Page 131
Axis properties
Appendix A
Recalculations based on Motor Catalog Number When the Motor Catalog Number changes on the Drive/Motor tab, the controller recalculates these values. On this tab
These attributes are recalculated
Motor Feedback tab
Motor Feedback Type Motor Feedback Resolution
Gains tab
Position Proportional Gains Velocity Proportional Gains
Dynamics tab
Maximum Speed Maximum Acceleration Maximum Deceleration
Limits tab
Position Error Tolerance
Custom Stop Action Attributes dialog box
Stopping Torque
Custom Limit Attributes dialog box
Velocity Limit Bipolar Velocity Limit Positive Velocity Limit Negative Acceleration Limit Bipolar Acceleration Limit Positive Acceleration Limit Negative Torque Limit Bipolar Torque Limit Positive Torque Limit
Tune Bandwidth dialog box
Position Loop Bandwidth Velocity Loop Bandwidth
See also Conversion Constant on page 179 Change Catalog Number on page 132 Calculate Position Parameters on page 132
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
131
Page 132
Appendix A
Axis properties
Change Catalog Number
Use the Change Catalog Number dialog box to select the catalog number of the module used in the project.
Item
Description
Catalog Number
Lists the available catalog numbers based on the selection criteria from the fields in the Filters area.
Filters
Three optional fields refine the search of the Motor Database. Voltage
Narrows the search to a voltage rating. The default is all.
Family
Narrows the search to a family of motors. The default is all.
Feedback Type
Narrows the search to a feedback type. The default is all.
See also Drive/Motor tab - AXIS_SERVO_DRIVE on page 129
Calculate Position Parameters
Use the Calculate Position Parameters dialog box to calculate drive resolution and conversion constant values based on specific position unit scaling and position range information. The parameters available on dialog box depend on the Position Mode setting on the Conversion tab.
132
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 133
Axis properties
Appendix A
Position Mode set to Linear
Position Mode set to Rotary
Item
Description
Position Unit Scaling
Position Unit Scaling defines the relationship between the Position Units defined on the Units tab and the units selected to measure position.
per
The units used for Position Unit Scaling. The options are: Motor Inch, Motor Millimeter, or Motor Rev.
Position Range
Maximum travel limit that the system can go.
Position Unit Unwind
For Rotary applications, enter the value for the maximum number of unwinds in position units per unwind cycle.
Calculate Parameters
The Calculate Parameters shows the values to calculate based upon the values entered for the Position Unit Scaling and Position Range.
Calculate
Select to calculate the Drive Resolution and Conversion Constant values.
Drive Resolution
Recalculates the resolution based upon the new values entered on this dialog box.
Conversion Constant
Recalculates the Conversion Constant based upon the new values entered on this dialog box. When editing the setting for the Conversion Constant or the Drive Resolution, selecting OK or Apply, choose whether to also recalculate the settings for these dependent attributes. The attributes are recalculated. On the Dynamics tab: • Maximum Velocity • Maximum Acceleration • Maximum Deceleration On the Limits tab: • Position Error Tolerance On the Custom Drive Scaling Attributes dialog box: • Torque Data Scaling On the Custom Limit Attributes dialog box: • Velocity Limit Bipolar • Velocity Limit Positive • Velocity Limit Negative • Acceleration Limit Bipolar • Acceleration Limit Positive • Acceleration Limit Negative
Position Unwind
Recalculates the Position Unwind based upon the new values entered on this dialog box.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
133
Page 134
Appendix A
Axis properties
See also Drive/Motor tab - (AXIS_SERVO_DRIVE) on page 129
Motor Feedback tab AXIS_SERVO_DRIVE
Use the Motor Feedback tab to configure motor and auxiliary feedback device (if any) parameters for an axis of the type AXIS_SERVO_DRIVE.
The Axis Configuration selection made on the General tab, and the Loop Configuration selection made on the Drive tab determine which sections of this dialog box – Motor and Auxiliary Feedback – are enabled. Item
Description
Feedback Type
This field displays the type of feedback associated with the selected motor.
Cycles
The number of cycles of the associated feedback device. This helps the Drive Compute Conversion constant used to convert drive units to feedback counts. Depending on the feedback type selected, this value may be read-only or editable.
Per
The units used to measure the cycles.
Interpolation Factor
This field displays a fixed, read-only value for each feedback type. This value is used to compute the resolution of the feedback device.
Feedback Resolution
Provides the drive with the resolution of the associated feedback device in cycles.
Aux Feedback tab AXIS_SERVO_DRIVE
134
The Aux Feedback tab is enabled only if on the Driver tab, the Loop Configuration field is set to Aux Feedback Only, Aux Position Servo, Dual Position Servo, Dual Command Servo, or Aux Dual Command Servo. Use this
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 135
Axis properties
Appendix A tab to configure motor and auxiliary feedback device parameters for an axis of the type AXIS_SERVO_DRIVE.
Item
Description
Feedback Type
For applications that use auxiliary feedback devices, choose the type of auxiliary feedback device type. These are drive dependent.
Cycles
The number of cycles of the auxiliary feedback device. This helps the Drive Compute Conversion constant used to convert drive units to feedback counts. Depending on the feedback type selected, this value may be read-only or editable.
Per
The units used to measure the cycles.
Interpolation Factor
Displays a fixed constant value for the selected feedback type. This value is used to compute the resolution of the feedback device.
Feedback Resolution
Provides the drive with the resolution of the associated feedback device in cycles.
Feedback Ratio
Represents the quantitative relationship between the auxiliary feedback device and the motor. Select the Conversion tab to access the Axis Properties Conversion dialog box.
Conversion tab
Use the Conversion tab to view and edit the Positioning Mode, Conversion Constant, and if configured as Rotary, the Position Unwind values for an axis, of the tag types AXIS_SERVO, AXIS_SERVO_DRIVE and AXIS_VIRTUAL. The differences in the appearance of the Conversion tab for the AXIS_SERVO and AXIS_SERVO_DRIVE are the default values for Conversion Constant and Position Unwind and the labels for these values.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
135
Page 136
Appendix A
Axis properties
Item
Description
Positioning Mode
This parameter is not editable for an axis of the data type AXIS_CONSUMED. Instead, this value is taken from a producing axis in a networked Logix processor. This value can be edited for AXIS_SERVO, AXIS_SERVO_DRIVE and AXIS_VIRTUAL.
Conversion Constant
Linear
Provides a maximum total linear travel of 2.14 (231) billion feedback counts. With this mode, the unwind feature is disabled and allows limiting the linear travel distance of the axis by specifying the positive and negative travel limits for the axis.
Rotary
Enables the rotary unwind capability of the axis. This feature provides infinite position range by unwinding the axis position whenever the axis moves through a complete unwind distance. The number of encoder counts per unwind of the axis is specified in the Position Unwind field.
Number of feedback counts per position unit. This conversion or ‘K’ constant lets the axis position appear, and motion to be programmed, in the position units set in the Units tab. The conversion constant is used to convert axis position units into feedback counts and vice versa for the AXIS_SERVO type and for the AXIS_SERVO_DRIVE, the number of counts per motor revolution, as set on the Drive tab in the Drive Resolution field. When editing the setting for the Conversion Constant or the Drive Resolution and selecting OK or Apply, choose whether to also recalculate the settings for these dependent attributes. These attributes are recalculated. On the Dynamics tab: • Maximum Velocity • Maximum Acceleration • Maximum Deceleration On the Limits tab: • Position Error Tolerance On the Custom Drive Scaling Attributes dialog box: • Torque Data Scaling On the Custom Limit Attributes dialog box: • Velocity Limit Bipolar • Velocity Limit Positive • Velocity Limit Negative • Acceleration Limit Bipolar • Acceleration Limit Positive • Acceleration Limit Negative
Position Unwind
This parameter is not editable for an axis of the data type AXIS_CONSUMED. Instead, this value is taken from a producing axis in a networked Logix processor. For a Rotary axis (AXIS_SERVO): • This value represents the distance (in feedback counts) used to perform automatic electronic unwind. Electronic unwind allows infinite position range for rotary axes by subtracting the unwind distance from the actual and command position, every time the axis travels the unwind distance. For axes of the type AXIS_SERVO_DRIVE: • When saving an edited Conversion Constant or a Drive Resolution value, a message box opens, asking if the controller should automatically recalculate certain attribute settings. See Conversion Constant and Drive Resolution attributes. • The label indicates the number of counts per motor revolution, as set on the Drive tab in the Drive Resolution field.
136
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 137
Axis properties
Appendix A
Homing tab - AXIS_SERVO
Use the Homing tab to configure the attributes related to homing an axis of the type AXIS_SERVO.
Item
Description
Mode
Select the homing mode. Active
• Active mode - enables the axis at the beginning of the home process. • Active homing sequences use the trapezoidal velocity profile. For LDT and SSI feedback selections, the only valid Home Sequences for Homing Mode are Immediate or Switch, as no physical marker exists for the LDT or SSI feedback devices. • For SSI, the selections for Home Sequence are based on if ‘Enable Absolute Feedback’ is checked.
Passive
• The homing redefines the absolute position of the axis on the occurrence of a home switch or encoder marker event. • Passive homing is most commonly used to calibrate uncontrolled axes. Can also use passive homing with controlled axes to create a custom homing sequence. • Passive homing, for a given home sequence, works similar to the corresponding active homing sequence, except that no motion is commanded; the controller waits for the switch and marker events to occur.
Absolute
AXIS_SERVO_DRIVE, and AXIS_SERVO when associated with a 1756-HYD02 [LDT feedback] or 1756-M02AS [SSI feedback] module only. Absolute homing is only available on Axis_Servo_Drive if the position feedback devices support absolute homing. Absolute Homing is not available on a 1756-M02AS module if Enable Absolute Feedback is cleared. • The absolute homing process establishes the true absolute position of the axis by applying the configured Home Position to the reported position of the absolute feedback device. • The only valid Home Sequence for an absolute Homing Mode is Immediate. In the LDT and SSI cases, the absolute homing process establishes the true absolute position of the axis by applying the configured Home Position less any enabled Absolute Feedback Offset to the reported position of the absolute feedback device. • Before execution of the absolute homing process using the MAH instruction, the axis must be in the Axis Ready state with the servo loop disabled.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
137
Page 138
Appendix A
Axis properties
Item
Description No Physical Marker Pulse Exists For the SSI feedback transducer, no physical marker pulse exists. However, a pseudo marker reference is established by the M02AS module firmware at the feedback device’s roll over point. A single-turn Absolute SSI feedback device rolls over at its maximum ‘turns count’ = 1 rev. A multi-turn Absolute SSI feedback device (there are multiple revs or feedback-base unit-distances) rolls over at its maximum ‘turns count’, which is usually 1024 or 2048. Home to Rollover is available in the Homing Properties if Enable Absolute Feedback is disabled. If establishing the rollover of the feedback device, a ladder rung using an SSV to set Home_Sequence equal ‘Home to Rollover’ is available in the Homing Properties if Enable Absolute Feedback is disabled. Add these parameters to the application program: • Class Name = Axis, • Attribute_Name = Home_Sequence, • and Value = 2 (to Marker) These parameters cannot be set in Axis Properties. Reset back to the initial values: 0 = Immediate or 1 = Switch, after establishing the rollover. Set the Home Sequence to Marker to allow feedback to travel until the rollover (that is, pseudo marker) is found. Do this without the motor attached to any axis because this could cause up to a Maximum number of turns before pseudo marker is found.
Position
The desired absolute position, in position units, for the axis after the specified homing sequence is complete. In most cases, this position is set to zero, although any value within the software travel limits is acceptable. After the homing sequence is complete, the axis is left in this position. If the Positioning Mode (set in the Conversion tab) of the axis is Linear, then the home position should be within the travel limits, if enabled. If the Positioning Mode is Rotary, then the home position should be less than the unwind distance in position units.
Offset
The desired offset (if any) in position units the axis is to move, upon completion of the homing sequence, to reach the home position. In most cases, this value is zero.
Sequence
Choose the event that sets the Home Position. See the Homing Configurations section, for a detailed description of each combination of homing mode, sequence and direction.
Limit Switch
Sequence Type
Description
Immediate
Sets the Actual Position to the Home Position.
Switch
Sets the Actual Position to the Home Position when axis motion encounters a home limit switch.
Marker
Sets the Actual Position to the Home Position when axis encounters an encoder marker.
Switch-Marker
Sets the Actual Position to the Home position when a marker is encountered after a home switch is encountered.
If a limit switch is used, indicates the normal state of that switch (that is, before being engaged by the axis during the homing sequence): • Normally Open • Normally Closed
Direction
138
For active homing sequences, except for the Immediate Sequence type, select the desired homing direction. Direction
Description
Forward Uni-directional
The axis jogs in the positive axial direction until a homing event (switch or marker) is encountered, then continues in the same direction until axis motion stops (after decelerating or moving the Offset distance).
Forward Bi-directional
The axis jogs in the positive axial direction until a homing event (switch or marker) is encountered, then reverses direction until motion stops (after decelerating or moving the Offset distance).
Reverse Uni-directional
The axis jogs in the negative axial direction until a homing event (switch or marker) is encountered, then continues in the same direction until axis motion stops (after decelerating or moving the Offset distance).
Reverse Bi-directional
The axis jogs in the negative axial direction until a homing event (switch or marker) is encountered, then reverses direction until motion stops (after decelerating or moving the Offset distance).
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 139
Axis properties
Appendix A
Item
Description
Speed
Type the speed of the jog profile used in the first leg of an active homing sequence. The homing speed specified should be less than the maximum speed and greater than zero.
Return Speed
The speed of the jog profile used in the return leg(s) of an active homing sequence. The home return speed specified should be less than the maximum speed and greater than zero.
Homing tab AXIS_SERVO_DRIVE
Use the Homing tab to configure the attributes related to homing an axis of the type AXIS_SERVO_DRIVE.
Item
Description
Mode
Select the homing mode. Active
• Active enables the axis at the beginning of the home process. • The desired homing sequence is selected by specifying whether a home limit switch and/or the encoder marker is used for this axis. • Active homing sequences use the trapezoidal velocity profile. For LDT and SSI feedback selections, the only valid Home Sequences for Homing Mode are immediate or switch, as no physical marker exists for the LDT or SSI feedback devices.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
139
Page 140
Appendix A
Item
Axis properties
Description Passive
• In this mode, homing redefines the absolute position of the axis on the occurrence of a home switch or encoder marker event. • Passive homing is most commonly used to calibrate uncontrolled axes, although it can also be used with controlled axes to create a custom homing sequence. • Passive homing, for a given home sequence, works similar to the corresponding active homing sequence, except that no motion is commanded; the controller just waits for the switch and marker events to occur.
Passive Absolute
AXIS_SERVO_DRIVE and AXIS_SERVO when associated with a 1756-HYD02 [LDT feedback] or 1756-M02AS [SSI feedback] module only. • In this mode, the absolute homing process establishes the true absolute position of the axis by applying the configured Home Position to the reported position of the absolute feedback device. • The only valid Home Sequence for an absolute Homing Mode is immediate. In the LDT and SSI cases, the absolute homing process establishes the true absolute position of the axis by applying the configured Home Position less any enabled Absolute Feedback Offset to the reported position of the absolute feedback device. • Before execution of the absolute homing process using the MAH instruction, the axis must be in the Axis Ready state with the servo loop disabled. No Physical Marker Pulse Exists For the SSI feedback transducer, no physical marker pulse exists. However, a pseudo marker reference is established by the M02AS module firmware at the feedback device’s roll over point. A single-turn Absolute SSI feedback device rolls over at its maximum ‘turns count’ = 1 rev. A multi-turn Absolute SSI feedback device (there are multiple revs or feedback-base unit-distances) rolls over at its maximum ‘turns count’, which is usually 1024 or 2048. If establishing the rollover of the feedback device, add a ladder rung using an SSV to set Home_Sequence equal ‘Home to marker’ with these parameters: Class Name = SSI_Axis, Attribute_Name = Home_Sequence, and Value = 2 (to Marker) to the application program (cannot be set to Axis Properties and must be reset back to its initial value 0 = Immediate or 1 = Switch after establishing the rollover). Use the Home Sequence = to Marker to allow feedback to travel until the rollover (that is, pseudo marker) is found. Do this without the motor attached to any axis because this could cause up to the Maximum number of turns before pseudo marker is found.
Sequence
140
Position
Type the desired absolute position, in position units, for the axis after the specified homing sequence is complete. In most cases, this position is set to zero, although any value within the software travel limits can be used. After the homing sequence is complete, the axis is left in this position. If the Positioning mode (set in the Conversion tab) of the axis is Linear, then the home position should be within the travel limits, if enabled. If the Positioning mode is Rotary, then the home position should be less than the unwind distance in position units.
Offset
Type the desired offset (if any) in position units the axis is to move, upon completion of the homing sequence, to reach the home position. In most cases, this value is zero.
Choose the event that sets the Home Position. Immediate
Sets the Actual Position to the Home Position.
Switch
Sets the Actual Position to the Home Position when axis motion encounters a home limit switch.
Marker
Sets the Actual Position to the Home Position when axis encounters an encoder marker.
Switch-Marker
Sets the Actual Position to the Home position when a marker is encountered after a home switch is encountered.
Torque Level
Sets the Home Position when the specified Homing Torque level is achieved on the assigned axis. Important: For more information on the Home to Torque-level sequence, see Home to Torque-level Example Application Note, publication MOTION-AT001.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018