Page 51

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IF8 Attribute

1756-IF8

Inputs

8 single-ended 4 differential 2 high-speed differential

Input range

±10V 0…10V 0…5V 0…20 mA

Resolution

±10.25V: 320 V/count (15 bits plus sign bipolar) 0…10.25V: 160 V/count (16 bits) 0…5.125V: 80 /V count (16 bits) 0…20.5mA: 0.32 A/count (16 bits)

Current draw @ 5.1V

150 mA

Current draw @ 24V

40 mA

Total backplane power

1.73 W

Voltage and current ratings

Backplane: 5.1V DC, 150 mA max, 24V DC, 40mA max Input voltage range: -10…+10V Input current range: 4…20mA Limited to 100VA

Power consumption

1.73 W

Power dissipation

Voltage: 1.73 W Current 2.33 W

Thermal dissipation

Voltage: 5.88 BTU/hr Current: 7.92 BTU/hr

Input impedance

Voltage: >1 M Current: 249

Open circuit detection time

Differential voltage: Positive full scale reading within 5 s Single-ended/diff. current: Negative full scale reading within 5 s Single-ended voltage: Even-numbered channels go to positive full scale reading within 5 s, odd-numbered channels go to negative full scale reading within 5 s

Overvoltage protection, max

Voltage: 30V DC Current: 8V DC

Normal mode noise rejection

>80 dB @ 50/60 Hz(2)

Common mode noise rejection

>100 dB @ 50/60 Hz

Calibrated accuracy 25 °C (77 °F)

Voltage: Better than 0.05% of range Current: Better than 0.15% of range

Calibration interval

12 months

Offset drift

45 V/°C

Gain drift with temperature

Voltage: 15 ppm/°C Current: 20 ppm/°C

Module error

Voltage: 0.1% of range Current: 0.3% of range

Module input scan time, min

8 pt single-ended (floating point): 16…488 ms 4 pt differential (floating point): 8…244 ms 2 pt differential (floating point): 5…122 m(1)

Onboard data alarming

Yes

Scaling to engineering units

Yes

Real-time channel sampling

Yes

Data format

Integer mode (left justified, 2 s complement) IEEE 32-bit floating point

Module conversion method

Sigma-Delta

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

51

Page 52

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IF8 (continued) Attribute

1756-IF8

Isolation voltage

250V (continuous), Reinforced insulation type, Inputs to Backplane. No isolation between individual Inputs. Routine tested at 1350V AC for 2 s

Module keying

Electronic, software configurable

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire size

1756-TBCH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max 1756-TBS6H Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at |105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max

Terminal block torque specs

1756-TBCH: 0.5 N•m (4.4 lb•in)

Wiring category(1)

2 - on signal ports

North American temp code

T4A

ATEX temp code

T4

IECEx temp code

T4

Enclosure type

None (open-style)

(1) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. (2) Notch filter dependent.

Environmental Specifications - 1756-IF8 Attribute

1756-IF8

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

IEC 61000-6-4

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

52

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 53

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IF8 (continued) Attribute

1756-IF8

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±2 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on shielded ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-IF8 Certification(1)

1756-IF8

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

CE

European Union 2014/30/EU EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2014/35/EU LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

RCM

Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions

Ex

European Union 2014/34/EU ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • DEMKO15ATEX1482X

IECEx

IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • IECEx UL 15.0053X

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

EAC

Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation

(1)

See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

53

Page 54

1756 ControlLogix I/O Specifications

1756-IF8H ControlLogix voltage/current analog input module with HART protocol 1756-IF8H Current

1756-IF8H Voltage

ANALOG INPUT

Voltage Input 2-wire Current Inputs

+V

2-Wire XMTR 24V DC Power Supply

+ -

+-

4-wire Current Inputs 24V DC Power Supply

+ +4-Wire+ - XMTR - -

IN0+

2

1

I RTN-0

IN0-

4

3

NC

IN1+

6

5

I RTN-1

IN1-

8

7

NC

RTN

10 9

RTN

IN2+

12 11

I RTN-2

IN2-

14 13

NC

IN3+

16 15

I RTN-3

IN3-

18 17

NC

IN4+

20 19

I RTN-4

IN4-

22 21

NC

NC

IN5+

24 23

I RTN-5

24 23

I RTN-5

IN5-

26 25

NC

IN5-

26 25

NC

RTN

28 27

RTN

RTN

28 27

RTN

IN6+

30 29

I RTN-6

IN6+

30 29

I RTN-6

IN6-

32 31

NC

IN6-

32 31

NC

IN7+

34 33

I RTN-7

IN7+

34 33

I RTN-7

IN7-

36 35

NC

IN7-

36 35

NC

-V IN0+

2

1

I RTN-0

IN0-

4

3

NC

IN1+

6

5

I RTN-1

IN1-

8

7

NC

RTN

10 9

RTN

IN2+

12 11

I RTN-2

IN2-

14 13

NC

IN3+

16 15

I RTN-3

IN3-

18 17

NC

IN4+

20 19

I RTN-4

IN4-

22 21

IN5+

Technical Specifications - 1756-IF8H Attribute

1756-IF8H

Inputs

Eight differential voltage or current inputs, one HART modem per module

Input range

±10V 0…5V 1…5V 0…10V 0…20 mA 4…20 mA

Resolution

16…21 bits

Voltage and current ratings

Backplane: 5.1V DC, 300mA, 24V DC, 135mA Input voltage range: -10…+10V Input current range: 0…20 mA, 4…20mA

Total backplane power

4.77 W

Power dissipation

Voltage: 3.21 W Current: 4.01 W

Thermal dissipation

Voltage: 11.0 BTU/hr Current: 13.7 BTU/hr

Input impedance

–

Open circuit detection time

Positive full scale reading within 5 s

Overvoltage protection, max

Voltage: 30V DC Current: 8V DC

Normal mode noise rejection

> 80 dB @ 50/60 Hz

Common mode noise rejection

> 100 dB @ 50/60 Hz

Calibrated accuracy

Voltage: Better than 0.05% of range Current: Better than 0.15% of range

Calibration interval

12 months

Offset drift

90 V/°C

Gain drift with temperature

Voltage: 10 ppm/°C Current: 20 ppm/°C

Module error

Voltage: 0.1% of range Current: 0.3% of range

54

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

CAL OK HART

Page 55

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IF8H (continued) Attribute

1756-IF8H

Module HART scan time

Analog: 18...488 ms (filter dependent). HART: typically 1 s per HART channel enabled. Estimate 10 s if all 8 channels have HART enabled. Typically 1 s per HART channel enabled. Estimate 10 s if all 8 channels have HART enabled. Pass through messages, handheld communicators, secondary masters, communication errors, or configuration changes can significantly increase the update time

Data format

Integer mode (left justified, 2 s complement) IEEE 32-bit floating point

Input conversion method

Successive approximation

Output conversion method

R-Ladder DAC, monotonicity with no missing codes

Isolation voltage

50V (continuous), Basic insulation type, input channels to backplane No isolation between individual input channels Type tested at 1500V AC for 60 s

Module keying

Electronic, software configurable

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire size

1756-TBCH Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F, or greater, 1.2 mm (3/64 in.) insulation max 1756-TBS6H Single wire connection: 0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max

Terminal block torque specs

1756-TBCH 0.5 N•m (4.4 lb•in)

Wire category(1)

2 - on signal ports

Wire type

Copper

North American temp code

T5

ATEX temp code

T4

IECEx temp code

T4

Enclosure type rating

None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-IF8H Attribute

1756-IF8H

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

55

Page 56

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IF8H (continued) Attribute

1756-IF8H

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

IEC 61000-6-4

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±2 kV at 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on shielded ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-IF8H Certification(1)

1756-IF8H c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2014/30/EU EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

RCM

Australian Radiocommunications Act, compliant with: EN 61000-6-4: Industrial Emissions

Ex

European Union 2014/34/EU ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • DEMKO12ATEX1219040X

IECEx

IECEx System, compliant with: • IEC 60079-0; General Requirements • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA IIC T4 Gc • IECEx UL 16.0109X

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

EAC

Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation

(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

56

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 57

1756 ControlLogix I/O Specifications

1756-IF8I ControlLogix isolated voltage/current analog input module. 1756-IF8I Module Wiring Diagram -Current Mode with External Loop Power i IMPORTANT: Remember the following:

• In this wiring diagram, an external, userprovided power supply provides 24V DC loop power. • If separate power sources are used, do not exceed the specific isolation voltage as listed in the specifications. • Place additional loop devices, for example, strip chart recorders, at either ‘A’ location in the current loop.

IN_0/V

+

+

A

4-wire Transmitter

24V DC –

A

–

IN_0/I/SRC RTN_0 Not used IN_2/V

Shield Ground

IN_1/I/SRC

6

5

RTN_1

8

7

10

9

Not used IN_3/V IN_3/I/SRC

14 13

RTN_3

Not used

16 15

Not used

Not used

+

3

12 11

RTN_4

24V DC

4

RTN_2

IN_4/I/SRC

2-wire – Transmitter +

1

IN_2/I/SRC

IN_4/V i

IN_1/V

2

18 17 20 19 22 21 24 23

IN_5/V IN_5/I/SRC RTN_5 Not used

IN_6/V

IN_7/V

A

26 25

IN_6/I/SRC

28 27

IN_7/I/SRC

A

RTN_6

30 29

RTN_7

Not used

32 31

Not used

Not used

34 33

Not used

Not used

36 35

Not used

–

Shield Ground

1756-IF8I Module Wiring Diagram -Current Mode with Internal Loop Power

IMPORTANT: Remember the following:

• In this wiring diagram, the module provides 24V DC loop power. • If separate power sources are used, do not exceed the specific isolation voltage as listed in the specifications. • Place additional loop devices, for example, strip chart recorders, at either ‘A’ location in the current loop.

2-wire Transmitter

+

IN_0/V

2

1

IN_1/V

A

IN_0/I/SRC

4

3

IN_1/I/SRC

-

A

RTN-0

6

5

RTN-1

Shield Ground i

Not used

8

7

Not used

IN_2/V

10

9

IN_3/V

IN_2/I/SRC

12 11

IN_3/I/SRC

RTN_2

14 13

RTN_3

Not used

16 15

Not used

IN_4/V

18 17

IN_5/V

IN_4/I/SRC

20 19

IN_5/I/SRC

RTN-4

22 21

RTN-5

Not used

24 23

Not used

IN_6/V

26 25

IN_7/V

IN_6/I/SRC

28 27

IN_7/I/SRC

RTN_6

30 29

RTN_7

Not used

32 31

Not used

Not used

34 33

Not used

Not used

36 35

Not used

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

57

Page 58

1756 ControlLogix I/O Specifications

1756-IF8I Module Wiring Diagram - Voltage Mode

IMPORTANT: If separate power sources are used, do not exceed the specific isolation voltage as listed in the specifications.

Device External Power

+

+ –

User Analog Input Device

–

Shield Ground

ANALOG INPUT

ST FLT

O K

IN_0/V

2

1

IN_1/V

IN_0/I/SRC

4

3

IN_1/I/SRC

RTN-0

6

5

RTN-1

Not used

8

7

Not used

IN_2/V

10

9

IN_3/V

IN_2/I/SRC

12 11

IN_3/I/SRC

RTN_2

14 13

RTN_3

Not used

16 15

Not used

IN_4/V

18 17

IN_5/V

IN_4/I/SRC

20 19

IN_5/I/SRC

RTN-4

22 21

RTN-5

Not used

24 23

Not used

IN_6/V

26 25

IN_7/V

IN_6/I/SRC

28 27

IN_7/I/SRC

RTN_6

30 29

RTN_7

Not used

32 31

Not used

Not used

34 33

Not used

Not used

36 35

Not used

Technical Specifications - 1756-IF8I Attribute

1756-IF8I

Inputs

Eight isolated channels - Any combination of Voltage or Current mode

Input ranges

-10…10V 0…10V 0…5V 0…20 mA

Resolution

24-bit ±10.5V (1.49 μV/count) 0…10.5V (1.49 μV/count) 0…5.25V (1.49 μV/count) 0…21 mA (2.99 nA/count)

Current draw @ 5.1V

200 mA

Current draw @ 24V

Voltage/Non-sourcing Current mode: 150 mA Sourcing Current mode: 400 mA (In Sourcing Current mode, the channel provides loop power.)

Total backplane power

Voltage/Non-sourcing Current mode: 4.6 W Sourcing Current mode: 10.6 W

Power dissipation, max

Voltage mode: 4.6 W Non-sourcing Current mode: 5.1 W Sourcing Current mode: 7.3 W

Thermal dissipation

Voltage mode: 15.7 BTU/hr Non-sourcing Current mode: 17.4 BTU/hr Sourcing Current mode: 24.9 BTU/hr

58

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

Page 59

1756 ControlLogix I/O Specifications

Technical Specifications - 1756-IF8I (continued) Attribute

1756-IF8I

Input impedance, approx

Voltage mode: 1 G (powered); 7500 (unpowered) Current mode: 125

Sourcing voltage, min

20V DC

Sourcing voltage, max

38V DC (open circuit)

Sourcing current, max

Current Limited < 45 mA (IN_x/I/SRC to RTN_x)

Open circuit detection time

5s

Overvoltage protection, max

±30V DC

Normal mode noise rejection

80 dB @ 60 Hz(1)

Common mode noise rejection

120 dB @ 50/60 Hz

Channel bandwidth

Notch Filter configuration dependent See publication 1756-UM540 for possible values.

Settling time

Notch Filter configuration dependent See publication 1756-UM540 for possible values.

Calibrated accuracy 25 °C (77 °F)

0.05%

Module error over full temperature range

0.1%

Module input scan time, min

1 ms

Onboard data alarming

Yes

Scaling to engineering units

Yes

Real-time channel sampling

Yes - Rate set by Requested Packet Interval rate

Data format

IEEE 32-bit floating point

Module conversion method

Sigma-Delta

Isolation voltage

250V (continuous), reinforced insulation type, inputs to backplane 250V (continuous), basic insulation type, input to input Type tested at 2300V AC for 60 s, inputs to backplane Type tested at 1500V AC for 60 s, input to input

Module keying

Electronic, software configurable

Removable terminal block

1756-TBCH 1756-TBS6H

RTB keying

User-defined mechanical

Slot width

1

Wire size

0.33…2.1 mm2 (22...14 AWG) solid or stranded shielded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max

Wire category

2 on signal ports(2)

North American temperature code

T4

IEC temperature code

T4

Enclosure type

None (open-style)

(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002J-EN-P - November 2016

59

Page 60

1756 ControlLogix I/O Specifications

Environmental Specifications - 1756-IF8I Attribute

1756-IF8I

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on shielded signal ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on shielded signal ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications - 1756-IF8I Certification(1)

1756-IF8I c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/IEC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: • EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: • EN 61000-6-4; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements II 3 G Ex nA IIC T4 Gc X

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

60