan time for all channels - analog, min

18…488 ms (filter dependent)

Typical module HART dynamic variables update time for all channels

1 s typical if all channels are HART enabled Pass through messages, handheld communications, secondary masters, communication errors, or configuration changes can significantly increase the update time.

Data format

32-bit floating point

Input conversion method

Sigma-Delta ADC (24-bit converter)

Module keying

Electronic, software configurable

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire Size

1756-TBCH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max 1756-TBS6H Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max

Terminal block torque specs

1756-TBCH 0.4 N•m (4. 4 lb•in)

Wire category

2 - on signal ports(1)

Wire type

Copper

North American temp code

T5

ATEX temp code

T4

IECEx temp code

T4

Enclosure type

None (open-style)

(1) Use this conductor category information for planning conductor routing. See Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

62

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 63

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IF8IH Attribute

1756-IF8IH

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

IEC 61000-6-4

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±2 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on shielded ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

63

Page 64

1756 ControlLogix I/O Specifications

Certifications - 1756-IF8IH Certification(1)

1756-IF8IH c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584 UL Listed for Class I, Division 2 Group A, B, C, D Hazardous Locations, certified for US and Canada. See UL File E194810.

CE

European Union 2014/30/EU EMC Directive, compliant with: • EN 61326-1: Meas./Control/Lab., Industrial Requirements • EN 61000-6-2: Industrial Immunity • EN 61000-6-4: Industrial Emissions • EN 61131-2: Programmable Controllers (Clause 8, Zone A and B) European Union 2014/35/EU LVD, compliant with: • EN 61131-2: Programmable Controllers (Clause 11)

RCM

Australian Radiocommunications Act, compliant with: • EN 61000-6-4: Industrial Emissions

Ex

European Union 2014/34/EU ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • DEMKO14ATEX1238X

IECEx

IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • IECEx UL 16.0110X

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3

EAC

Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation

(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

64

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 65

1756 ControlLogix I/O Specifications

1756-IF16 ControlLogix voltage/current analog input module 1756-IF16 Differential Current Channel 0

Channel 0 i A

Shield Ground Channel 3 2-wire Transmitter

1756-IF16 Differential Voltage i A

1 i RTN-0 i RTN-1

IN-0 IN-1

2 4

3

IN-2

6

5

IN-3

8

7

RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9

10

IN-10 IN-11 RTN IN-12 IN-13 IN-14

24 23

34 33 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14

IN-15

36 35 i RTN-15

9

12 11 14 13 16 15 18 17 20 19 22 21

26 25 28 27 30 29 32 31 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9

Use this table when wiring your module in Differential mode.

+ –

Jumper Shield Ground Wires

Channel 3

+ –

Shield Ground

IN-0 IN-1 IN-2 IN-3

1

4

3 i RTN-0 i RTN-1

6

5 i RTN-2

8

7 i RTN-3

RTN IN-4 IN-5 IN-6 IN-7

10

9

IN-8 IN-9

20 19

RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9

IN-10 IN-11 RTN IN-12 IN-13 IN-14

24 23

IN-15

12 11 14 13 16 15 18 17

22 21

32 31 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13

34 33 i RTN-14

36 35 i RTN-15

26 25 28 27 30 29

Use this table when wiring your module in Differential mode.

This channel

Uses these terminals

This channel

Uses these terminals

Channel 0

IN-0 (+), IN-1 (-), i RTN-0

Channel 0

IN-0 (+), IN-1 (-)

Channel 1

IN-2 (+), IN-3 (-), i RTN-2

Channel 1

IN-2 (+), IN-3 (-)

Channel 2

IN-4 (+), IN-5 (-), i RTN-4

Channel 2

IN-4 (+), IN-5 (-)

Channel 3

IN-6 (+), IN-7 (-), i RTN-6

Channel 3

IN-6 (+), IN-7 (-)

Channel 4

IN-8 (+), IN-9 (-), i RTN-8

Channel 4

IN-8 (+), IN-9 (-)

Channel 5

IN-10 (+), IN-11 (-), i RTN-10

Channel 5

IN-10 (+), IN-11 (-)

Channel 6

IN-12 (+), IN-13 (-), i RTN-12

Channel 6

IN-12 (+), IN-13 (-)

Channel 7

IN-14 (+), IN-15 (-), i RTN-14

Channel 7

IN-14 (+), IN-15 (-)

• All terminals marked RTN are connected internally. • A 249 current loop resistor is located between IN-x and i RTN-x terminals. • If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the accuracy of the module. • Place additional loop devices (such as strip chart recorders) at the A location in the current loop.

2

• All terminals marked RTN are connected internally. • If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the accuracy of the module. • Terminals marked RTN or i RTN are not used for differential voltage wiring. IMPORTANT: When operating in 4-channel, High-Speed mode, only use channels 0, 2, 4, and 6.

IMPORTANT: When operating in 4-channel, High-Speed mode, only use channels 0, 2, 4, and 6.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

65

Page 66

1756 ControlLogix I/O Specifications

1756-IF16 Single-ended Voltage

1756-IF16 Single-ended Current i

+ IN-0 IN-1 IN-2 IN-3

Shield Ground 2-wire Transmitter i A

2

1

4

3

6

5

8

7 9 i RTN-0 i RTN-1 i RTN-2 i RTN-3

RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9

10

IN-10 IN-11 RTN IN-12 IN-13 IN-14

24 23

34 33 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14

IN-15

36 35 i RTN-15

12 11 14 13 16 15 18 17 20 19 22 21

26 25 28 27 30 29 32 31

RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9

• All terminals marked RTN are connected internally. • For current applications, all terminals marked i RTN must be wired to terminals marked RTN. • A 249 current loop resistor is located between IN-x and iRTN-x terminals. • Place additional loop devices (such as strip chart recorders) at the A location in the current loop.

–

Jumper Wires Shield Ground

+ –

Shield Ground

1

4

3 i RTN-0 i RTN-1

IN-2

6

5 i RTN-2

IN-3

8

7 i RTN-3

RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9

10

9

RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9

IN-10 IN-11 RTN IN-12 IN-13

24 23

32 31 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13

IN-14

34 33 i RTN-14

IN-15

36 35 i RTN-15

12 11 14 13 16 15 18 17 20 19 22 21

26 25 28 27 30 29

• All terminals marked RTN are connected internally. • Terminals marked i RTN are not used for single-ended voltage wiring.

ANALOG INPUT CAL OK

66

2

IN-0 IN-1

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 67

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IF16 Attribute

1756-IF16

Inputs

16 single ended, 8 differential or 4 differential (high speed)

Input range

±10V 0…10V 0…5V 0…20 mA

Resolution

320 μV/count (15 bits + sign bipolar) @ ±10.25V 160 μV/count (16 bits) @ 0…10.25V 80 μV/count (16 bits) @ 0…5.125V 0.32 μA/count (16 bits) @ 0…20.5 mA

Current draw @ 5.1V

150 mA

Current draw @ 24V

65 mA

Total backplane power

2.33 W

Voltage and current ratings

Backplane: 5.1V DC, 150mA max 24V DC, 65mA max Input Voltage Range: -10…+10V Input Current Range: 4…20mA Limited to 100VA

Power consumption

2.3 W

Power dissipation

Voltage: 2.3 W Current: 3.9 W

Thermal dissipation

Voltage: 7.84 BTU/hr Current: 13.3 BTU/hr

Input impedance

Voltage: >10 M Current: 249

Open circuit detection time

Differential voltage - Positive full scale reading within 5 s Single-ended/differential current - Negative full scale reading within 5 s Single-ended voltage - Even-numbered channels go to positive full scale reading within 5 s, odd-numbered channels go to negative full scale reading within 5 s

Overvoltage protection, max

Voltage: 30V DC Current: 8V DC

Normal mode noise rejection

>80 dB @ 50/60 Hz(2)

Common mode noise rejection

>100 dB @ 50/60 Hz

Channel bandwidth

15 Hz (-3 dB)(1)

Settling time

<80 ms to 5% of full scale(1)

Calibrated accuracy 25 °C (77 °F)

Voltage: Better than 0.05% of range Current: Better than 0.15% of range

Offset drift

45 V/°C

Gain drift with temperature

Voltage: 15 ppm/°C Current: 20 ppm/°C

Module error

Voltage: 0.1% of range Current: 0.3% of range

Module input scan time, min

16 pt single-ended: 16…488 ms 8 pt differential: 8…244 ms 4 pt differential: 5…122 ms(1)

Onboard data alarming

Yes

Scaling to engineering units

Yes

Real-time channel sampling

Yes

Data format

Integer mode (left justified, 2 s complement) IEEE 32-bit floating point

Module conversion method

Sigma-Delta

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

67

Page 68

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IF16 (continued) Attribute

1756-IF16

Isolation voltage

250V (continuous), Reinforced insulation type, Inputs-to-Backplane. No isolation between individual Inputs. Routine tested at 1350V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire size

1756-TBCH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max 1756-TBS6H Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max

Terminal block torque specs

1756-TBCH: 0.5 N•m (4.4 lb•in)

Wire category(1)

2 - on signal ports

North American temp code

T4A

ATEX temp code

T4

IECEx temp code

T4

Enclosure type

None (open-style)

(1) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. (2) Notch filter dependent.

Environmental Specifications - 1756-IF16 Attribute

1756-IF16

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

IEC 61000-6-4

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

68

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 69

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IF16 (continued) Attribute

1756-IF16

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±2 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on shielded ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-IF16 Certification(1)

1756-IF16

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

CE

European Union 2014/30/EU EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2014/35/EU LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

RCM

Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions

Ex

European Union 2014/34/EU ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • DEMKO15ATEX1482X

IECEx

IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • IECEx UL 15.0053X

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

EAC

Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

69

Page 70

1756 ControlLogix I/O Specifications

1756-IF16H ControlLogix current analog input module with HART protocol

+-

+ -

2

1

IN0

4

3

IN1

RTN0

6

5

RTN1

IN2

8

7

IN3

RTN2

10

9

RTN3

+ + +

IN4

12 11

IN5

-

RTN4

14 13

RTN5

IN6

16 15

IN7

RTN6

18 17

RTN7

-

-

ANALOG INPUT CAL OK

IN8

20 19

IN9

RTN8

22 21

RTN9

IN10

24 23

IN11

RTN10

26 25

RTN11

IN12

28 27

IN13

RTN12

30 29

RTN13

IN14

32 31

IN15

RTN14

34 33

RTN15

HART

36 35

Technical Specifications - 1756-IF16H Attribute

1756-IF16H

Inputs

16 differential, current Dedicated HART modem per channel

Input range

0…20 mA 4…20 mA

Resolution

16…21 bits

Voltage and current ratings

Backplane: 5.1V DC @ 200 mA, 24V DC @ 125 mA Input current range: 0…20 mA, 4…20 mA

Total backplane power

4.02 W

Power dissipation, max

6W

Isolation voltage

50V (continuous), Basic insulation type, Input Channels to Backplane No isolation between individual Input Channels Type tested at 1500V DC for 60 s

Thermal dissipation

12 BTU/hr

Input impedance

249

Open circuit detection time

Positive full scale reading within 5 s

Overvoltage protection, max

8V DC

Normal mode noise rejection

74 dB @ 50/60 Hz (15 Hz filter) 90 dB @ 60 Hz (20 Hz filter)

Common mode noise rejection

> 90 dB @ 50/60 Hz (15 Hz and 20 Hz filters only)

70

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

When a common supply is used, tie the IN- to RTN.