Page 107

Chapter

8

Troubleshooting the Sequence of Events Module

What This Chapter Contains

This chapter describes how to troubleshoot the Sequence of Events module. Table 8.1 For information on:

Using LED Status Indicators

See page:

Using LED Status Indicators

8-1

Using RSLogix 5000 To Troubleshoot the Module

8-2

Your Sequence of Events module has yellow indicators that show individual I/O state and a bi-colored (red/green) indicator that shows module status with an “OK”. Status indicators are located on the front of the module. The LED status indicators used on the Sequence of Events module are shown in Figure 8.1. Figure 8.1

20945

During power up, an indicator test is done and the following occurs: • "OK" indicator turns red for 1 second and then turns to flashing green if it has passed the self-test. • I/O status indicators turn ON for a maximum of 2 seconds and then turn OFF.

1

Publication 1756-UM528A-EN-P - April 2004

Page 108

8-2

Troubleshooting the Sequence of Events Module

Table 8.2 describes how to use the Sequence of Events module’s LED status indicators. Table 8.2 This indicator:

With this display:

Means:

Take this action:

OK

Steady green light

The inputs are being multicast and in normal operating state.

None

Flashing green light

The module has passed internal diagnostics but is not multicasting inputs.

Configure the module with RSLogix 5000.

Flashing red light

One of the following:

I/O State

• Previously established communication has timed out

• Check controller and chassis communication.

• A FLASH update is in progress.

• Finish the update

Steady red light

An unrecoverable error has occurred on the module.

Replace the module.

Yellow

The input is active.

None

Using RSLogix 5000 To Troubleshoot the Module

In addition to the LED status indicators on the module, RSLogix 5000 alerts you to fault and other conditions in one of three ways: • Warning signal on the main screen next to the module – This occurs when the connection to the module is broken.

Warning icon appears when a communications fault occurs or if the module is inhibited

Warning signal - The module in slot 1 has a communications fault

Publication 1756-UM528A-EN-P - April 2004

Page 109

Troubleshooting the Sequence of Events Module

8-3

• Message in a screen’s status line

Status line provides information on the module’s fault and on the connection to the module

• Notification in the Tag Editor - General module faults are also reported in the Tag Editor. Diagnostic faults are only reported in the Tag Editor

RSLogix 5000 generates 1s in response to a module communication fault. In this example, a communication fault occurred between the controller and the Sequence of Events module, so the controller automatically writes 1s for all bits in the word.

Publication 1756-UM528A-EN-P - April 2004

Page 110

8-4

Troubleshooting the Sequence of Events Module

Determining Fault Type When you are monitoring a module’s configuration properties in RSLogix 5000 and receive a Communications fault message, the Connection page lists the type of fault.

The fault type is listed here

For a detailed listing of the possible faults, their causes and suggested solutions, see Module Faults in the online help.

Chapter Summary and What’s Next

Publication 1756-UM528A-EN-P - April 2004

In this chapter you learned about troubleshooting the module. Appendix A lists the Sequence of Events module’s Specifications and Module Block Diagrams.