1756-IB16ISOE Specifications
Number of Inputs
16 (Individually isolated)
Module Location
1756 ControlLogix Chassis
Backplane Current
295mA @ 5.1V dc & 2mA @ 24V dc
Backplane Power
1.5W
Maximum Power Dissipation (Module)
5.5W @ 60oC
Thermal Dissipation
17.22 BTU/hr.
On-State Voltage Range
10-55V dc
Nominal Input Voltage
24V dc/48V dc
On-State Current Minimum Nominal Maximum
2.0mA @ 9V dc 4.5mA @ 24-31V dc 5.1mA @ 48-55V dc
Maximum Off-State Current
1.5mA
Maximum Off-State Voltage
5V dc
Maximum Input Impedance
10.8kΩ @ 55V dc
Input Delay Time OFF to ON
ON to OFF
1
Hardware Delay (10µs nominal/20µs maximum) + Firmware Scan (up to 25µs) + Input Filter Time (User selectable time: 0ms to 50ms) + ASIC delay (175µs - FIFO/625µs - CST Per Point) Hardware Delay (25µs nominal/50µs maximum) + Firmware Scan (25µs) + Input Filter Time (User selectable time: 0ms to 50ms) + ASIC delay (175µs - FIFO/625µs - CST Per Point)
Timestamp accuracy
100µs
Cyclic Update Time (RPI)
User selectable (250µs minimum/750ms maximum)
Reverse Polarity Protection
Yes
Isolation Voltage Inputs to backplane Input to input
250V continuous 125V continuous
RTB Screw Torque (Cage clamp)
4.4 inch-pounds (0.4Nm) maximum
Module Keying (Backplane)
Software configurable
RTB Keying
User defined mechanical keying
RTB and Housing
36-Position RTB (1756-TBCH or TBS6H)(1)
Publication 1756-UM528A-EN-P - April 2004
Page 112
A-2
Specifications and Module Block Diagrams
Conductors Wire Size Category Screwdriver Blade Width for RTB
#22 to #14 AWG (0.324 to 2.08 sq. mm) stranded(1) 3/64 inch (1.2mm) insulation maximum 1(2) 1/8 inch (3.2mm) maximum
Environmental Conditions
Publication 1756-UM528A-EN-P - April 2004
Operational Temperature
IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0 to 60°C (32 to 140°F)
Storage Temperature
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold), IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock): -40 to 85°C (-40 to 185°F)
Relative Humidity
IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat): 5 to 95% non-condensing
Vibration
IEC 60068-2-6 (Test Fc, Operating): 2g @ 10-500Hz
Operating Shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30g
Non-operating Shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50g
Emissions
CISPR 11: Group 1, Class A
ESD Immunity
IEC 61000-4-2: 6kV contact discharges 8kV air discharges
Radiated RF Immunity
IEC 61000-4-3: 10V/m with 1kHz sine-wave 80%AM from 80MHz to 1000MHz 10V/m with 200Hz 50% Pulse 100%AM at 900Mhz 10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz
Page 113
Specifications and Module Block Diagrams
A-3
EFT/B Immunity
IEC 61000-4-4: ±4kV at 2.5kHz on signal ports
Surge Transient Immunity
IEC 61000-4-5: ±1kV line-line (DM) and ±2kV line-earth (CM) on signal ports
Conducted RF Immunity
IEC 61000-4-6: 10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
Oscillatory Surge Withstand
IEEE C37.90.1: 3kV
Enclosure Type Rating
None (open-style)
Agency Certification (when product is marked)
UL CSA CSA
UL Listed Industrial Control Equipment CSA Certified Process Control Equipment CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations CE(3) European Union 89/336/EEC EMC Directive, compliant with: EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions C-Tick(3) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions EEx(3) European Union 94/9/EC ATEX Directive, compliant with: EN 50021; Potentially Explosive Atmospheres, Protection "n" (Zone 2)
(1)
Maximum wire size will require extended housing - 1756-TBE.
(2)
Use this Conductor Category information for planning conductor routing. Refer to Publication 1770-4.1, “Industrial Automation Wiring and Grounding Guidelines”.
(3)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Publication 1756-UM528A-EN-P - April 2004
Page 114
A-4
Specifications and Module Block Diagrams
1756-IB16ISOE Module Block Diagram
Figure A.1 shows the Sequence of Events module block diagram. Figure A.1 Isolation Barrier
B a c k p l a n e C o n n e c t o r
5V power
Serial EEPROM
Backplane ASIC
BF532 Blackfin DSP
Dualport RAM
OK LED
125V dc or 24/48V dc input circuit
SRAM
FLASH
F r o n t E n d
OPTO Isolation
16 channel LEDs
125V dc or 24/48V dc input circuit
24V power
(The 125V dc or 24/48Vdc input circuits are shown in greater detail below.)
1.2V power
43687
24/48Vdc input circuit Electronic current limit circuit
5V
IN-0
GND-0 43836
ControlLogix Display backplane Interface
Publication 1756-UM528A-EN-P - April 2004
C o n n e c t o r
Page 115
Specifications and Module Block Diagrams
1756-IH16ISOE Specifications
Number of Inputs
16 (Individually isolated)
Module Location
1756 ControlLogix Chassis
Backplane Current
275mA @ 5.1V dc & 2mA @ 24V dc
Backplane Power
1.3W
Maximum Power Dissipation (Module)
5.5W @ 60oC
Thermal Dissipation
17.22 BTU/hr.
On-State Voltage Range
90-140V dc
Nominal Input Voltage
125V dc
On-State Current
1.15mA @ 90V dc minimum 1.85mA @ 140V dc maximum
Maximum Off-State Current
0.3mA
Maximum Off-State Voltage
20V dc
Maximum Input Impedance
74.8kΩ
Input Delay Time OFF to ON
ON to OFF
A-5
Hardware Delay (10µs nominal/20µs maximum) + Firmware Scan (25µs) + Input Filter Time (User selectable time: 0ms to 50ms) + ASIC delay (175µs - FIFO/625µs - CST Per Point) Hardware Delay (50µs nominal/75µs maximum) + Firmware Scan ((25µs) + Input Filter Time (User selectable time: 0ms to 50ms) + ASIC delay (175µs - FIFO/625µs - CST Per Point)
Timestamp accuracy
100µs
Cyclic Update Time (RPI)
User selectable (250µs minimum/750ms maximum)
Reverse Polarity Protection
Yes
Isolation Voltage Inputs to backplane and Input to input
250V continuous
RTB Screw Torque (Cage clamp)
4.4 inch-pounds (0.4Nm) maximum
Module Keying (Backplane)
Software configurable
RTB Keying
User defined mechanical keying
RTB and Housing
36-Position RTB (1756-TBCH or TBS6H)(1)
Publication 1756-UM528A-EN-P - April 2004
Page 116
A-6
Specifications and Module Block Diagrams
Conductors Wire Size Category Screwdriver Blade Width for RTB
#22 to #14 AWG (0.324 to 2.08 sq. mm) stranded(1) 3/64 inch (1.2mm) insulation maximum 1(2) 1/8 inch (3.2mm) maximum
Environmental Conditions
Publication 1756-UM528A-EN-P - April 2004
Operational Temperature
IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0 to 60°C (32 to 140°F)
Storage Temperature
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold), IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock): -40 to 85°C (-40 to 185°F)
Relative Humidity
IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat): 5 to 95% non-condensing
Vibration
IEC 60068-2-6 (Test Fc, Operating): 2g @ 10-500Hz
Operating Shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30g
Non-operating Shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50g
Emissions
CISPR 11: Group 1, Class A
ESD Immunity
IEC 61000-4-2: 6kV contact discharges 8kV air discharges
Radiated RF Immunity
IEC 61000-4-3: 10V/m with 1kHz sine-wave 80%AM from 80MHz to 1000MHz 10V/m with 200Hz 50% Pulse 100%AM at 900Mhz 10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz
Page 117
Specifications and Module Block Diagrams
A-7
EFT/B Immunity
IEC 61000-4-4: ±4kV at 2.5kHz on signal ports
Surge Transient Immunity
IEC 61000-4-5: ±1kV line-line (DM) and ±2kV line-earth (CM) on signal ports
Conducted RF Immunity
IEC 61000-4-6: 10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
Oscillatory Surge Withstand
IEEE C37.90.1: 3kV
Enclosure Type Rating
None (open-style)
Agency Certification (when product is marked)
UL CSA CSA
UL Listed Industrial Control Equipment CSA Certified Process Control Equipment CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations (3) CE European Union 89/336/EEC EMC Directive, compliant with: EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions European Union 73/23/EEC LVD Directive, compliant with: EN 61131-2; Programmable Controllers (3) C-Tick Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
(1)
Maximum wire size will require extended housing - 1756-TBE.
(2)
Use this Conductor Category information for planning conductor routing. Refer to Publication 1770-4.1, “Industrial Automation Wiring and Grounding Guidelines”.
(3)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Publication 1756-UM528A-EN-P - April 2004
Page 118
A-8
Specifications and Module Block Diagrams
1756-IH16ISOE Module Block Diagram
Figure A.2 shows the Sequence of Events module block diagram. Figure A.2 Isolation Barrier
B a c k p l a n e C o n n e c t o r
5V power
Serial EEPROM
Backplane ASIC
Dualport RAM
OK LED
125V dc or 24/48V dc input circuit
SRAM
FLASH
BF532 Blackfin DSP
E n d
OPTO Isolation
16 channel LEDs
125V dc or 24/48V dc input circuit
24V power
(The 125V dc or 24/48Vdc input circuits are shown in greater detail below.)
1.2V power
F r o n t
C o n n e c t o r
43687
125Vdc input circuit 5V IN-0
GND-0 43835
ControlLogix Display backplane Interface
Publication 1756-UM528A-EN-P - April 2004