Page 121

Install ControlLogix I/O Modules

IMPORTANT

Chapter 6

Make sure the wire, and not the screwdriver, is inserted into the open terminal to prevent damage to the module.

The open section at the bottom of the RTB is called the strain relief area. The wiring from the connections can be grouped with a plastic tie.

RTB Wiring Recommendations Consider these guidelines when wiring your RTB: • Begin wiring the RTB at the bottom terminals and move up. • Use a tie to secure the wires in the strain relief area of the RTB. • A jumper bar is shipped with certain I/O modules to assist in installation. For an example of when to use the jumper bar, see the 1756-IA16I wiring diagram. Extra jumper bars can be purchased by ordering catalog number 1756-JMPR. • For applications that require heavy gauge wiring, order and use an extended-depth housing, catalog number 1756-TBE. For more information, see page 123.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

121

Page 122

Chapter 6

Install ControlLogix I/O Modules

Assemble the Removable Terminal Block and Housing

Removable housing covers the wired RTB to protect wiring connections when the RTB is seated on the module. Parts of the 1756-TBCH RTB (for example) are identified in the table.

1

2 3

5

2 3 4

20858-M

Item

Description

1

Housing cover

2

Groove

3

Side edge of RTB

4

RTB

5

Strain relief area

Follow these steps to attach the RTB to the housing. 1. Align the grooves at the bottom of each side of the housing with the side edges of the RTB. 2. Slide the RTB into the housing until it snaps into place. IMPORTANT

122

If additional wire routing space is required for your application, use extended-depth housing, catalog number 1756-TBE.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 123

Install ControlLogix I/O Modules

Choose Extended-depth Housing

Chapter 6

There are two housing options you must consider when wiring your ControlLogix digital I/O module: standard-depth or extended-depth. When you order an RTB for your I/O module, you receive standard-depth housing. If your application uses heavy gauge wiring, you can order extendeddepth housing. Extended-depth housing does not come with an RTB. Standard-depth Housing

Extended-depth Housing

30484-M

IMPORTANT

The housings shown are used with a spring clamp RTB, but the capacity for each remains the same regardless of RTB type.

Cat. No.

RTB Type

Wire Capacity

Number of Wires

1756-TBNH

NEMA clamp

1756-TBSH

Spring clamp (20-position)

Standard-depth 336 mm2 (0.52 in.2)

36…18 AWG wires 23…14 AWG wires

1756-TBCH

Cage clamp

1756-TBS6H

Spring clamp (36-position)

1756-TBE

Any RTB that uses heavy gauge wiring

Extended-depth 628 mm2 (0.97 in.2)

40…18 AWG wires

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

123

Page 124

Chapter 6

Install ControlLogix I/O Modules

Cabinet Size Considerations with Extended-depth Housing When you use extended-depth housing, catalog number 1756-TBE, the I/O module depth is increased. The diagram shows the difference in depth between an I/O module using standard-depth housing and one using extended-depth housing. Dimensions are in mm (in.) 144.73 (5.698) 12.7 (0.5)

131.75 (5.187) 3.18 (0.125)

Rear Surface of ControlLogix Chassis

Standard-depth Housing

Extended-depth Housing

41682

IMPORTANT

124

The depth from the front of the module to the back of the chassis is as follows: • Standard-depth housing = 147.91 mm (5.823 in.) • Extended-depth housing = 157.43 mm (6.198 in.)

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 125

Install ControlLogix I/O Modules

Install the Removable Terminal Block

Chapter 6

This section shows how to install the RTB onto the module to connect the wiring. WARNING: When you connect or disconnect the removable terminal block (RTB) with field-side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

SHOCK HAZARD: If the RTB is installed onto the module while the field-side power is applied, the RTB is electrically live. Do not touch the RTB’s terminals. Failure to observe this caution may cause personal injury. The RTB is designed to support removal and insertion under power (RIUP). However, when you remove or insert an RTB with field-side power applied, unintended machine motion or loss of process control can occur. Exercise extreme caution when using this feature. It is recommended that field-side power be removed before installing the RTB onto the module. Before installing the RTB, make certain of the following: • • • •

Field-side wiring of the RTB has been completed RTB housing is snapped into place on the RTB RTB housing door is closed The locking tab at the top of the module is unlocked

To install the RTB, follow these steps. 1. Align the top, bottom and left side guides of the RTB with the guides on the module.

Top Guide

Bottom Guide 20853-M

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

125

Page 126

Chapter 6

Install ControlLogix I/O Modules

2. Press quickly and evenly to seat the RTB on the module until the latches snap into place. 3. Slide the locking tab down to lock the RTB onto the module.

20854-M

126

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 127

Install ControlLogix I/O Modules

Remove the Removable Terminal Block

Chapter 6

If you need to remove the module from the chassis, you must first remove the RTB from the module. SHOCK HAZARD: If the RTB is removed from the module while the field-side power is applied, the module is electrically live. Do not touch the RTB’s terminals. Failure to observe this caution may cause personal injury. The RTB is designed to support removal and insertion under power (RIUP). However, when you remove or insert an RTB with field-side power applied, unintended machine motion or loss of process control can occur. Exercise extreme caution when using this feature. It is recommended that field-side power be removed before removing the module. Follow these steps to remove an RTB from the module. 1. Unlock the locking tab at the top of the module. 2. Open the RTB door by using the bottom tab. 3. Hold the spot marked PULL HERE and pull the RTB off the module.

SHOCK HAZARD: Do not wrap your fingers around the entire door.

20855-M

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

127

Page 128

Chapter 6

Install ControlLogix I/O Modules

Remove the Module from the Chassis

Follow these steps to remove a module from its chassis. 1. Push in the top and bottom locking tabs.

20856-M

2. Pull module out of the chassis.

20857-M

128

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 129

Chapter

7

Configure ControlLogix Digital I/O Modules

Topic

Page

Configuration Process Overview

130

Create a New Module

131

Edit the Configuration

136

Connection Properties

137

View and Change Module Tags

138

You must configure your module upon installation. The module does not work until it has been configured. In most cases, you will use the Studio 5000 Logix Designer® application to complete the configuration. The application uses default configurations, such as RPI and filter times, to get your I/O module to communicate with its owner-controller. You can edit the default configuration as needed from the Module Properties dialog box.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

129

Page 130

Chapter 7

Configure ControlLogix Digital I/O Modules

Follow these steps to configure a ControlLogix® digital I/O module with Logix Designer.

Configuration Process Overview

1. Create a new module. 2. Accept or customize the default configuration for the module. 3. Edit the configuration as changes are needed. Figure 22 - Full Configuration Profile Diagram New Module 1. Choose a module from the list. 2. Choose a Major Revision.

Click a tab/category to customize the configuration.

Naming Screen Name Slot number Communication/ connection format Minor revision Keying choice

Click OK to use the default configuration. OK Button

Tab/Category

Series of Application Specific Screens

Configuration Complete

Edit Configuration

A series of tabs in the programming software enable you to change a module’s configuration.

41058

130

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017