Page 91

Program

Chapter 4

Profile

ACC/DEC

Motor

Priority of Control

S-curve

2X Slower

Best

Jerk

Jerk Programming in Units/Sec3

Unique program considerations

Acc/Dec

Velocity

Position

To specify the jerk in 'Units/sec3' instead of '% of time', adjust the jerk value to get the programmed value:

If programming a move using the ‘% of Time units’, Logix Designer application computes an: Accel Jerk = a2/v where a = the programmed Accel Rate and v = programmed Speed. Therefore, the higher the programmed speed, the lower the computed Jerk. The system has a Jerk priority planner. In other words, Jerk has a higher priority than acceleration and velocity. Therefore, the programmed Jerk is always present. If a move is velocity-limited, the move does not reach the programmed acceleration and/or velocity. Once the velocity limit for the length of the move is reached, as the velocity increases, the move requires more time to complete. ‘Decel Jerk’ is computed similarly to the Accel Jerk described above. The only difference is that instead of a2/v, Decel Jerk = d2/v, where d = the programmed Decel Rate.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

91

Page 92

Chapter 4

Program

Example:

Example #1 Start Speed = 8.0 in/sec Desired Speed = 5.0 in/sec Desired Decel Rate = 2.0 in/sec2 Desired Decel Jerk = 1.0 in/sec3 Temporary Speed = (Desired Decel Rate)2 / Desired jerk value in Units/Sec3= 2.02 / 1.0 = = 4.0 in/sec k = (8.0 - 5.0) / max(5.0, 4.0) = 3.0 / 5.0 = = 0.6 Because k < 1, enter the desired Decel jerk directly in the faceplate Instruction faceplate Decel jerk in Units/Sec3 = 1.0 in/sec3

Example:

Example #2 Start Speed = 13.0 in/sec Desired Speed = 5.0 in/sec Desired Decel Rate = 2.0 in/sec2 Desired Decel Jerk = 1.0 in/sec3 Temporary Speed = (Desired Decel Rate)2 / Desired jerk value in Units/Sec3= 2.02 / 1.0 = = 4.0 in/sec k = (13.0 - 5.0) / max(5.0, 4.0) = 8.0 / 5.0 = = 1.6 Because k > 1, must calculate the Decel jerk to use on the instruction faceplate as: Instruction faceplate Decel jerk in Units/Sec3 = = 1.0 in/sec3 * 1.6 = = 1.6 in/sec3

What is the revision?

Profile operand

•

15 or earlier – % of Time is fixed at 100.

•

16 or later – % of Time defaults to 100% of time on projects converted from earlier versions. For new projects, enter the Jerk value.

The profile operand has two profile types: •

Trapezoidal velocity profile

•

S-Curve velocity profile

See also Choose a profile on page 85

Trapezoidal velocity profile

92

The trapezoidal velocity profile is the most commonly used profile because it provides the most flexibility in programming subsequent motion and the fastest acceleration and deceleration times. The change in velocity per unit time is specified by acceleration and deceleration. Jerk is not a factor for trapezoidal

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Page 93

Program

Chapter 4 profiles. Therefore, it is considered infinite and is shown as a vertical line in the following graph.

S-Curve velocity profile

S-Curve velocity profiles are most often used when the stress on the mechanical system and load needs to be minimized. The acceleration and deceleration time is balanced against the machine stress using two additional parameters, acceleration jerk and deceleration jerk. Depending on the Jerk settings, the acceleration profile can be set to: •

Almost pure trapezoidal (fastest and highest stress).

•

S-Curve (slowest, lowest stress).

The typical acceleration profile is a trade-off between stress and speed. The Jerk is specified by the user (in Units/sec3 or as a percentage of maximum), or it is calculated from the percentage of time. (Percentage of time is equal to the percentage of ramp time in the acceleration/deceleration profile):

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

93

Page 94

Chapter 4

Program

Backward compatibility

The Jerk of 100% of time produces triangular acceleration and deceleration profiles. Very small Jerk rates that are less than 5% of time, produce acceleration and deceleration profiles close to trapezoidal ones. Important:

Trapezoidal Velocity Profile 3

Higher values of the % of Time result in lower values of Jerk Rate Limits and, therefore, slower profiles. See table for reference.

S-shaped Velocity Profile with 1< = Jerk <100% of Time4

S-shaped Velocity Profile with Jerk = 100% of Time5

Accel/Decel Jerk in Units/sec3

∞

Accel/Decel Jerk in % of Maximum

NA

0 - 100%

NA

Accel/Decel Jerk in % of Time

0%

1 - 100%

100%

Calculations are performed when an Axis Move, Change Dynamics, or an MCS Stop of StopType = Move or Jog is initiated.

The example labeled Trapezoidal Accel/Decel Time uses a rectangular acceleration profile. 4 The example labeled Programmable S-Curve Accel/Decel Time, Acceleration Jerk = 60% of Time uses a trapezoidal acceleration profile. 5 The example labeled S-Curve Accel/Decel Time, Backward Compatibility Setting: Acceleration Jerk = 100% of Time uses a triangular acceleration profile. 3

94

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Page 95

Program

Chapter 4

Programmable S-Curve Accel/Decel Time Acceleration Jerk = 60% of Time

S-Curve Accel/Decel Time, Backward Compatibility Setting: Acceleration Jerk = 100% of Time

Enter basic logic

The controller gives a set of motion control instructions for the axes. •

Uses the instructions in the same way as other Logix 5000 instructions. Program motion control in these programming languages.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

95

Page 96

Chapter 4

Program

•

Ladder diagram (LD)

•

Structured text (ST)

•

Sequential function chart (SFC)

•

Each motion instruction works on one or more axes.

•

Each motion instruction needs a motion control tag. The tag uses a MOTION_INSTRUCTION data type. The tag stores the instruction status information.

ATTENTION: Use the tag for the motion control operand of motion instruction only once. Unintended operation of the control variables may happen if reusing the same motion control tag in other instructions.

Example: Motion control program

This example of ladder logic homes, jogs, and moves an axis.

If Initialize_Pushbutton = on and the axis = off (My_Axis_X.ServoActionStatus = off) then The MSO instruction turns on the axis.

If Home_Pushbutton = on and the axis has not been homed (My_Axis_X.AxisHomedStatus = off) then The MAH instruction homes the axis.

96

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Page 97

Program

Chapter 4

If Jog_Pushbutton = on and the axis = on (My_Axis_X.ServoActionStatus = on) then The MAJ instruction jogs the axis forward at 8 units/s.

If Jog_Pushbutton = off then The MAS instruction stops the axis at 100 units/s2 Make sure that Change Decel is Yes. Otherwise, the axis decelerates at its maximum speed.

If Move_Command = on and the axis = on (My_Axis_X.ServoActionStatus = on) then The MAM instruction moves the axis. The axis moves to the position of 10 units at 1 unit/s.

Download a program and run the logic

Use these instructions to download a program to the controller. To download a program to a controller: 1. With the keyswitch, place the controller in Program or Remote Program mode. 2. From the Communications menu, select Download. 3. Confirm to complete the download procedure. Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

97

Page 98

Chapter 4

Program

4. Select Download. 5. Once the download is complete, place the controller in Run/Test mode. The status and compiler messages appear in the status bar. See also Test an axis with Motion Direct Commands on page 75 Troubleshoot axis motion on page 100

Choose a motion instruction Use this table to choose an instruction and verify its availability as a Motion Direct Command.

To

And

Use This Instruction

Motion Direct Command

Change the state of an axis

Enable the drive and activate the axis servo loop.

MSO Motion Servo On

Yes

Disable the drive and deactivate the axis servo loop.

MSF Motion Servo Off

Yes

Force an axis into the shutdown state and block any instructions that initiate axis motion.

MASD Motion Axis Shutdown

Yes

Reset the axis from the shutdown state.

MASR Motion Axis Shutdown Reset

Yes

Enable the drive and set the servo output voltage of an axis.

MDO Motion Direct Drive On

Yes

Disable the drive and set the servo output voltage to the output offset voltage.

MDF Motion Direct Drive Off

Yes

Clear all motion faults for an axis.

MAFR Motion Axis Fault Reset

Yes

Stop any motion process on an axis.

MAS Motion Axis Stop

Yes

Home an axis.

MAH Motion Axis Home

Yes

Jog an axis.

MAJ Motion Axis Jog

Yes

Move an axis to a position.

MAM Motion Axis Move

Yes

Start electronic gearing between 2 axes.

MAG Motion Axis Gear

Yes

Control axis position

98

Change the speed, acceleration, or deceleration of a move MCD or a jog that is in progress. Motion Change Dynamics

Yes

Define a Master/Slave relationship between two motion axes and select the type of move instructions.

No

MDAC Master Driven Axis Control

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Page 99

Program

To

Chapter 4

And

Use This Instruction

Motion Direct Command

Change the command or actual position of an axis.

MRP Motion Redefine Position

Yes

Calculate a Cam Profile based on an array of cam points.

MCCP Motion Calculate Cam Profile

No

Start electronic camming between 2 axes.

MAPC Motion Axis Position Cam

No

Start electronic camming as a function of time.

MATC Motion Axis Time Cam

No

Calculate the slave value, slope, and derivative of the slope for a cam profile and master value.

MCSV Motion Calculate Slave Values

No

Stop motion of all axes.

MGS Motion Group Stop

Yes

Force all axes into the shutdown state.

MGSD Motion Group Shutdown

Yes

Transition all axes to the ready state.

MGSR Motion Group Shutdown Reset

Yes

Latch the current command and actual position of all axes.

MGSP Motion Group Strobe Position

Yes

Arm and disarm special event checking Arm the watch-position event checking for an axis. functions such as registration and watch position Disarm the watch-position event checking for an axis.

MAW Motion Arm Watch Position

Yes

MDW Motion Disarm Watch Position

Yes

Initiate action on all axes

Arm the servo-module registration-event checking for an MAR axis. Motion Arm Registration

Yes

Disarm the servo-module registration-event checking for an axis.

MDR Motion Disarm Registration

Yes

Arm an output cam for an axis and output.

MAOC Motion Arm Output Cam

No

Disarm one or all output cams connected to an axis.

MDOC Motion Disarm Output Cam

No

MAAT Motion Apply Axis Tuning

No

MRAT Motion Run Axis Tuning

No

Tune an axis and run diagnostic tests for Uses the results of an MRAT instruction to calculate and the control system. These tests include: update the servo gains and dynamic limits of an axis. • Motor/encoder hookup test Run a tuning motion profile for an axis. • Encoder hookup test • Marker test

Control multi-axis coordinated motion

Use the results of an MRHD instruction to set encoder and MAHD servo polarities. Motion Apply Hookup Diagnostic

No

Run one of the diagnostic tests on an axis.

MRHD Motion Run Hookup Diagnostic

No

Start a linear coordinated move for the axes of coordinate MCLM system. Motion Coordinated Linear Move

No

Start a circular move for the axes of coordinate system.

MCCM Motion Coordinated Circular Move

No

Change in path dynamics for the active motion on a coordinate system.

MCCD Motion Coordinated Change Dynamics

No

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

99

Page 100

Chapter 4

Program

To

And

Use This Instruction

Motion Direct Command

Stop the axes of a coordinate system or cancel a transform.

MCS Motion Coordinated Stop

No

Shutdown the axes of a coordinate system.

MCSD Motion Coordinated Shutdown

No

Start a transform that links two coordinate systems together. This is like bi-directional gearing.

MCT Motion Coordinated Transform 6

No

Calculate the position of one coordinate system with respect to another coordinate system.

MCTP Motion Calculate Transform Position7

No

Transition the axes of a coordinate system to the ready state and clear the axis faults.

MCSR Motion Coordinated Shutdown Reset

No

Define a Master/Slave relationship between a Master Axis MDCC and a Coordinate System. Master Driven Coordinated Control

No

Sample projects

The Rockwell Automation sample project's default location is: c:\Users\Public\Public Documents\Studio 5000\Sample\ENU\v<current_release>\Rockwell Automation A PDF file named Vendor Sample Projects explains how to work with the sample projects. Free sample code is available at http://samplecode.rockwellautomation.com/. The Vendor Sample Projects.pdf default location is: c:\Users\Public\Public Documents\Studio 5000\Sample\ENU\v<current_release>\Third Party Products

Troubleshoot axis motion

Troubleshooting information is provided for situations that may occur while running an axis.

Why does my axis accelerate when I stop it?

While an axis is accelerating, you try to stop it. The axis keeps accelerating for a short time before it starts to decelerate.

Example

You start a Motion Axis Jog (MAJ) instruction. Before the axis gets to its target speed, you start a Motion Axis Stop (MAS) instruction. The axis continues to speed up and then eventually slows to a stop.

6 7

100

Use this instruction only with 1756-L6x controllers. Use this instruction only with 1756-L6x controllers.