Page 27

Chapter

3

Installing the Sequence of Events Module

What This Chapter Contains

This chapter describes how to install the Sequence of Events module. Table 3.1 For information on:

Installing the Sequence of Events Module

Installing the Sequence of Events Module

3-1

Keying the Removable Terminal Block

3-3

Connecting Wiring

3-4

Assembling The Removable Terminal Block and the Housing

3-7

Choosing the Extended-Depth Housing

3-8

Installing the Removable Terminal Block

3-10

Removing the Removable Terminal Block

3-12

Removing the Module from the Chassis

3-13

You can install or remove the module while chassis power is applied. ATTENTION

1

See page:

The module is designed to support Removal and Insertion Under Power (RIUP). However, when you remove or insert an RTB with field-side power applied, unintended machine motion or loss of process control can occur. Exercise extreme caution when using this feature.

Publication 1756-UM528A-EN-P - April 2004

Page 28

3-2

Installing the Sequence of Events Module

1. Align circuit board with top and bottom chassis guides. Figure 3.1

Printed Circuit Board

20861-M

2. Slide module into chassis until module tabs ‘click’. Figure 3.2 Locking Tab

20862-M

Publication 1756-UM528A-EN-P - April 2004

Page 29

Installing the Sequence of Events Module

Keying the Removable Terminal Block

3-3

Key the RTB to prevent inadvertently connecting the incorrect RTB to your module. When the RTB mounts onto the module, keying positions match up. For example, if you place a U-shaped keying band in position #4 on the module, you cannot place a wedge-shaped tab in #4 on the RTB or your RTB does not mount on the module. We recommend that you use a unique keying pattern for each slot in the chassis. 1. Insert the U-shaped band with the longer side near the terminals. Push the band onto the module until it snaps in place. Figure 3.3 .

U-shaped Keying Band

20850-M

2. Key the RTB in positions that correspond to unkeyed module positions. Insert the wedge-shaped tab on the RTB with the rounded edge first. Push the tab onto the RTB until it stops. IMPORTANT

When keying your RTB and module, you must begin with a wedge-shaped tab in position #6 or #7.

Figure 3.4 Wedge–shaped Keying Tab

Module side of RTB

0

12

3

45 6

20851–M

7 Publication 1756-UM528A-EN-P - April 2004

Page 30

3-4

Installing the Sequence of Events Module

Connecting Wiring

You can use an RTB or a Bulletin 1492 prewired Interface Module (IFM) to connect wiring to your module. You must connect wires to the RTB. An IFM has been prewired before you received it. If you are using an IFM to connect wiring to the module, skip this section and go to page 3-7.

Wiring the RTB You can use either of the following RTBs with your Sequence of Events module. • Cage Clamp RTB - Catalog number 1756-TBCH • Spring Clamp RTB - Catalog number 1756-TBS6H Wire the RTB with a 1/8 inch (3.2mm) maximum flat-bladed screwdriver before installing it onto the module.

WARNING

When you connect or disconnect the Removable Terminal Block (RTB) while field side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.

Be sure that power is removed or that the area is nonhazardous before proceeding.

Cage Clamp RTB 1. Strip 3/8 inch (9.5mm) maximum length of wire. 2. Insert the wire into the open terminal. 3. Turn the screw clockwise to close the terminal on the wire. Figure 3.5

Strain relief area

Publication 1756-UM528A-EN-P - April 2004

20859-M

Page 31

Installing the Sequence of Events Module

3-5

Spring Clamp RTB 1. Strip 7/16 inch (11mm) maximum length of wire. 2. Insert the screwdriver into the inner hole of the RTB. 3. Insert the wire into the open terminal and remove the screwdriver. Figure 3.6

Strain relief area

20860-M

Recommendations for Wiring Your RTB Consider the following guidelines when wiring your RTB: • Begin wiring the RTB at the bottom terminals and move up. • Use a tie to secure the wires in the strain relief area of the RTB. • The jumper bar part number is 97739201. Contact your local Rockwell Automation sales representative to order additional jumper bars, if necessary. • Order and use an extended-depth housing (Catalog number 1756-TBE) for applications that require heavy gauge wiring. For more information, see page 3-8.

Publication 1756-UM528A-EN-P - April 2004

Page 32

3-6

Installing the Sequence of Events Module

Wiring the Sequence of Events Module

Use Figure 3.7 to wire your Sequence of Events module.

WARNING

If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

Figure 3.7 Sink input wiring

Isolated wiring DC-0 (-)

GND-0

2

1

IN-0

DC-0 (+)

DC-1 (-)

GND-1

4

3

IN-1

DC-1 (+)

GND-2

6

5

IN-2

GND-3

8

7

IN-3

GND-4

10 9

IN-4

DC-5 (-)

GND-5

12 11

IN-5

DC-5 (+)

DC-6 (-)

GND-6

14 13

IN-6

DC-6 (+)

GND-7

16 15

IN-7

GND-8

18 17

IN-8

GND-9

20 19

IN-9

GND-10

22 21

IN-10

GND-11

24 23

IN-11

GND-12

26 25

IN-12

GND-13

28 27

IN-13

GND-14

30 29

IN-14

GND-15

32 31

IN-15

GND-15

34 33

Not used

Not used

36 35

Not used

Source input wiring

Non-isolated wiring

Jumper bar (Cut to length)

DC (-)

Daisy chain to other RTBs

Source input wiring

Sink input wiring

DC (+)

40167-M

NOTES: 1. All terminals with the same name are connected together on the module. For example, DC (-) can be connected to either terminal marked GND-15. 2. When you use the second GND-15 terminal to daisy chain to other RTBs, always connect the daisy chain to the terminal directly connected to the supply wire, as shown in the example above. 3. If separate power sources are used, do not exceed the specified isolation voltage. 4. Do not connect more than 2 wires to any single terminal. 5. The jumper bar part number is 97739201. Contact your local Rockwell Automation sales representative to order jumper bars, if necessary.

Publication 1756-UM528A-EN-P - April 2004

Page 33

Installing the Sequence of Events Module

Assembling The Removable Terminal Block and the Housing

3-7

Removable housing covers the wired RTB to protect wiring connections when the RTB is seated on the module. 1. Align the grooves at the bottom of each side of the housing with the side edges of the RTB. Figure 3.8 Housing

Groove Side edge of RTB Groove Strain relief area Side edge of RTB

RTB 20858-M

1756-TBCH RTB shown for reference

2. Slide the RTB into the housing until it snaps into place. IMPORTANT

If additional wire routing space is required for your application, use extended-depth housing 1756-TBE.

Publication 1756-UM528A-EN-P - April 2004

Page 34

3-8

Installing the Sequence of Events Module

Choosing the Extended-Depth Housing

There are two housing options you must consider when wiring your Sequence of Events module–standard-depth or extended-depth. When you order an RTB for your module, you receive a standard-depth housing with the RTB. If your application uses heavy gauge wiring, you can order an extended-depth housing. This housing does not come with an RTB. You can use one of the housings listed in Table 3.2. Table 3.2 Use this housing:

with this RTB:

This combination allows up to this capacity of wires:

1756-TBCH

Cage clamp

336 sq. mm

1756-TBS6H

Spring clamp (36-position)

1756-TBE

Any RTB that uses heavy gauge wiring

628 sq. mm

Figure 3.9 shows the difference, in terms of capacity, between the housing options. IMPORTANT

The housings shown are used with a spring clamp RTB, but the capacity for each remains the same regardless of RTB type.

Figure 3.9 Standard-Depth Housing

Extended-Depth Housing

Maximum Area = 336mm2 36 - 18AWG wires 23 - 14AWG wires

Maximum Area = 628mm2 40 - 14AWG wires

30484-M

Publication 1756-UM528A-EN-P - April 2004

Page 35

Installing the Sequence of Events Module

3-9

Recommendations for Using the Extended-Depth Housing Consider the following recommendations when deciding to use an extended-depth housing on your Sequence of Events module. It is recommended you use the 1756-TBE when: • using >36 18AWG wires • using >23 14AWG wires

Cabinet Size Considerations With the Extended-Depth Housing When you use an extended-depth housing (1756-TBE), the module depth is increased. The diagram below shows the difference, in terms of depth, between a Sequence of Events module using a standard-depth housing and one using an extended-depth housing. Figure 3.10 144.73mm (5.698in) 12.7mm (0.5in)

3.18mm (0.125in)

131.75mm (5.187in)

Rear Surface of ControlLogix Chassis Standard-Depth Housing

Extended-Depth Housing

41682

IMPORTANT

The depth from front of the module to the back of the chassis is as follows: – standard-depth housing = 147.91mm (5.823in) – extended-depth housing = 157.43mm (6.198in)

Publication 1756-UM528A-EN-P - April 2004

Page 36

3-10

Installing the Sequence of Events Module

Installing the Removable Terminal Block

Install the RTB onto the module to connect wiring.

ATTENTION

Shock hazard exists. If the RTB is installed onto the module while the field-side power is applied, the RTB will be electrically live. Do not touch the RTB’s terminals. Failure to observe this caution may cause personal injury. The RTB is designed to support Removal and Insertion Under Power (RIUP). However, when you remove or insert an RTB with field-side power applied, unintended machine motion or loss of process control can occur. Exercise extreme caution when using this feature. It is recommended that field-side power be removed before installing the RTB onto the module.

Before installing the RTB, make certain: • field-side wiring of the RTB has been completed. • the RTB housing is snapped into place on the RTB. • the RTB housing door is closed. • the locking tab at the top of the module is unlocked. 1. Align the top, bottom and left side guides of the RTB with the guides on the module.

Top guide

Left side guides Bottom guide 20853-M

Publication 1756-UM528A-EN-P - April 2004

Page 37

Installing the Sequence of Events Module

3-11

2. Press quickly and evenly to seat the RTB on the module until the latches snap into place.

Locking tab

20854-M

3. Slide the locking tab down to lock the RTB onto the module.

Publication 1756-UM528A-EN-P - April 2004

Page 38

3-12

Installing the Sequence of Events Module

Removing the Removable Terminal Block

If you need to remove the module from the chassis, you must first remove the RTB from the module.

ATTENTION

Shock hazard exists. If the RTB is removed from the module while the field-side power is applied, the module will be electrically live. Do not touch the RTB’s terminals. Failure to observe this caution may cause personal injury. The RTB is designed to support Removal and Insertion Under Power (RIUP). However, when you remove or insert an RTB with field-side power applied, unintended machine motion or loss of process control can occur. Exercise extreme caution when using this feature. It is recommended that field-side power be removed before removing the module.

1. Unlock the locking tab at the top of the module. 2. Open the RTB door using the bottom tab. 3. Hold the spot marked PULL HERE and pull the RTB off the module. IMPORTANT

Do not wrap your fingers around the entire door. A shock hazard exists.

20855-M

Publication 1756-UM528A-EN-P - April 2004

Page 39

Installing the Sequence of Events Module

Removing the Module from the Chassis

3-13

1. Push in the top and bottom locking tabs.

Locking tabs

20856-M

2. Pull module out of the chassis.

20857-M

Publication 1756-UM528A-EN-P - April 2004

Page 40

3-14

Installing the Sequence of Events Module

Chapter Summary and What’s Next

In this chapter, you read about: • installing the module. • keying the RTB and IFM. • connecting wiring. • assembling the RTB and the housing. • installing the RTB or IFM onto the module. • removing the RTB from the module. • removing the module from the chassis. Chapter 4 explains Configuring the Sequence of Events Module.

Publication 1756-UM528A-EN-P - April 2004