Page 111

Fast Module Features

Chapter 5

Troubleshooting Issue: I/O Module Connection Error or I/O Module Configuration Error (yellow triangle in Logix Designer I/O configuration) 1. Verify that both entries in the Logix Designer I/O Configuration have the same RPI. 2. Verify that both entries in the Logix Designer I/O Configuration have the same configuration. You can toggle the Sync_Module_Config BOOL tag in the IO_Mapping Program MainRoutine Rung 1. This will trigger a copy of the module A configuration to the module B configuration, making them the same. IMPORTANT

This copy will not change the module RPI. The two I/O module entries must have the same configuration.

3. Remove the module from the chassis. 4. Reinsert the module. 5. If you still have the error, delete one of the module entries in the Logix Designer I/O Configuration and add it into your project again. These troubleshooting steps below assume that the system was commissioned and running without any errors before the issue occurred. Issue: Output is ON in the user application code, but is not ON at the Output module. 1. Verify that at least one of the connections to the output module is active. 2. Verify that the output is ON in the output module tags. 3. Confirm whether all of the connections in the chassis are faulted, including the Ethernet modules. 4. Troubleshoot the Ethernet communication issue to the Ethernet modules. 5. Troubleshoot the error code displayed in Module Properties > Connection tab.

In the example project, this is EN2T_B.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

111

Page 112

Chapter 5

Fast Module Features

Issue: Incorrect output behavior on response 1. Verify that only one of the connections to the Output module has the .OwnerClaim output set to true (1). 2. Verify that only one of the connections to the Output module has the .OwnerReady output set to true (1).

For all of the issues described in this section, you can consult product manuals, Rockwell Automation® KnowledgeBase, and Rockwell Automation Technical Support.

112

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 113

Chapter

6

Install ControlLogix I/O Modules

Topic

Page

Install the Module

115

Key the Removable Terminal Block

117

Connect the Wires

118

Assemble the Removable Terminal Block and Housing

122

Choose Extended-depth Housing

123

Install the Removable Terminal Block

125

Remove the Removable Terminal Block

127

Remove the Module from the Chassis

128

Table 28 - Environment and Enclosure

ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments. This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that are present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. In addition to this publication, see the following: • Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for additional installation requirements. • NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

113

Page 114

Chapter 6

Install ControlLogix I/O Modules

Table 29 - North American Hazardous Location Approval The following information applies when operating this equipment in hazardous locations.

Informations sur l’utilisation de cet équipement en environnements dangereux.

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.

WARNING: EXPLOSION HAZARD

WARNING: RISQUE D’EXPLOSION

• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous. • Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product. • Substitution of components may impair suitability for Class I, Division 2. • If this product contains batteries, they must only be changed in an area known to be nonhazardous.

• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement. • Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit. • La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2. • S'assurer que l'environnement est classé non dangereux avant de changer les piles.

Table 30 - European Hazardous Location Approval The following applies when the product bears the Ex Marking. This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive. Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.

ATTENTION: This equipment is not resistant to sunlight or other sources of UV radiation.

WARNING: • This equipment must be installed in an enclosure providing at least IP54 protection when applied in Zone 2 environments. • This equipment shall be used within its specified ratings defined by Rockwell Automation. • Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40% when applied in Zone 2 environments. • This equipment must be used only with ATEX certified Rockwell Automation backplanes. • Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product. • Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.

114

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 115

Install ControlLogix I/O Modules

Install the Module

Chapter 6

You can install or remove a ControlLogix® I/O module while chassis power is applied. Removal and Insertion Under Power (RIUP) provides the flexibility to maintain modules without having to stop production. WARNING: When you insert or remove the module while backplane power is on, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electric arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation. ATTENTION: Although the module is designed to support RIUP, when you remove or insert a module or an RTB with field-side power applied, unintended machine motion or loss of process control can occur. Exercise extreme caution when using this feature. ATTENTION: Prevent Electrostatic Discharge This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static. • Wear an approved grounding wriststrap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment. • Use a static-safe workstation, if available. • Store the equipment in appropriate static-safe packaging when not in use.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

115

Page 116

Chapter 6

Install ControlLogix I/O Modules

Follow these steps to insert the module into the chassis. 1. Align the circuit board with the top and bottom chassis guides.

Printed Circuit Board

20861-M

2. Slide the module into the chassis until the locking tabs click.

20862-M

Installation of the module is now complete.

116

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 117

Install ControlLogix I/O Modules

Key the Removable Terminal Block

Chapter 6

Key the removable terminal block (RTB) to prevent inadvertently connecting the wrong wiring in the RTB to your module. Wedge- and U-shaped bands are manually inserted into the RTB and module. This process hinders a wired RTB from being accidentally inserted into a module that does not match the positioning of the respective tabs. Key positions on the module that correspond to unkeyed positions on the RTB. For example, if you place a U-shaped keying band in slot 4 on the module, do not insert a wedge-shaped tab in slot 4 on the RTB, or your RTB does not mount on the module. We recommend that you use a unique keying pattern for each slot in the chassis. Follow these steps to key the RTB. 1. To key the module, insert the U-shaped band with the longer side near the terminals. 2. Push the band onto the module until it snaps into place.

20850-M

3. To key the RTB in positions that correspond to unkeyed module positions, insert the straight, wedge-shaped tab on the RTB with the rounded edge first.

Module side of RTB

0

12

3

45

67

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

20851-M

117

Page 118

Chapter 6

Install ControlLogix I/O Modules

4. Push the tab onto the RTB until it stops. 5. Repeat step 1…step 4 by using additional U-shaped and straight tabs until the module and RTB lock into each other properly.

Connect the Wires

You can use an RTB or a Bulletin 1492 prewired interface module (IFM)(1) to connect wires to your module. If you are using an RTB, follow the directions to connect wires to the RTB. IFMs are wired prior to shipping. WARNING: If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

ATTENTION: If multiple power sources are used, do not exceed the specified isolation voltage.

ATTENTION: When using the 1756-TBCH, do not wire more than two 0.33...1.3 mm2 (22...16 AWG) conductors on any single terminal. Use only the same size wires with no intermixing of solid and stranded wire types. When using the 1756-TBS6H, do not wire more than 1 conductor on any single terminal. When using the 1756-TBNH, do not wire more than two 0.33...2.1 mm2 (22...14 AWG) conductors on any single terminal. Use only the same size wires with no intermixing of solid and stranded wire types. When using the 1756-TBSH, do not wire more than 1 conductor on any single terminal. To see a listing of the IFMs available for use with the ControlLogix analog I/O modules, see Appendix G. This chapter explains the general guidelines for wiring your digital I/O modules, including grounding the cable and connecting the wires to each RTB type. Table 35 on page 139 shows each module catalog number and the corresponding page with the wiring diagram.

(1) The ControlLogix system has been agency certified using only the ControlLogix RTBs (1756-TBCH, 1756-TBNH, 1756-TBSH and 1756-TBS6H). Any application that requires agency certification of the ControlLogix system using other wiring termination methods may require application specific approval by the certifying agency

118

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 119

Install ControlLogix I/O Modules

Chapter 6

RTB Types There are three types of RTBs: • Cage Clamp - catalog number 1756-TBCH • NEMA Clamp - catalog number 1756-TBNH • Spring Clamp - catalog number 1756-TBSH or TBS6H Each RTP comes with housing. Wire the RTB with a 3.2 mm (1/8 in.) maximum screwdriver before installing it onto the module.

Cage Clamp Follow these steps to wire a cage clamp. 1. Strip 9.5 mm (3.8 in.) maximum length of wire. 2. Insert the wire into the open terminal on the side. 3. Turn the screw clockwise to close the terminal on the wire.

Strain Relief Area 20859-M

The open section at the bottom of the RTB is called the strain relief area. The wiring from the connections can be grouped with a plastic tie.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

119

Page 120

Chapter 6

Install ControlLogix I/O Modules

NEMA Clamp Follow these steps to wire a NEMA clamp. 1. Strip 8 mm (5/16 in.) maximum length of wire. 2. Turn the terminal screw counterclockwise. 3. Insert the stripped end of the wire under the plate on the terminal.

Strain Relief Area 40201-M

4. Turn the terminal screw clockwise until the wire is secured. The open section at the bottom of the RTB is called the strain relief area. The wiring from the connections can be grouped with a plastic tie.

Spring Clamp Follow these steps to wire a spring clamp. 1. Strip 11 mm (7/16 in.) maximum length of wire. 2. Insert the screwdriver into the outer hole of the RTB to depress the spring-loaded clamp. 3. Insert the wire into the open terminal and remove the screwdriver.

Strain Relief Area 20860-M

120