The text of a manual · part 11 of 30
SERCOS and Analog Motion Configuration and Startup User Manual, pages 101 to 110
Pages 101 to 110 of 297
The original document is the PDF (13 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-M16SE/A
Page 101
Program
Chapter 4
Look For
Cause
When using an S-curve profile, jerk determines the acceleration and deceleration time of the axis. •
An S-curve profile must get acceleration to 0 before the axis can slow down.
•
The time required depends on the acceleration and speed.
•
In the meantime, the axis continues to speed up.
These trends show how the axis stops with a trapezoidal profile and an S-curve profile. Stop while accelerating Trapezoidal
S-curve
The axis slows down as soon as you start the stopping instruction.
The axis continues to speed up until the S-curve profile brings the acceleration rate to 0.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
101
Page 102
Chapter 4
Corrective Action
Program
Revision 15 or earlier
Revision 16 or later Leave bit 0 of the DynamicsConfigurationBits attribute for the axis turned ON. Otherwise, this corrective action will not work. For more information search for Dynamic Configuration Bits in the Help.
In Revision 16 and later, increase the deceleration jerk of an Motion Action Stop (MAS) instruction to get a quicker stop.
102
If the Jerk Units Are
Then Make This Change to the Decel Jerk
% of Time
Reduce the % of Time on the Decel Jerk
% of Maximum
Increase the % of Maximum on the Decel Jerk
Units per sec3
Increase Units per sec3 on the Decel Jerk
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 103
Program
Chapter 4
Why does my axis overshoot its target speed?
While an axis is accelerating, you try to stop the axis or change its speed. The axis keeps accelerating and goes past its initial target speed. Eventually the axis starts to decelerate.
Example
You start a Motion Axis Jog (MAJ) instruction. Before the axis gets to its target speed, you try to stop it with another MAJ instruction. The speed of the second instruction is set to 0. The axis continues to speed up and overshoots its initial target speed. Eventually it slows to a stop.
Look For
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
103
Page 104
Chapter 4
Program
Cause
When using an S-curve profile, jerk determines the acceleration and deceleration time of the axis. •
An S-curve profile must get acceleration to 0 before the axis can slow down.
•
If reducing the acceleration, more time is required to get acceleration to 0.
•
In the meantime, the axis continues past its initial target speed.
These trends show how the axis stops with a trapezoidal profile and an S-curve profile. Stop while accelerating and reduce the acceleration rate
104
Trapezoidal
S-curve
The axis slows down as soon as the stopping instruction starts. The lower acceleration does not change the response of the axis.
The stopping instruction reduces the acceleration of the axis. It now takes longer to bring the acceleration rate to 0. The axis continues past its target speed until acceleration equals 0.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 105
Program
Corrective Action
Chapter 4
Use a Motion Axis Stop (MAS) instruction to stop the axis or configure the instructions as shown:
Why is there a delay when I stop While an axis is jogging at its target speed, you stop the axis. Before the axis stops completely, you restart the jog. The axis continues to slow down before it speeds and then restart a jog? up.
Example
Use a Motion Axis Stop (MAS) instruction to stop a jog. While the axis is slowing down, use a Motion Axis Jog (MAJ) instruction to start the axis again. The axis does not respond right away. It continues to slow down. Eventually the axis speeds back up to the target speed.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
105
Page 106
Chapter 4
Program
Look For
For Stop Type, the instruction that stops the axis keeps the S-curve profile. If using a Motion Axis Stop (MAS) instruction with the Stop Type set to Jog, the axis keeps the profile of the Motion Axis Jog (MAJ) instruction that started the axis.
Cause
106
When using an S-curve profile, jerk determines the acceleration and deceleration time of the axis. An S-curve profile has to get acceleration to 0 before the axis can speed up again. These trends show how the axis stops and starts with a trapezoidal profile and an S-curve profile.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 107
Program
Chapter 4
Start while decelerating Trapezoidal
S-curve
The axis speeds back up as soon as you start the jog again.
The axis continues to slow down until the S-curve profile brings the acceleration rate to 0.
Corrective action
The corrective action depends on the revision of the controller. If the controller revision is
Then
Result
15 or earlier
Increase the deceleration rate of the Motion Axis Jog (MAJ) instruction that starts the jog.
This increases the deceleration jerk. The axis stops the deceleration sooner at the higher deceleration jerk.
16 or later
Increase the deceleration jerk of the Motion Axis Jog (MAJ) instruction that starts the jog.
The axis stops the deceleration sooner at the higher deceleration jerk.
Why does my axis overshoot its position and reverse direction? Example
While an axis is moving to a target position, you change a parameter of the move. The axis overshoots its target position. Eventually the axis stops and moves back to its target position. Use a Motion Change Dynamics (MCD) instruction to reduce the deceleration while a Motion Axis Move (MAM) instruction is in process. The axis continues past the target position of the move, stops, and returns to the target position.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
107
Page 108
Chapter 4
Program
Look For
Cause
108
The axis does not have enough time at the new lower deceleration to stop at the target position. The axis stops past the target position. Then the axis corrects to get back to the target position.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 109
Program
Corrective action
Chapter 4
To avoid overshooting position, do one: •
Avoid decreasing the deceleration or deceleration jerk while an axis is decelerating along an S-curve profile.
•
Avoid increasing the programmed speed while an axis is decelerating along an S-curve profile. This has the same effect as decreasing the deceleration jerk.
Test any changes in small increments to make sure a change does not cause an overshoot during normal operation.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
109