ControlLogix Digital I/O Modules User Manual: ControlLogix Digital I/O Modules User Manual, pages 131 to 140

Pages 131 to 140 of 258, from ControlLogix Digital I/O Modules User Manual

The original document is the PDF (7.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1756-OB16E

Page 131

Configure ControlLogix Digital I/O Modules

Create a New Module

Chapter 7

Before creating a new module, make sure you complete these procedures in the Logix Designer application: • Create a controller project. • If you plan to add the I/O module to a remote chassis, add ControlNet or EtherNet/IP communication modules to both the local and remote chassis in the I/O Configuration tree. – For more information on ControlLogix ControlNet modules, see ControlNet Modules in Logix5000™ Control Systems, publication CNET-UM001. – For more information on ControlLogix EtherNet/IP modules, see EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication ENET-UM001. IMPORTANT

The Studio 5000® environment lets you add I/O modules online. When using a previous version, you must be offline to create a new module.

Follow these steps to add a local or remote I/O module. 1. To add an I/O module to a local chassis, right-click the I/O Configuration folder and choose New Module. or To add an I/O module to a remote chassis, right-click the remote communication module, and choose New Module. 2. On the Select Module Type dialog box, select the digital module to create, and then click Create.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

131

Page 132

Chapter 7

Configure ControlLogix Digital I/O Modules

3. On the Select Major Revision dialog box, click OK to accept the default major revision.

4. On the New Module dialog box, complete the fields and click OK. • For information about how to choose an electronic keying method, see page 40. • For information about how to choose a communication format or connection type, see page 136. The fields on the New Module dialog box vary depending on the catalog number of your I/O module.

To edit the module’s configuration, make sure the Open Module Properties checkbox is checked.

Click Change to open the Module Definition dialog box and choose additional properties, such as an electronic keying method and connection format.

132

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 133

Configure ControlLogix Digital I/O Modules

Chapter 7

Module Definitions, Communication or Connection Formats The initial configuration of a module requires you to choose a module definition or a communication or connection format. The term that is used depends on the Add-on Profile (AOP) for your module. Earlier AOPs use communication formats, later AOPs use connection formats, and the newest AOPs use module definitions. A module definition or communication or connection format determines the following: • Available configuration options • Type of data that is transferred between the module and its ownercontroller • Which tags are generated when the configuration is complete IMPORTANT

Communication formats cannot be changed whether online or offline after a program is downloaded to the controller. However, connection formats can be changed when offline after a program is downloaded to the controller.

The communication or connection format also defines the connection between the controller writing the configuration and the module. The number and type of choices varies depending on what module you are using and whether it is in a local or remote chassis. TIP

When you choose a Listen-only format, only the General and Connection tabs appear when you view a module’s properties in Logix Designer. Controllers that want to listen to a module but not own it use a Listen-only format.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

133

Page 134

Chapter 7

Configure ControlLogix Digital I/O Modules

Tables 31 and 32 describe the communication and connection formats available for input modules. Table 31 - Input Module Communication Formats Communication Format

Data Return

Module

Input Data

Module returns only general fault and input data.

CST Timestamped Input Data

Module returns input data with the value of the system clock from its local chassis when the input data changes.

1756-IA16, 1756-IA16I, 1756-IA32, 1756-IB16I, 1756-IB16, 1756-IB32, 1756-IC16, 1756-IG16, 1756-IH16I, 1756-IM16I, 1756-IN16, 1756-IV16, 1756-IV32

Rack Optimization

The 1756-CNB module collects all digital input words in the remote chassis and sends them to the controller as a single rack image. This connection type limits the status and diagnostic information available.

Listen Only - Input Data

These formats have the same definition as the similarly-named options above except that they are Listen-only connections.

Listen Only - CST Timestamped Input Data Listen Only - Rack Optimization Full Diagnostic Input Data

Module returns input data, the value of the system clock from its local chassis when the input data changes, and diagnostic data.

1756-IA8D, 1756-IB16D

Listen Only - Full Diagnostic Input Data

This format has the same definition as Full diagnostic input data except that it is a Listen-only connection.

1756-IA8D, 1756-IB16D

Table 32 - Input Module Module Definitions Connection

Input Data

Data Return

Module

Data

Timestamp Data

Module returns input data with COS timestamps in CIP Sync system time. To configure per point timestamping, see page 83.

1756-IB16IF

Data

Module returns input data without COS timestamps. This format is useful when the highest possible throughput is required.

Data with Event

Timestamp Data

Results in two input connections: • Connection to return input data with COS timestamps in CIP Sync system time. • Connection to initiate event tasks. See page 89.

Listen Only

Timestamp Data

These formats have the same definition as those above except that they are Listen-only connections.

Data Listen Only with Event

134

Timestamp Data

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 135

Configure ControlLogix Digital I/O Modules

Chapter 7

Tables 33 and 34 describe the communication and connection formats available for output modules. Table 33 - Output Module Communication Formats Communication Format

Data Return

Module

Output Data

The owner-controller sends the module only output data.

Scheduled Output Data

The owner-controller sends the module output data and a CST timestamp value

Rack Optimization

The owner-controller sends all digital output words to the remote chassis as a single rack image.

1756-OA8, 1756-OA16I, 1756-OB8, 1756-OB8I, 1756-OB16I, 1756-OB16IS(1), 1756-OB32, 1756-OC8, 1756-OG16, 1756-OH8I, 1756-ON8, 1756-OW16I, 1756-OX8I

Listen Only - Output Data

These formats have the same definition as those above except that they are Listen-only connections.

Listen Only - Rack Optimization CST Timestamped Fuse Data - Output Data

The owner-controller sends the module only output data. The module returns fuse blown status with the value of the system clock (from its local chassis) when the fuse is either blown or reset.

CST Timestamped Fuse Data - Scheduled Output Data

The owner-controller sends the module output data and a CST timestamp value. The module returns fuse blown status with the value of the system clock (from its local chassis) when the fuse is either blown or reset.

1756-OA16, 1756-OA8E, 1756-OB16E, 1756-OB8EI, 1756-OV16E, 1756-OV32E

Listen Only - CST Timestamped Fuse Data - Output Data This choice has the same definition as CST timestamped fuse data output data except that it is a Listen-only connection. Full Diagnostics - Output Data

The owner-controller sends the module only output data. The module returns diagnostic data and a timestamp of diagnostics.

Full Diagnostics - Scheduled Output Data

The owner-controller sends the module output data and a CST timestamp value. The module returns diagnostic data and a timestamp of diagnostics.

Listen Only - Full Diagnostics - Output Data

This format has the same definition as Full diagnostics - output data except that it is a Listen-only connection.

Scheduled Output Data per Point

The owner-controller sends the module output data and a CST timestamp value.

1756-OA8D, 1756-OB16D

1756-OB16IS only

(1) The 1756-OB16IS module does not support the Rack optimization, Listen only - rack optimization and Scheduled output data communication formats.

Table 34 - Output Module Module Definitions Connection

Output Data

Data Return

Module

Data

Data

The owner-controller sends the module only output data.

1756-OB16IEF, 1756-OB16IEFS

Scheduled Per Module

The owner-controller sends the module output data and a CIP Sync timestamp value.

1756-OB16IEF

Scheduled Per Point

The owner-controller sends output data and a CIP Sync timestamp value to points configured for scheduling.

1756-OB16IEFS

Listen Only

None

Establishes a Listen-only connection with no data.

1756-OB16IEF, 1756-OB16IEFS

Peer Input with Data

Data with Peer

Establishes a Listen-only connection to input peer modules. See the Peer Ownership Application Technique, publication 1756-AT016.

1756-OB16IEF

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

135

Page 136

Chapter 7

Configure ControlLogix Digital I/O Modules

Edit the Configuration

After you add a module to the I/O configuration in Logix Designer, you can review and edit the configuration. You can also download the data to the controller while online. This is called dynamic reconfiguration. Follow these steps to edit a module’s configuration. 1. On the Controller Organizer, right-click an I/O module and choose Properties.

2. On the Module Properties dialog box, click the tab/category corresponding to the feature to modify, and then click OK: • To configure connection properties between the module and the controller, see page 137. • To configure features common to all modules, see Chapter 3. • To configure features specific to diagnostic modules, see Chapter 4. • To configure features specific to fast modules, see Chapter 5.

136

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 137

Configure ControlLogix Digital I/O Modules

Connection Properties

Chapter 7

Connection properties define controller-to-module behavior. When defining connection properties, you can do the following: • Select a requested packet interval (RPI) to set a defined, maximum period of time when data is transferred to the owner-controller • Choose to inhibit the module • Configure the controller so that a loss of connection to this module causes a major fault • View information about the condition of the connection between the module and the controller Follow these steps to configure connection properties. 1. On the Module Properties dialog box, click the Connection tab/category.

2. Complete the fields as described and click OK. Field

Description

Requested Packet Interval (RPI)

Enter an RPI value or use the default. See RPI in Chapter 2 for more information.

Inhibit module

Check the box to prevent communication between the owner-controller and the module. This option enables maintenance of the module without faults being reported to the controller. See Module Inhibiting in Chapter 3 for more information.

Major fault On Controller If Connection Fails While in Run Mode

Check the box to create a major fault if there is a connection failure with the module while in Run mode. For important information on this checkbox, see the Logix5000 Controllers Information and Status Programming Manual, publication 1756-PM015.

Module Fault

The fault box is empty if you are offline. The type of connection fault appears in the text box if a fault occurs when the module is online.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

137

Page 138

Chapter 7

Configure ControlLogix Digital I/O Modules

View and Change Module Tags

When you create a module, a set of tags is created by the ControlLogix system that can be viewed in the Tag Editor of Logix Designer. Each configured feature on your module has a unique tag that can be used in the controller’s program logic. Follow these steps to access a module’s tags. 1. On the Controller Organizer, expand the Controller folder, right-click Controller Tags, and choose Monitor Tags.

The Controller Tags dialog box appears with data. 2. Expand the slot number of the module for which to view information. See Appendix B for details on viewing and changing a module’s configuration tags.

138

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 139

Chapter

8

Wiring Diagrams

This chapter provides wiring diagrams for all ControlLogix® digital modules. Table 35 - Wiring Diagrams by Catalog Number Cat. No.

Page

Cat. No.

Page

1756-IA8D

141

1756-OA16I

159

1756-IA16

141

1756-OB8

160

1756-IA16I

142

1756-OB8EI

161

1756-IA32

143

1756-OB8I

162

1756-IB16

144

1756-OB16D

163

1756-IB16D

145

1756-OB16E

164

1756-IB16I

146

1756-OB16I

167

1756-IB16IF

147

1756-OB16IEF

168

1756-IB32

148

1756-OB16IEFS

169

1756-IC16

149

1756-OB16IS

170

1756-IG16

150

1756-OB32

171

1756-IH16I

151

1756-OC8

172

1756-IM16I

152

1756-OG16

173

1756-IN16

152

1756-OH81

174

1756-IV16

153

1756-ON8

175

1756-IV32

154

1756-OV16E

176

1756-OA8

155

1756-OV32E

177

1756-OA8D

156

1756-OW16I

178

1756-OA8E

157

1756-OX8I

178

1756-OA16

158

Table 36 - Types of Digital I/O Modules Digital I/O Type

Description

Diagnostic

These modules provide diagnostic features to the point level. These modules have a D at the end of the catalog number.

Electronic fusing

These modules have internal electronic fusing to prevent too much current from flowing through the module. These modules have an E at the end of the catalog number.

Individually isolated

These modules have individually isolated inputs or outputs. These modules have an I at the end of the catalog number.

Fast

These modules provide fast response times. These modules have an F at the end of the catalog number.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

139

Page 140

Chapter 8

Wiring Diagrams

The 1756 digital I/O modules support these features. Table 37 - 1756 I/O Module Features Module Type

Features

1756 digital AC input modules

• • • •

1756 digital AC output modules

• • • •

Scheduled outputs: Synchronization within 16.7 seconds maximum, reference to the Coordinated System Time Fault states per point: Hold last state, on or off (off is default) States in Program mode per point: Hold last state, on or off (off is default) Fusing: – 1756-OA8D, 1756-OA8E: Electronically fused per point – 1756-OA16: Mechanically fused/group, 3.15 A @ 250V AC slow blow, 1500 A interruption current, Littelfuse p/n H2153.15 – All other modules: Not protected. A fused IFM is recommended to protect outputs (see publication 1492-TD008) • Module keying: Electronic, software configurable • RTB keying: User-defined mechanical

1756 digital DC input modules

• Reverse polarity protection: All modules except 1756-IG16 module • Change of state: Software configurable • Timestamp of inputs: – ±100 μs for sequence of events modules(1) – ±200 μs for all other modules • Module keying: Electronic, software configurable • RTB Keying: User-defined mechanical

1756 digital DC output modules

• • • •

Scheduled outputs: Synchronization within 16.7 seconds maximum, reference to the Coordinated System Time Fault states per point: Hold last state, on or off (off is default) States in Program mode per point: Hold last state, on or off (off is default) Fusing: – 1756-OB8EI, 1756-OB16D, 1756-OB16E, 1756-OB16IEF, 1756-OB16IEFS, 1756-OV16E, 1756-OV32E: Electronically fused per point – All other modules not protected. A fused IFM is recommended to protect outputs. See publication 1492-TD008. • Module keying: Electronic, software configurable • RTB keying: User-defined mechanical

1756 digital contact modules

• • • • • •

Change of state: Software configurable Timestamp of inputs: ±200 μs Module keying: Electronic, software configurable RTB keying: User-defined mechanical

Scheduled outputs: Synchronization within 16.7 seconds maximum, reference to the Coordinated System Time Configurable fault states per point: Hold last state, on or off (off is default) Configurable states in Program mode per point: Hold last state, on or off (off is default) Fusing: Not protected. A fused IFM is recommended to protect outputs (See publication 1492-TD008) Module keying: Electronic, software configurable RTB keying: User-defined mechanical

(1) For details, see the ControlLogix Sequence of Events Module Installation Instructions, publication 1756-IN592, and the ControlLogix Sequence of Events Module User Manual, publication 1756-UM528.

IMPORTANT

140

For the latest I/O module specifications, see the 1756 ControlLogix I/O Modules Technical Specifications, publication 1756-TD002.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017