Page 121
Axis properties
Appendix A
Node with a Kinetix 6000 drive
If using the auxiliary feedback port of a Kinetix 6000 drive as a feedback-only axis, the drive must have firmware revision 1.80 or later.
When a Kinetix 6000 drive is designated in the Associated Module box, there is an additional option for the Node value. The option is the node associated with the drive plus 128 with (Auxiliary) after the number. The range is 129 to 234. When the Auxiliary Node assignment is chosen, the axis configuration is changed to Feedback Only on the General tab and an asterisk (*) appears next to General. This also places an asterisk (*) on the Aux Feedback tab. Select that tab and choose values. On the Drive/Motor tab, the Loop Configuration changes to Aux Feedback Only.
General tab - AXIS_VIRTUAL This image is an example of the General tab for an AXIS_VIRTUAL Data Type.
Motion Group
Select the Motion Group to which the axis is associated. An axis assigned to a Motion Group appears in the Motion Groups folder of the Controller Organizer. Selecting ‘none’ terminates the Motion Group association, and moves the axis to the Ungrouped Axes folder in the Controller Organizer. Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
121
Page 122
Appendix A
Axis properties
MOTION_GROUP structure
One MOTION_GROUP data type per controller. This structure contains status and configuration information about the motion group.
Enumerations
Data Type
Description
GroupStatus
DINT
The status bits for the group.
MotionFault
ServoFault
GroupFault
AxisFault
DINT
DINT
DINT
DINT
Bit
Number
Data Type
Description
InhibitStatus
00
DINT
Inhibit status.
GroupSynced
01
DINT
Synchronization status.
AxisInhibitStatus
02
DINT
-no-tag
02
DINT
Timer Event started.
Reserved
03…31
The motion fault bits for the group. Bit
Number
Data Type
Description
ACAsyncConnFault
00
DINT
Asynchronous connection fault.
ACSyncConnFault
01
DINT
Synchronous connection fault.
Reserved
02…31
The servo-module fault bits for the group. Bit
Number
Data Type
Description
POtrvlFault
00
DINT
Positive overtravel fault.
NOtrvlFault
01
DINT
Negative overtravel fault.
PosErrorFault
02
DINT
Position error fault.
EncCHALossFault
03
DINT
Encoder channel A loss fault.
EncCHBLossFault
04
DINT
Encoder channel B loss fault.
EncCHZLossFault
05
DINT
Encoder channel Z loss fault.
EncNsFault
06
DINT
Encoder noise fault.
DriveFault
07
DINT
Drive fault.
Reserved
08…31
Bit
Number
Data Type
Description
SyncConnFault
00
DINT
Synchronous connection fault.
HardFault
01
DINT
Servo hardware fault.
Reserved
02…31
The fault bits for the group. Bit
Number
Data Type
Description
GroupOverlapFault
00
DINT
Group task overlap fault.
CSTLossFault
01
DINT
The controller has lost synchronization with the CST master.
GroupTaskLoadingFault
02
DINT
The group base update period is too low, user application tasks are not getting enough time to execute.
Reserved
03…31 Data Type
Description
The fault bits for the axis. Bit
122
Number
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 123
Axis properties
Enumerations
Appendix A
Data Type
Description PhysicalAxisFault
00
DINT
A Servo or Drive fault occurred.
ModuleFault
01
DINT
A serious fault occurred with the motion module associated with the selected axis. Usually affects all axes associated with the motion module.
ConfigFault
02
DINT
One or more axis attributes associated with a motion module or drive was not successfully updated to match the value of the corresponding attribute of the local controller.
Reserved
03…31
General tab – AXIS_GENERIC
This example shows the General tab for an AXIS_GENERIC data type.
Item
Description
Axis Configuration
Selects and displays the intended use of the axis. Feedback Only
If the axis is used only to display position information from the feedback interface. This selection minimizes the display of axis properties tabs and parameters. The Dynamics tab is not available.
Servo
If the axis is used for full servo operation. This selection maximizes the display of axis properties tabs and parameters.
Motion Group
Selects and displays the Motion Group to which the axis is associated. An axis assigned to a Motion Group appears in the Motion Groups folder of the Controller Organizer, under the selected Motion Group sub-folder. Selecting <none> terminates the Motion Group association, and moves the axis to the Ungrouped Axes sub-folder of the Motion Groups branch.
Module
Selects and displays the name of the motion module to which the axis is associated. Displays <none> if the axis is not associated with any motion module.
Channel
Selects and displays the motion module channel, 0 or 1, to which the axis is assigned. Disabled when the axis is not associated with any motion module.
Motion Planner tab
Use the Motion Planner tab options to: •
Set and edit the number of Output Cam Execution Targets and the Program Stop Action
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
123
Page 124
Appendix A
Axis properties
•
Select and clear the Master Delay Compensation and Enable Master Position Filter
•
Set the bandwidth for Master Position Filter Bandwidth
The Motion Planner tab has the same fields regardless of the type of axis.
124
Item
Description
Output Cam Execution Targets
Determines how many Output Cam execution nodes (instances) to create for an axis. The Execution Target parameter for the MAOC/MDOC instructions specifies which of the configured execution nodes the instruction affects. In addition, the number specified in the Axis Properties dialog box specifies the number of instances of Output Cam in which the value of zero means ‘none’. The value specified for Execution Target in the MAOC instruction references an instance in which a value of zero selects the first instance.
Program Stop Action
Selects how an axis is stopped when the processor undergoes a mode change, or when an explicit Motion Group Programmed Stop (MGPS) instruction is executed. Apply Program Stop Action when an MSG is programmed to Stop type. Fast Disable
The axis is decelerated to a stop using the current configured value for maximum deceleration. Servo action is maintained until the axis motion has stopped, at which time the axis is turned off (that is, Drive Enable is disabled, and Servo Action is disabled).
Fast Shutdown
The axis is decelerated to a stop using the current configured value for maximum deceleration. Once the axis motion has stopped, the axis is placed in the shutdown state (that is, Drive Enable is disabled, Servo Action is disabled, and the OK contact is opened). To recover from this state, execute a Shutdown reset instruction.
Fast Stop
The axis is decelerated to a stop using the current configured value for maximum deceleration. Servo action is maintained after the axis motion has stopped. This mode is useful for gravity or loaded systems, where servo control is needed at all times.
Hard Disable
The axis is immediately disabled (that is, Drive Enable is disabled, Servo Action is disabled, but the OK contact is left closed). Unless the drive is configured to provide some form of dynamic breaking, this results in the axis coasting to a stop.
Hard Shutdown
The axis is immediately placed in the shutdown state. Unless the drive is configured to provide some form of dynamic breaking, this results in the axis coasting to a stop. To recover from this state, a Shutdown reset instruction must be executed.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 125
Axis properties
Appendix A
Item
Description
Master Delay Compensation
Enables or disables Master Delay Compensation. The default setting is Disabled. Select to enable Master Delay Compensation. Master Delay Compensation balances the delay time between reading the master axis command position and applying the associated slave command position to the slave’s servo loop. It ensures that the slave axis command position accurately tracks the actual position of the master axis; that is, zero tracking error. If the axis is configured for Feedback only, disable Master Delay Compensation.
Enable Master Position Filter
Enables or disables the Master Position Filter. The default is disabled. Select to enable position filtering. Master Position Filter effectively filters the specified master axis position input to the slave axis’s gearing or position camming operation. The filter smooths out the actual position signal from the master axis, and thus smooths out the corresponding motion of the slave axis. When this feature is enabled the Master Position Filter Bandwidth field is enabled.
Master Position Filter Bandwidth
Enabled when Enable Master Position Filter is selected. This field controls the bandwidth for master position filtering. Enter a value in Hz to set the bandwidth for the Master Position Filter. Important: A value of zero for Master Position Filter Bandwidth effectively disables the master position filtering.
The Units tab is the same for all axis data types. Use this tab to determine the units to define the motion axis.
Units tab
Item
Description
Position Units
User-defined engineering units (rather than feedback counts) used for labeling all motion-related values, for example, position and velocity. These position units can differ for each axis. Choose position units for maximum ease of use in the application. For example, linear axes might use position units of Inches, Meters, or mm whereas rotary axes might use units of Revs or Degrees.
Average Velocity Timebase
Specifies the time (in seconds) used for calculating the average velocity of the axis. This value is computed by taking the total distance the axis travels in the amount of time specified and dividing this value by the timebase. The average velocity timebase value should be large enough to filter out the small changes in velocity that result in a noisy velocity value, but small enough to track significant changes in axis velocity. A value of 0.25 to 0.50 seconds works well for most applications.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
125
Page 126
Appendix A
Axis properties
Servo tab - AXIS_SERVO
This image is an example of the Servo tab for AXIS_SERVO.
Item
Description
External Drive Configuration
Select the drive type for the servo loop: • Velocity - Disables the servo module’s internal digital velocity loop. • Torque - The servo module’s internal digital velocity loop is active, which is the required configuration for interfacing the servo axis to a torque loop drive. • Hydraulic - Enables hydraulic servo application features.
Loop Configuration
Select the configuration of the servo loop. For this release, only Position Servo is available.
Enable Drive Fault Input
Select to enable the Drive Fault Input. When active, the motion module receives notice whenever the external drive detects a fault.
Drive Fault Input
Specifies the usual state of the drive fault input when a fault is detected on the drive. • Normally Open – When a drive fault is detected, it opens its drive fault output contacts. • Normally Closed – When a drive fault is detected, it closes its drive fault output contacts.
126
Enable Direct Drive Ramp Control
Select to set the Direct Drive Ramp Rate in volts per second when a Direct Drive On (MDO) instruction is executed.
Direct Drive Ramp Rate
The Direct Drive Ramp Rate is a slew rate for changing the output voltage when an MDO instruction is executed. A Direct Drive Ramp Rate of 0 disables the output rate limiter, letting the Direct Drive On voltage be applied directly.
Attribute 1/Attribute 2
Select up to two axis attributes whose statuses are transmitted with, for example, the actual position data to the Logix processor. Access the values of the selected attributes through the standard GSV or Get Attribute List service. Can also access the values using template data. The servo status data is updated each base update period. If a GSV is done to one of these servo status attributes without having selected this attribute through the Drive Info Select attribute, the attribute value is static and does not reflect the true value in the servo module.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 127
Axis properties
Appendix A
Feedback tab – AXIS_SERVO Use the Feedback tab to select the type of Feedback used with the Servo axis.
Item
Description
Feedback Type
Select the Feedback type for the current configuration. The options depend on the motion module to which the axis is associated. A Quadrature B Encoder Interface (AQB)
The 1756-M02AE servo module provides interface hardware to support incremental quadrature encoders equipped with standard 5-Volt differential encoder-interface signals. The AQB option has no associated attributes to configure.
Synchronous Serial Interface (SSI)
The 1756-M02AS servo module provides an interface to transducers with Synchronous Serial Interface (SSI) outputs. SSI outputs use standard 5V differential signals (RS422) to transmit information from the transducer to the controller. The signals consist of a Clock generated by the controller and Data generated by the transducer.
Linear Displacement Transducer (LDT)
The 1756-HYD02 Servo module provides an interface to the Linear Magnetostrictive Displacement Transducer, or LDT. A Field Programmable Gate Array (FPGA) is used to implement a multi-channel LDT Interface. Each channel is functionally equivalent and is capable of interfacing to an LDT device with a maximum count of 240,000. The LDT interface has transducer failure detection and digital filtering to reduce electrical noise.
Item
Description
Feedback Type
Feedback Type is set to SSI - Synchronous Serial Interface.
Code Type
The type of code, Binary or Gray, used to report SSI output. If the module’s setting does not match the feedback device, the positions jump around erratically as the axis moves.
Data Length
The length of output data in a specified number of bits between 8 and 31. The data length for the selected feedback device is found in its specifications.
Clock Frequency
Sets the clock frequency of the SSI device to 208 (default) or 625 kHz. When the higher clock frequency is used, the data from the feedback device is more recent, but the length of the cable to the transducer must be shorter than with the lower frequency.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
127
Page 128
Appendix A
128
Axis properties
Item
Description
Enable Absolute Feedback
The default is enabled (checked). If Enable Absolute Feedback is set, the servo module adds the Absolute Feedback Offset to the current position of the feedback device to establish the absolute machine reference position. Absolute feedback devices retain their position reference even through a power-cycle; therefore, the machine reference system can be restored at powerup.
Absolute Feedback Offset
If Absolute feedback is enabled, this field becomes active. Enter the amount of offset, in position units, to add to the current position of the Feedback device. The SSI is an absolute feedback device. To establish a value for the Offset, execute the MAH instruction with the Home Mode set to Absolute. When executed, the module computes the Absolute Feedback Offset as the difference between the configured value for Home Position and the current absolute feedback position of the axis. The computed Absolute Feedback Offset is immediately applied to the axis upon completion of the MAH instruction. The actual position of the axis is rereferenced during execution of the MAH instruction; therefore, the servo loop must not be active. If the servo loop is active, the MAH instruction generates an error. When the Enable Absolute Feedback is disabled, the servo module ignores the Absolute Feedback Offset and treats the feedback device as an incremental position transducer. A homing or redefine position operation is required to establish the absolute machine reference position. The Absolute Home Mode is invalid. If using single-turn or multi-turn Absolute SSI Feedback transducers, see the Homing tab information for important details concerning Absolute feedback transducer’s marker reference.
Item
Description
Feedback Type
Feedback Type is set to LDT - Linear Displacement Transducer.
LDT Type
Selects the type of LDT to use to provide feedback to the Hydraulic module. The available types are PWM, Start/Stop Rising, or Start/Stop Falling.
Recirculations
Use this field to set the number of repetitions to use to acquire a measurement from an LDT.
Calibration Constant
Number engraved on the LDT by the manufacturer. The number specifies the characteristics of the individual LDT. Each LDT has its own calibration constant; therefore, changing the LDT also requires changing the Calibration constant.
Length
Defines the stroke of travel of the hydraulic cylinder. The length value is used with the number of recirculations to determine the minimum servo update period.
Scaling
Defines the relationship between the LDT unit of measure (length field) and the unit of measure defined at the Units tab.
Enable Absolute Feedback
Active only when Feedback Type is LDT.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 129
Axis properties
Appendix A
Item
Description
Absolute Feedback Offset
Enter the amount of offset, in position units, to add to the current position of the LDT. The LDT is an absolute feedback device. To establish a value for the Offset, execute the MAH instruction with the Home Mode set to Absolute. When executed, the module computes the Absolute Feedback Offset as the difference between the configured value for Home Position and the current absolute feedback position of the axis. The computed Absolute Feedback Offset is immediately applied to the axis upon completion of the MAH instruction. The actual position of the axis is re-referenced during execution of the MAH instruction; therefore, the servo loop must not be active. If the servo loop is active, the MAH instruction generates an error. When the Enable Absolute Feedback is disabled, the servo module ignores the Absolute Feedback Offset and treats the feedback device as an incremental position transducer. A homing or redefine position operation is required to establish the absolute machine reference position. The Absolute Home Mode is invalid.
Calculated Values
Conversion Constant
The Conversion Constant is calculated from the values entered on the Feedback screen when selecting Calculate. This calculated value must be typed into the Conversion Constant field on the Conversion tab because the value is not automatically updated.
Minimum The Minimum Servo Update period is calculated based on the values entered for Recirculations and Length Servo Update on the Feedback tab. When these values are changed, clicking Calculate recalculates the Minimum Servo Period Update Period based on the new values. Calculate Button
Drive/Motor tab AXIS_SERVO_DRIVE
Calculate becomes active whenever making changes to the values on the Feedback tab. Selecting Calculate recalculates the Conversion Constant and Minimum Servo Update Period values. Re-enter the Conversion Constant value at the Conversion tab because the values are not updated automatically.
Use the Drive/Motor tab to configure the servo loop for an AXIS_SERVO_DRIVE axis, and open the Change Catalog dialog box.
Item
Description
Amplifier Catalog Number
Select the catalog number of the amplifier to which this axis is connected.
Motor Catalog Number
Select the catalog number of the motor associated with this axis. When changing a Motor Catalog Number, the controller recalculates the values.
Change Catalog
Opens the Change Catalog Number dialog box to select a new motor catalog number.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
129
Page 130
Appendix A
Axis properties
Loop Configuration
Select the configuration of the servo loop. • Motor Feedback Only – Displayed when Axis Configuration is Feedback only • Aux Feedback Only – Displayed when Axis Configuration is Feedback only • Position Servo • Aux Position Servo (not applicable to Ultra3000 drives) • Dual Position Servo • Dual Command Servo • Aux Dual Command Servo • Velocity Servo • Torque Servo • Dual Command/Feedback Servo
Drive Resolution
Type the number of counts per motor revolution. This value applies to all position data. Valid values range from 1 to 2^32 - 1. One Least Significant Bit (LSB) for position data equals 360° / RotationalPositionResolution. The Drive Resolution is also referred to as Rotational Position Resolution. When saving an edited Conversion Constant or a Drive Resolution value, a message box opens, asking if the controller should automatically recalculate certain attribute settings. Drive Resolution is especially helpful for fractional unwind applications or multi-turn applications requiring cyclic compensation. Modify the Drive Resolution value so that dividing it by the Unwind Value yields a whole integer value. The higher the Drive Resolution setting, the finer the resolution.
Drive Counts per
Choose the units to use for this drive. Options are Motor Inch, Motor Millimeter, and Motor Rev (default).
Calculate
Opens the Calculate Position Parameters dialog box to calculate Drive Resolution and Conversion Constant values based on specific Position Unit Scaling and Position Range information.
Drive Enable Input Checking
Select to enable Drive Enable Input Checking. When enabled, the drive regularly monitors the state of the Drive Enable Input. This dedicated input enables the drive's power structure and servo loop. If cleared, no checking of the Drive Enable Input occurs.
Drive Enable Input Fault
Select to activate the Drive Enable Input Fault. When active, a fault detected on the external drive notifies the motion module via Drive Fault Input.
Real Time Axis Information Attribute 1/Attribute 2
Select up to two axis attributes whose statuses are transmitted – along with the actual position data – to the Logix processor. Access the values of the selected attributes using a GSV command or from the axis tag itself. This data is transmitted at a rate equal to the servo status data update time. If issuing a GSV command for servo status attribute, or using the value from the axis tag, without selecting this attribute via the Drive Info Select attribute, the attribute value is static and does not reflect the true value in the servo module. If the AXIS_SERVO_DRIVE is associated with a Kinetix Enhanced Safe Torque-Off or Advanced Safety Drive, these two additional Real Time Axis attributes are available. • Guard Status • Guard Faults If an AXIS_SERVO_DRIVE is associated with a Kinetix Advanced Safety Drive, we recommend configuring the Guard Status attribute. Otherwise, a warning appears when verifying the project.
130
If the AXIS_SERVO_DRIVE is associated with a Kinetix Advanced Safety Drive, and
Then
Attribute 1 or Attribute 2 is populated as Guard Status
No action is taken.
Attribute 1 or Attribute 2 is not populated as Guard Status
Attribute 2 is populated as Guard Status.
Attribute 2 is populated with an attribute other than Guard Status, and Attribute 1 is undefined
Attribute 1 is populated as Guard Status.
Attribute 1 and Attribute 2 are populated with an attribute other than Guard Status
Upon project verification, a warning is issued.