Page 41

Chapter

4

Configuring the Sequence of Events Module

What This Chapter Contains

This chapter describes how to configure your Sequence of Events module. Table 4.1 For information on:

Configuring Your I/O Module

See page:

Configuring Your I/O Module

4-1

Overview of the Configuration Process

4-2

Adding a New Module to Your RSLogix 5000 Project

4-3

Using the Default Configuration

4-6

Altering the Default Configuration

4-6

Downloading Configuration

4-7

Editing Configuration

4-7

Configuring Modules in a Remote Chassis

4-9

You must configure your module upon installation. The module will not work until it has been configured with at least the default configuration. IMPORTANT

This chapter focuses on configuring I/O modules in a local chassis. To configure I/O modules in a remote chassis, you must follow all the detailed procedures with two additional steps. To see the additional steps, see page 4-9.

RSLogix 5000 Configuration Software You must use RSLogix 5000, version 13 to set configuration for your Sequence of Events module. You have the option of accepting default configuration for your module or writing point level configuration specific to your application. Both options are explained in detail, including views of software screens, in this chapter.

1

Publication 1756-UM528A-EN-P - April 2004

Page 42

4-2

Configuring the Sequence of Events Module

Overview of the Configuration Process

When you use the RSLogix 5000 software to configure a Sequence of Events module, you must perform the following steps: 1. Add the new module to your RSLogix 5000 project. 2. Accept the default configuration or change it to specific configuration for the module. 3. Edit configuration for a module when changes are needed. Figure 4.1 shows an overview of the configuration process. Figure 4.1 Select a: • New module • Major Revision

Click on the Next Button to Set Specific Configuration

Configure the: • Name • Slot number • Comm. format • Minor revision • Keying choice

NEXT

Click on the Finish Button to Use Default Configuration FINISH

Series of Application Specific Screens Make custom configuration choices here

Configuration complete

Download configuration to owner-controller

Reconfigure module as needed via series of screens or controller tags 41058

Publication 1756-UM528A-EN-P - April 2004

Page 43

Configuring the Sequence of Events Module

Adding a New Module to Your RSLogix 5000 Project

4-3

After you have started RSLogix 5000 and created a controller, you must add a new module to your project. The wizard allows you to create a new module and write configuration. You can use default configuration or write specific configuration for your application. IMPORTANT

You must be offline when you create a new module.

1. If necessary, go offline.

If you are not offline, use this pull-down menu to go offline

2. Add the Sequence of Events module to your RSLogix 5000 project.

A. Right-click on I/O Configuration. B. Select New Module

Publication 1756-UM528A-EN-P - April 2004

Page 44

4-4

Configuring the Sequence of Events Module

3. When the Select Module Type screen appears, select the Sequence of Events module.

A. Select the Sequence of Events module. B. Click OK.

4. Configure the module. The first screen of the configuration wizard is shown below. A. Name the module. B. Select the module’s slot number. C. Choose a Communications Format. For more information, see page 4-5. D. Make sure the Minor Revision number matches your module’s minor revision. E. Choose an Electronic Keying method. For more information, see page 5-13. F. If you are altering the default configuration, click Next. Go to page 4-6. G. If you are using default configuration, click Finish. Go to page 4-6.

Publication 1756-UM528A-EN-P - April 2004

Page 45

Configuring the Sequence of Events Module

4-5

Communications Format The communications format determines what operational mode your Sequence of Events module uses and, consequently, what tags RSLogix 5000 generates when configuration is complete. Once a module is created, you cannot change the communications format unless you delete and recreate the module. Table 4.2 lists the communications formats used with input modules: Table 4.2 If you want the Sequence of Events module to operate in this mode choose this communication format:

CST Per Point mode

CST Per Point

FIFO mode

CST FIFO Mode

For more information on the Sequence of Events module’s operational modes, see page 5-3.

Electronic Keying Electronic keying allows the ControlLogix system to control what modules belong in the various slots of a configured system. During module configuration, you must choose one of the following keying options for your Sequence of Events module: • Exact Match • Compatible Module • Disable Keying For more information on electronic keying, see page 5-13.

Publication 1756-UM528A-EN-P - April 2004

Page 46

4-6

Configuring the Sequence of Events Module

Using the Default Configuration

If you use the default configuration and click on Finish, you are done.

Altering the Default Configuration

If you click Next in step 4 on page 4-4, you can write specific configuration for your module in RSLogix 5000. Some of the screens that appear during this initial module configuration process are blank and are not shown here. However, those screens can be important during online monitoring. To see these screens in use, see Chapter 8, Troubleshooting the Sequence of Events Module. Write specific configuration for your Sequence of Events module on the following screens.

On this screen, you can: A. Change the RPI. For more information on the RPI, see page 2-6. B. Inhibit the module. For more information on inhibiting the module, see page 5-15. C. Make sure a Major Fault occurs on the module’s owner-controller if there is a connection failure between the module and the controller. D. Click Next until you see the screen below.

On this screen, you can: A. Enable CST Capture for each input point. For more information on CST Capture, see page 5-5. B. Configure Chatter Detection for each input point. For more information on Chatter Detection, see page 5-8. C. Set the Input Filter Times. For more information on Input Filters, see page 5-10. D. Click on the box to enable CST Latching. For more information on CST Latching, see page 5-7. E. Click Finish.

Publication 1756-UM528A-EN-P - April 2004

Page 47

Configuring the Sequence of Events Module

Downloading Configuration

4-7

After you write configuration for your Sequence of Events module, the module does not use this configuration until you download it to the owner-controller. The download transfers the entire program to the controller, overwriting any existing program. Download module configuration as shown below.

A. Click here to see the pull-down menu. B. Click download.

Depending on your application, a variety of RSLogix 5000 screens may appear to choose a path to your ControlLogix controller and to verify the download. Navigate those screens as best fits your application. This completes the download process.

Editing Configuration

After you have set configuration for a module, you can review and change your choices. You can change configuration data and download it to the controller while online. This is called dynamic reconfiguration. Your freedom to change some configurable features, though, depends on whether the controller is in Remote Run Mode or Program Mode. IMPORTANT

Although you can change configuration while online, you must go offline to add or delete modules from the project.

Publication 1756-UM528A-EN-P - April 2004

Page 48

4-8

Configuring the Sequence of Events Module

The editing process begins on the main page of RSLogix 5000.

A. Right-click on the module. B. Select Properties

The General tab of the configuration wizard appears. Click on the tab of the page that you want to view or reconfigure and make any appropriate changes. Make any necessary changes as shown in the example below.

A. Click the tab where you need to reconfigure the module. In this example, CST Capture was disabled for several input points. B. When the module is reconfigured, click OK.

Publication 1756-UM528A-EN-P - April 2004

Page 49

Configuring the Sequence of Events Module

Configuring Modules in a Remote Chassis

4-9

ControlLogix ControlNet Interface modules (1756-CNB or 1756-CNBR) or the EtherNet/IP Bridge module (1756-ENBT) are required to communicate with Sequence of Events modules in a remote chassis. You must configure the communications module in the local chassis and the remote chassis before adding remote Sequence of Events modules to your project. 1. Add a communications module to the local chassis.

A. Right-click on I/O Configuration. B. Select New Module

2. Choose a communications module (1756-CNB, 1756-CNBR or 1756-ENBT) for the local chassis. 3. Configure the communications module in the local chassis. For more information on the ControlLogix ControlNet Interface modules, see the Using ControlNet Communication Modules in Logix5000 Control Systems user manual, publication CNET-UM001. For more information on the ControlLogix EtherNet/IP Bridge module, see the Using EtherNet/IP Communication Modules in Logix5000 Control Systems user manual, publication ENET-UM001.

Publication 1756-UM528A-EN-P - April 2004

Page 50

4-10

Configuring the Sequence of Events Module

4. Add a communications module to the remote chassis.

A. Right-click on the local communication module. B. Select New Module

5. Select a communications module for the remote chassis. 6. Configure the communications module in the remote chassis. 7. Add a Sequence of Events module to the remote chassis.

A. Right-click on the remote communication module. B. Select New Module

8. Configure the new Sequence of Events module as described earlier in this chapter. Publication 1756-UM528A-EN-P - April 2004

Page 51

Configuring the Sequence of Events Module

Chapter Summary and What’s Next

4-11

In this chapter, you read about configuring your Sequence of Events module. Chapter 5 describes Using the Sequence of Events Module Features.

Publication 1756-UM528A-EN-P - April 2004

Page 52

4-12

Configuring the Sequence of Events Module

Notes: