For the Allen-Bradley 1756-IB16, Allen-Bradley 1756-OB16E and Allen-Bradley 1756-TBNH
Page 51
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-IF8 Attribute
1756-IF8
Inputs
8 single-ended 4 differential 2 high-speed differential
Input range
±10V 0…10V 0…5V 0…20 mA
Resolution
±10.25V: 320 V/count (15 bits plus sign bipolar) 0…10.25V: 160 V/count (16 bits) 0…5.125V: 80 /V count (16 bits) 0…20.5mA: 0.32 A/count (16 bits)
Current draw @ 5.1V
150 mA
Current draw @ 24V
40 mA
Total backplane power
1.73 W
Voltage and current ratings
Backplane: 5.1V DC, 150 mA max, 24V DC, 40mA max Input voltage range: -10…+10V Input current range: 4…20mA Limited to 100VA
Power consumption
1.73 W
Power dissipation
Voltage: 1.73 W Current 2.33 W
Thermal dissipation
Voltage: 5.88 BTU/hr Current: 7.92 BTU/hr
Input impedance
Voltage: >1 M Current: 249
Open circuit detection time
Differential voltage: Positive full scale reading within 5 s Single-ended/diff. current: Negative full scale reading within 5 s Single-ended voltage: Even-numbered channels go to positive full scale reading within 5 s, odd-numbered channels go to negative full scale reading within 5 s
Overvoltage protection, max
Voltage: 30V DC Current: 8V DC
Normal mode noise rejection
>80 dB @ 50/60 Hz(2)
Common mode noise rejection
>100 dB @ 50/60 Hz
Calibrated accuracy 25 °C (77 °F)
Voltage: Better than 0.05% of range Current: Better than 0.15% of range
Calibration interval
12 months
Offset drift
45 V/°C
Gain drift with temperature
Voltage: 15 ppm/°C Current: 20 ppm/°C
Module error
Voltage: 0.1% of range Current: 0.3% of range
Module input scan time, min
8 pt single-ended (floating point): 16…488 ms 4 pt differential (floating point): 8…244 ms 2 pt differential (floating point): 5…122 m(1)
Onboard data alarming
Yes
Scaling to engineering units
Yes
Real-time channel sampling
Yes
Data format
Integer mode (left justified, 2 s complement) IEEE 32-bit floating point
Module conversion method
Sigma-Delta
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
51
Page 52
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-IF8 (continued) Attribute
1756-IF8
Isolation voltage
250V (continuous), Reinforced insulation type, Inputs to Backplane. No isolation between individual Inputs. Routine tested at 1350V AC for 2 s
Module keying
Electronic, software configurable
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire size
1756-TBCH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max 1756-TBS6H Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at |105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max
Terminal block torque specs
1756-TBCH: 0.5 N•m (4.4 lb•in)
Wiring category(1)
2 - on signal ports
North American temp code
T4A
ATEX temp code
T4
IECEx temp code
T4
Enclosure type
None (open-style)
(1) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. (2) Notch filter dependent.
Environmental Specifications - 1756-IF8 Attribute
1756-IF8
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
IEC 61000-6-4
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
52
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 53
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-IF8 (continued) Attribute
1756-IF8
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±2 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on shielded ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-IF8 Certification(1)
1756-IF8
UL
UL Listed Industrial Control Equipment. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
CE
European Union 2014/30/EU EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2014/35/EU LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
RCM
Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions
Ex
European Union 2014/34/EU ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • DEMKO15ATEX1482X
IECEx
IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • IECEx UL 15.0053X
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
EAC
Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1)
See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
53
Page 54
1756 ControlLogix I/O Specifications
1756-IF8H ControlLogix voltage/current analog input module with HART protocol 1756-IF8H Current
1756-IF8H Voltage
ANALOG INPUT
Voltage Input 2-wire Current Inputs
+V
2-Wire XMTR 24V DC Power Supply
+ -
+-
4-wire Current Inputs 24V DC Power Supply
+ +4-Wire+ - XMTR - -
IN0+
2
1
I RTN-0
IN0-
4
3
NC
IN1+
6
5
I RTN-1
IN1-
8
7
NC
RTN
10 9
RTN
IN2+
12 11
I RTN-2
IN2-
14 13
NC
IN3+
16 15
I RTN-3
IN3-
18 17
NC
IN4+
20 19
I RTN-4
IN4-
22 21
NC
NC
IN5+
24 23
I RTN-5
24 23
I RTN-5
IN5-
26 25
NC
IN5-
26 25
NC
RTN
28 27
RTN
RTN
28 27
RTN
IN6+
30 29
I RTN-6
IN6+
30 29
I RTN-6
IN6-
32 31
NC
IN6-
32 31
NC
IN7+
34 33
I RTN-7
IN7+
34 33
I RTN-7
IN7-
36 35
NC
IN7-
36 35
NC
-V IN0+
2
1
I RTN-0
IN0-
4
3
NC
IN1+
6
5
I RTN-1
IN1-
8
7
NC
RTN
10 9
RTN
IN2+
12 11
I RTN-2
IN2-
14 13
NC
IN3+
16 15
I RTN-3
IN3-
18 17
NC
IN4+
20 19
I RTN-4
IN4-
22 21
IN5+
Technical Specifications - 1756-IF8H Attribute
1756-IF8H
Inputs
Eight differential voltage or current inputs, one HART modem per module
Input range
±10V 0…5V 1…5V 0…10V 0…20 mA 4…20 mA
Resolution
16…21 bits
Voltage and current ratings
Backplane: 5.1V DC, 300mA, 24V DC, 135mA Input voltage range: -10…+10V Input current range: 0…20 mA, 4…20mA
Total backplane power
4.77 W
Power dissipation
Voltage: 3.21 W Current: 4.01 W
Thermal dissipation
Voltage: 11.0 BTU/hr Current: 13.7 BTU/hr
Input impedance
–
Open circuit detection time
Positive full scale reading within 5 s
Overvoltage protection, max
Voltage: 30V DC Current: 8V DC
Normal mode noise rejection
> 80 dB @ 50/60 Hz
Common mode noise rejection
> 100 dB @ 50/60 Hz
Calibrated accuracy
Voltage: Better than 0.05% of range Current: Better than 0.15% of range
Calibration interval
12 months
Offset drift
90 V/°C
Gain drift with temperature
Voltage: 10 ppm/°C Current: 20 ppm/°C
Module error
Voltage: 0.1% of range Current: 0.3% of range
54
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
CAL OK HART
Page 55
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-IF8H (continued) Attribute
1756-IF8H
Module HART scan time
Analog: 18...488 ms (filter dependent). HART: typically 1 s per HART channel enabled. Estimate 10 s if all 8 channels have HART enabled. Typically 1 s per HART channel enabled. Estimate 10 s if all 8 channels have HART enabled. Pass through messages, handheld communicators, secondary masters, communication errors, or configuration changes can significantly increase the update time
Data format
Integer mode (left justified, 2 s complement) IEEE 32-bit floating point
Input conversion method
Successive approximation
Output conversion method
R-Ladder DAC, monotonicity with no missing codes
Isolation voltage
50V (continuous), Basic insulation type, input channels to backplane No isolation between individual input channels Type tested at 1500V AC for 60 s
Module keying
Electronic, software configurable
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire size
1756-TBCH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F, or greater, 1.2 mm (3/64 in.) insulation max 1756-TBS6H Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max
Terminal block torque specs
1756-TBCH 0.5 N•m (4.4 lb•in)
Wire category(1)
2 - on signal ports
Wire type
Copper
North American temp code
T5
ATEX temp code
T4
IECEx temp code
T4
Enclosure type rating
None (open-style)
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications - 1756-IF8H Attribute
1756-IF8H
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
55
Page 56
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-IF8H (continued) Attribute
1756-IF8H
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
IEC 61000-6-4
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±2 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on shielded ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-IF8H Certification(1)
1756-IF8H c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2014/30/EU EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
RCM
Australian Radiocommunications Act, compliant with: EN 61000-6-4: Industrial Emissions
Ex
European Union 2014/34/EU ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • DEMKO12ATEX1219040X
IECEx
IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • IECEx UL 16.0109X
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
EAC
Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
56
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 57
1756 ControlLogix I/O Specifications
1756-IF8I ControlLogix isolated voltage/current analog input module. 1756-IF8I Module Wiring Diagram -Current Mode with External Loop Power i IMPORTANT: Remember the following:
• In this wiring diagram, an external, userprovided power supply provides 24V DC loop power. • If separate power sources are used, do not exceed the specific isolation voltage as listed in the specifications. • Place additional loop devices, for example, strip chart recorders, at either ‘A’ location in the current loop.
IN_0/V
+
+
A
4-wire Transmitter
24V DC –
A
–
IN_0/I/SRC RTN_0 Not used IN_2/V
Shield Ground
IN_1/I/SRC
6
5
RTN_1
8
7
10
9
Not used IN_3/V IN_3/I/SRC
14 13
RTN_3
Not used
16 15
Not used
Not used
+
3
12 11
RTN_4
24V DC
4
RTN_2
IN_4/I/SRC
2-wire – Transmitter +
1
IN_2/I/SRC
IN_4/V i
IN_1/V
2
18 17 20 19 22 21 24 23
IN_5/V IN_5/I/SRC RTN_5 Not used
IN_6/V
IN_7/V
A
26 25
IN_6/I/SRC
28 27
IN_7/I/SRC
A
RTN_6
30 29
RTN_7
Not used
32 31
Not used
Not used
34 33
Not used
Not used
36 35
Not used
–
Shield Ground
1756-IF8I Module Wiring Diagram -Current Mode with Internal Loop Power
IMPORTANT: Remember the following:
• In this wiring diagram, the module provides 24V DC loop power. • If separate power sources are used, do not exceed the specific isolation voltage as listed in the specifications. • Place additional loop devices, for example, strip chart recorders, at either ‘A’ location in the current loop.
2-wire Transmitter
+
IN_0/V
2
1
IN_1/V
A
IN_0/I/SRC
4
3
IN_1/I/SRC
-
A
RTN-0
6
5
RTN-1
Shield Ground i
Not used
8
7
Not used
IN_2/V
10
9
IN_3/V
IN_2/I/SRC
12 11
IN_3/I/SRC
RTN_2
14 13
RTN_3
Not used
16 15
Not used
IN_4/V
18 17
IN_5/V
IN_4/I/SRC
20 19
IN_5/I/SRC
RTN-4
22 21
RTN-5
Not used
24 23
Not used
IN_6/V
26 25
IN_7/V
IN_6/I/SRC
28 27
IN_7/I/SRC
RTN_6
30 29
RTN_7
Not used
32 31
Not used
Not used
34 33
Not used
Not used
36 35
Not used
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
57
Page 58
1756 ControlLogix I/O Specifications
1756-IF8I Module Wiring Diagram - Voltage Mode
IMPORTANT: If separate power sources are used, do not exceed the specific isolation voltage as listed in the specifications.
Device External Power
+
+ –
User Analog Input Device
–
Shield Ground
ANALOG INPUT
ST FLT
O K
IN_0/V
2
1
IN_1/V
IN_0/I/SRC
4
3
IN_1/I/SRC
RTN-0
6
5
RTN-1
Not used
8
7
Not used
IN_2/V
10
9
IN_3/V
IN_2/I/SRC
12 11
IN_3/I/SRC
RTN_2
14 13
RTN_3
Not used
16 15
Not used
IN_4/V
18 17
IN_5/V
IN_4/I/SRC
20 19
IN_5/I/SRC
RTN-4
22 21
RTN-5
Not used
24 23
Not used
IN_6/V
26 25
IN_7/V
IN_6/I/SRC
28 27
IN_7/I/SRC
RTN_6
30 29
RTN_7
Not used
32 31
Not used
Not used
34 33
Not used
Not used
36 35
Not used
Technical Specifications - 1756-IF8I Attribute
1756-IF8I
Inputs
Eight isolated channels - Any combination of Voltage or Current mode
Input ranges
-10…10V 0…10V 0…5V 0…20 mA
Resolution
24-bit ±10.5V (1.49 μV/count) 0…10.5V (1.49 μV/count) 0…5.25V (1.49 μV/count) 0…21 mA (2.99 nA/count)
Current draw @ 5.1V
200 mA
Current draw @ 24V
Voltage/Non-sourcing Current mode: 150 mA Sourcing Current mode: 400 mA (In Sourcing Current mode, the channel provides loop power.)
Total backplane power
Voltage/Non-sourcing Current mode: 4.6 W Sourcing Current mode: 10.6 W
Power dissipation, max
Voltage mode: 4.6 W Non-sourcing Current mode: 5.1 W Sourcing Current mode: 7.3 W
Thermal dissipation
Voltage mode: 15.7 BTU/hr Non-sourcing Current mode: 17.4 BTU/hr Sourcing Current mode: 24.9 BTU/hr
58
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
Page 59
1756 ControlLogix I/O Specifications
Technical Specifications - 1756-IF8I (continued) Attribute
1756-IF8I
Input impedance, approx
Voltage mode: 1 G (powered); 7500 (unpowered) Current mode: 125
Sourcing voltage, min
20V DC
Sourcing voltage, max
38V DC (open circuit)
Sourcing current, max
Current Limited < 45 mA (IN_x/I/SRC to RTN_x)
Open circuit detection time
5s
Overvoltage protection, max
±30V DC
Normal mode noise rejection
80 dB @ 60 Hz(1)
Common mode noise rejection
120 dB @ 50/60 Hz
Channel bandwidth
Notch Filter configuration dependent See publication 1756-UM540 for possible values.
Settling time
Notch Filter configuration dependent See publication 1756-UM540 for possible values.
Calibrated accuracy 25 °C (77 °F)
0.05%
Module error over full temperature range
0.1%
Module input scan time, min
1 ms
Onboard data alarming
Yes
Scaling to engineering units
Yes
Real-time channel sampling
Yes - Rate set by Requested Packet Interval rate
Data format
IEEE 32-bit floating point
Module conversion method
Sigma-Delta
Isolation voltage
250V (continuous), reinforced insulation type, inputs to backplane 250V (continuous), basic insulation type, input to input Type tested at 2300V AC for 60 s, inputs to backplane Type tested at 1500V AC for 60 s, input to input
Module keying
Electronic, software configurable
Removable terminal block
1756-TBCH 1756-TBS6H
RTB keying
User-defined mechanical
Slot width
1
Wire size
0.33…2.1 mm2 (22...14 AWG) solid or stranded shielded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max
Wire category
2 on signal ports(2)
North American temperature code
T4
IEC temperature code
T4
Enclosure type
None (open-style)
(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016
59
Page 60
1756 ControlLogix I/O Specifications
Environmental Specifications - 1756-IF8I Attribute
1756-IF8I
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11, Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on shielded signal ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on shielded signal ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications - 1756-IF8I Certification(1)
1756-IF8I c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: • EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: • EN 61000-6-4; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 Gc X
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
60
Rockwell Automation Publication 1756-TD002J-EN-P - November 2016